| 2016-06-17 11:37:45 | RESIDENTIAL (R3) ADDITION/ALTERATION, THIRD BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE ICC EVALUATION REPORT (2 COPIES) FOR ICYNENE |
| | INSULATION SPECIFIED ON PLANS. ARCHITECT OF RECORD TO |
| | REVIEW AND APPROVE IN WRITING PRIOR TO SUBMITTAL. SEC. |
| | R316 OF FBC-RESIDENTIAL, 5TH EDITION (2014), |
| | |
| | RESPONSE: INSULATION WAS CHANGED TO R30 BATT |
| | INSULATION. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| | SHOWING HOW COMPLYING WITH THE ROOF VENTILATION SEC. |
| | R806 FBC-RESIDENTIAL, 5TH EDITION (2014). REPEAT |
| | COMMENT. NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 2- PROVIDE COMPLETE AND CLEAR INFORMATION FOR WINDOWS |
| | AND DOORS. SPECIFY SIZE FOR ALL DOORS AND WINDOWS TO |
| | VERIFY COMPLIANCE WITH THE PRODUCT APPROVALS SUBMITTED. |
| | . AND SPECIFY SIZE AND TYPE OF EXISTING BEDROOM WINDOWS |
| | TO BE REPLACED TO VERIFY COMPLIANCE WITH SEC. 704 OF |
| | FBC-EXISTING BUILDING, 5TH EDITION (2014). NOTE: NEW |
| | BEDROOM WINDOWS NEED TO COMPLY WITH SEC. R310 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014), |
| | |
| | RESPONSE: UNABLE TO VERIFY EGRESS REQUIREMENTS FOR THE |
| | FIRST FLOOR MASTER BEDROOM. SIZE SPECIFIED ON PLANS IS |
| | NOT LISTED ON THE PRODUCT APPROVAL SUBMITTED. PROVIDE |
| | MANUFACTURER'S CUT SHEETS FOR THE SPECIFIED SIZE SHOWN |
| | ON FLOOR PLAN AND TYPE OF WINDOW SHOWN ON THE EXTERIOR |
| | ELEVATION (UNEQUAL LITES) TO VERIFY COMPLIANCE WITH |
| | EGRESS. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | ORIGINAL COMMENT: |
| | A) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | RESPONSE: NOA 14-0903.03 SUBMITTED IS FOR 4", 6" & 12" |
| | WIDE LINTELS. THIS IS NOT THE SIZE SPECIFIED ON PLANS. |
| | PROVIDE CORRECT PRODUCT APPROVAL FOR 8" LINTELS. |
| | |
| | ORIGINAL COMMENT: |
| | B) GARAGE DOOR THAT MEETS THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER OF RECORD. FLORIDA PRODUCT |
| | APPROVAL FL15371-R2 SUBMITTED DOESN'T MEET THE DESIGN |
| | PRESSURES SHOWN ON SHEET S0.1. |
| | |
| | RESPONSE: NOT ADDRESSED (TWICE). |
| | |
| | 4- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE |
| | PRODUCT APPROVALS AS REQUIRED BY SEC. 107.4.1 CITY |
| | AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 5- SPECIFY ATTIC ACCESS LOCATION AND SIZE AT NEW GARAGE |
| | ADDITION. SEC. R807 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | RESPONSE: SIZE WAS NO SPECIFIED. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD |
| | DRAWINGS TO NEW RESUBMITTED SET. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |