| 2016-03-07 12:24:34 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | ELECTRICAL REVIEW COMMENTS. |
| | |
| | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. 2014 FBC R314, 315 |
| | |
| | UPDATE THE LOAD CALCULATION TO INCLUDE THE ADDITIONAL |
| | APPLIANCE BRANCH CIRCUITS, DRYERS, OVENS, MOTORS AND |
| | THE FIRST 10 K OF THE GENERAL LIGHTING LOAD. NEC |
| | 220.82, FBC R E3704.4 |
| | |
| | PROVIDE THE LOCATION OF THE POOL PANEL AND ELECTRIC |
| | SERVICE. NEC 215.5, FBC R E3704 |
| | |
| | THE SWIMMING POOL PUMP REQUIRES GFCI PROTECTION. NEC |
| | 680.21(C), FBC R E4203.1.3 |
| | |
| | A GFCI RECEPTACLE IS REQUIRED ON THE PATIO MORE THAN |
| | SIX FEET FROM THE POOL. NEC 680.22(A) 3, FBC R |
| | E4203.1.2 |
| | |
| | PROVIDE A 20 AMP LAUNDRY CIRCUIT. NEC 210.11 (C) (2); |
| | FBC R E3703.3 |
| | |
| | VERIFY ALL NEW CIRCUITS ARE AFCI PROTECTED. NEC 210.12; |
| | FBC R E3902.12 |
| | |
| | VERIFY ALL NEW RECEPTACLES ARE TAMPER RESISTANT. NEC |
| | 406.2; FBC R E4002.14 |
| | |
| | VERIFY RECEPTACLES ARE PROPERLY PLACED TO SERVICE ALL |
| | AREAS INCLUDING WALL SPACES TWO FEET OR MORE IN WIDTH. |
| | NEC 210.52 (A), FBC R E3901.2 |
| | |
| | |