| Date |
Text |
| 2016-03-14 16:55:42 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT : 16020613 |
| | ADD: : 310 EVERNIA ST. |
| | CONT: ANDERSON MOORE |
| | TEL: 662-1819 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY/ MARCH 14/ 2016 |
| | ACTION: DENIED |
| | |
| | 1A) THE RENDERING ON THE FRONT COVER IS DECEIVING IT |
| | APPEARS THAT YOU ARE VIEWING THROUGH THE FRONT GLAZING |
| | OF THE BUILDING INTO A HOLLOW TUBE ABOVE THE CONFERENCE |
| | ROOM. SHEET 004_A1.1.1 SHOWS A CROSS SECTION THROUGH |
| | THE LENGTH OF THE CONFERENCE ROOM NORTH TO SOUTH, BUT |
| | IT ACTUALLY ONLY SHOWS THE GLASS WALL, IT DOES NOT |
| | PROVIDE A DETAIL THROUGH THE GLASS WALL ONLY. SHEET |
| | 005_A1.1.2 THE CEILING PLANS ALSO SHOW A SECTION |
| | THROUGH THE CEILING/ SOFFIT DETAIL 2/ A3.01 BUT THIS IS |
| | THE SAME GLASS WALL. |
| | |
| | 1B) PLEASE PROVIDE BOTH A SECTION NORTH/SOUTH THROUGH |
| | THE SOFFIT AREA AS WELL AS EAST WEST, PLEASE INCLUDE |
| | THE WALL THAT SEPARATES THE 2ND CONFERENCE ROOM AND |
| | FRONT ENTRY. PLEASE PROVIDE HOW THE 2ND STORY OF THE |
| | ATRIUM WALL IS GOING TO BE BUILT, IS THE WALL GOING TO |
| | BE HUNG FROM THE 2ND FLOOR CEILING FRAMING. SHEET |
| | 009_A.0.1. SHOWS MOTORIZED WINDOW TREATMENT BUT THERE |
| | ARE NO DETAILS OF HOW THE SOFFIT AREA SURROUNDING THIS |
| | ROOM IS GOING TO BE FRAMED/ HUNG? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 2) THE STRUCTURAL SHEETS 015_S1.0 SHOW WELDED AND |
| | BOLTED CONNECTIONS REQUIRING NORMALLY REQUIRING A |
| | RESIDENT INSPECTOR. WE ARE REQUESTING THIRD PARTY |
| | CERTIFICATION FOR THE BOLTED CONNECTIONS AND WELDERS? |
| | CERTIFICATE FOR ANY FIELD WELDS SINCE THERE IS A |
| | MINIMUM AMOUNT OF THIS TYPE OF WORK. 2014 FLORIDA |
| | BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 110.3.9 OTHER INSPECTION SERVICES. |
| | |
| | 3)SHEET 004_A1.1.1. PLEASE PROVIDE WHAT TYPE OF DRYWALL |
| | IS GOING TO BE ON THE WALLS OF STAIR # 104 AND CLOSET |
| | 105 THE WALLS AND CEILING OF CLOSET. |
| | FBC-B 1009.9.3 ENCLOSURES UNDER INTERIOR STAIRWAYS. THE |
| | WALLS AND SOFFITS WITHIN ENCLOSED USABLE SPACES UNDER |
| | ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE PROTECTED BY |
| | 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION OR THE |
| | FIRE-RESISTANCE RATING OF THE STAIRWAY ENCLOSURE, |
| | WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED SPACE |
| | SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR ENCLOSURE. |
| | DOOR 105 STORAGE UNDER THE STAIR, DOES NOT SHOW A FIRE |
| | RATING IN THE DOOR SCHEDULE, NEITHER DOES DOOR 104 NOR |
| | DOOR 202. BLDG. TYPE VB/SPRINKLERED. FBC-B TABLE 716.5. |
| | 4) SHEET A1.1.1. SHOWS A 2 STORY ATRIUM PLEASE PROVIDE |
| | WHERE THE 1 HOUR FIRE RATING IS TAKING PLACE FROM THE |
| | REMAINING PORTION OF THE BUILDING FBC-B 404.6. |
| | 5) SHEET A1.1.1. ON THE 2ND FLOOR INDICATES A GLASS |
| | WALL THAT SEPARATES THE ATRIUM FROM THE 2ND FLOOR AREA |
| | FORMING A SMOKE PARTITION, PLEASE SHOW COMPLIANCE WITH |
| | 404.6 EXCEPTION 1.1-1.3. |
| | 6) SHEET A1.1.1 DOES NOT SHOW THE ELEVATOR IN A 1 HOUR |
| | FIRE RATED SHAFT. FBC-B 713.4. |
| | 7) SHEET A1.1.1. THE REAR STAIRWAY # 2 THE PLANS SHOW A |
| | ONE HOUR STAIR ENCLOSURE, IS THE AREA UNDER THE STAIR |
| | PART OF THE ELECTRIC ROOM, OR IS THE AREA UNDER THIS |
| | STAIR NOT USED AND THE ONE HOUR FIRE WALL IS THE |
| | ELECTRICAL ROOM WALL WHERE ALL PENETRATIONS HAVE TO BE |
| | FIRE SEALED? FBC-B 714.3.1. |
| | 8) BOTH THE DOORS 117& 213 SHOULD BE FIRE RATED DOORS |
| | SINCE THEY ARE IN THE 1 HOUR VERTICAL EXIT. 2014 FBC-B |
| | TABLE 716.5. |
| | 9) THERE IS NO SECTION THROUGH THE REAR STAIRWAY BUT IT |
| | APPEARS THAT THE STAIR STRINGER WILL BE LOW THE CEILING |
| | LEVEL OF THE LADIES CEILING IN ROOM 114 REQUIRING THE |
| | ONE HOUR FIRE RATING TO ALSO CONTINUE INTO THIS ROOM. |
| | 10) SHEET A1.1.1. THE 1ST FLOOR INDICATES THE USE OF A |
| | SINGLE DRINKING FOUNTAIN, THE NOTE # 12 INDICATES ANEW |
| | SINGLE ADA DRINKING FOUNTAIN W/ BOTTLE FILLING STATION, |
| | PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE |
| | 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING |
| | FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN |
| | SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH 602.7. |
| | 11) THE LIFE SAFETY PLANS INDICATE THE OCCUPANT LOAD OF |
| | 110 OCCUPANTS. THE LIFE SAFETY PLAN DOES NOT INDICATE |
| | IF THERE ARE (2) ACCESSIBLE EXITS, LEVEL WITH THE |
| | EXTERIOR OF THE BUILDING. 2014 FBC-ACCESSIBILITY CODE |
| | 207.1 GENERAL. MEANS OF EGRESS SHALL COMPLY WITH |
| | SECTION 1003.2.13 OF THE INTERNATIONAL BUILDING CODE |
| | (2000 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF |
| | THE INTERNATIONAL BUILDING CODE (2003 EDITION) |
| | (INCORPORATED BY REFERENCE, SEE ?REFERENCED STANDARDS? |
| | IN CHAPTER 1). |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |