| Plan Review Notes For Permit 16020613 |
| Permit Number |
16020613 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-23 06:24:07 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1.PLEASE LABEL FLOOR PLAN ROOM #112 RECEPTACLES WITHIN | | | 6FT OF SINK TO BE GFCI PROTECTED PER NEC 210.8B5 | | | 2.CLARIFY IF SHOW WINDOW RECEPTACLES REQUIRED PER NEC | | | 210.62- 220.14G, NOT SHOWN ON FLOOR PLAN OR PANEL LOAD | | | SCHEDULES. | | | 3.SHOW ON FLOOR PLAN EXISTING WP/GFCI RECEPTACLE FOR | | | SERVICE AT THE A/C LOCATION WITHIN 25 FT OF UNIT PER | | | NEC 210.63, CIRCUIT H-8 | | | 4.CLARIFY REQUIRED BRANCH CIRCUIT FOR DEDICATED SIGN | | | OUTLET PER NEC 600.5A | | | 5.PLEASE CORRECT PANEL SCHEDULE H-15, 17 THAT SHOWS A | | | 60 AMP OVERCURRENT FOR THE RTU#3 WITH A #12 CONDUCTOR. | | | CORRECT TYPO TO REFLECT ACTUAL CONDUCTOR SIZE BASED ON | | | NEC 310.15B16. | | | 6.PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|