2016-03-07 12:24:34PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2014 FBC R314, 315
  
 UPDATE THE LOAD CALCULATION TO INCLUDE THE ADDITIONAL
 APPLIANCE BRANCH CIRCUITS, DRYERS, OVENS, MOTORS AND
 THE FIRST 10 K OF THE GENERAL LIGHTING LOAD. NEC
 220.82, FBC R E3704.4
  
 PROVIDE THE LOCATION OF THE POOL PANEL AND ELECTRIC
 SERVICE. NEC 215.5, FBC R E3704
  
 THE SWIMMING POOL PUMP REQUIRES GFCI PROTECTION. NEC
 680.21(C), FBC R E4203.1.3
  
 A GFCI RECEPTACLE IS REQUIRED ON THE PATIO MORE THAN
 SIX FEET FROM THE POOL. NEC 680.22(A) 3, FBC R
 E4203.1.2
  
 PROVIDE A 20 AMP LAUNDRY CIRCUIT. NEC 210.11 (C) (2);
 FBC R E3703.3
  
 VERIFY ALL NEW CIRCUITS ARE AFCI PROTECTED. NEC 210.12;
 FBC R E3902.12
  
 VERIFY ALL NEW RECEPTACLES ARE TAMPER RESISTANT. NEC
 406.2; FBC R E4002.14
  
 VERIFY RECEPTACLES ARE PROPERLY PLACED TO SERVICE ALL
 AREAS INCLUDING WALL SPACES TWO FEET OR MORE IN WIDTH.
 NEC 210.52 (A), FBC R E3901.2
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER