| 2016-05-20 14:54:50 | RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | |
| | NOTE: BUILDING REVIEW MAY BE APPROVED WITH PROVISO. |
| | CONTRACTOR MAY SUBMIT THE REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED AND BEFORE INSPECTIONS. REVISION |
| | FEES MAY APPLY. CONTRACTOR TO ADVICE IS PROVISO OPTION |
| | IS PREFERRED AT THIS TIME. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE SPECIFICATIONS FOR GARAGE DOOR LEADING TO |
| | THE LIVING AREA TO SHOW COMPLIANCE WITH ALL THE |
| | REQUIREMENTS OF SEC. R302.5.1 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014), INCLUDING SELF CLOSING DEVICE. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 2- PROVIDE ICC EVALUATION REPORT (2 COPIES) FOR ICYNENE |
| | INSULATION SPECIFIED ON PLANS. ARCHITECT OF RECORD TO |
| | REVIEW AND APPROVE IN WRITING PRIOR TO SUBMITTAL. SEC. |
| | R316 OF FBC-RESIDENTIAL, 5TH EDITION (2014), |
| | RESPONSE: INSULATION WAS CHANGED TO R30 BATT |
| | INSULATION. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| | SHOWING HOW COMPLYING WITH THE ROOF VENTILATION SEC. |
| | R806 FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | ORIGINAL COMMENT: |
| | 3- PROVIDE COMPLETE AND CLEAR INFORMATION FOR WINDOWS |
| | AND DOORS. SPECIFY SIZE FOR ALL DOORS AND WINDOWS TO |
| | VERIFY COMPLIANCE WITH THE PRODUCT APPROVALS SUBMITTED. |
| | . AND SPECIFY SIZE AND TYPE OF EXISTING BEDROOM WINDOWS |
| | TO BE REPLACED TO VERIFY COMPLIANCE WITH SEC. 704 OF |
| | FBC-EXISTING BUILDING, 5TH EDITION (2014). NOTE: NEW |
| | BEDROOM WINDOWS NEED TO COMPLY WITH SEC. R310 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014), |
| | RESPONSE: UNABLE TO VERIFY SIZES FOR BEDROOM EGRESS |
| | REQUIREMENTS. THERE IS NOT RELATIONSHIP BETWEEN THE |
| | WINDOWS PRODUCT APPROVAL SUBMITTED AND THE WAY WINDOWS |
| | ARE SPECIFIED ON PLANS. NOTE: CLEARLY SPECIFY ON PLANS |
| | WHICH EXISTING DOORS AND WINDOWS ARE GOING TO BE |
| | REPLACED AND PROVIDE EXISTING TYPE AND SIZE OF EXISTING |
| | BEDROOM WINDOWS TO BE REPLACED TO VERIFY THE EGRESS |
| | REQUIREMENTS. COORDINATE INFORMATION WITH THE |
| | DEMOLITION PLANS. |
| | |
| | ORIGINAL COMMENT: |
| | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | INSTALLATION OF DECORATIVE SHUTTERS SHOWN ON EXTERIOR |
| | ELEVATIONS. SPECIFY MATERIALS AND SHUTTERS INSTALLATION |
| | TO RESIST THE WINDOW LOADS OF SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | RESPONSE: NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 5- NEW COVERED PATIO ROOF PITCH SHOWN ON EAST ELEVATION |
| | ON SHEET B-202 IS INCORRECT. REVISE AS REQUIRED. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | RESPONSE: NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | RESPONSE: ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| | FL158-R7 WAS SUBMITTED. PROVIDE COMPLETE INFORMATION |
| | THAT SHOWS SPECIFIED LINTELS. |
| | |
| | B) SLIDING GLASS DOOR SIZE (9076) SHOWN IN THE DINING |
| | ROOM. FLORIDA PRODUCT APPROVAL FL14138-R4 SUBMITTED |
| | DOESN'T COVER DOORS WITH THE WIDTH SPECIFIED FOR THIS |
| | DOOR. |
| | |
| | C) GARAGE DOOR THAT MEETS THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER OF RECORD. FLORIDA PRODUCT |
| | APPROVAL FL15371-R2 SUBMITTED DOESN'T MEET THE DESIGN |
| | PRESSURES SHOWN ON SHEET S0.1. |
| | RESPONSE: NOT ADDRESSED. |
| | |
| | D) SWINGING EXTERIOR DOORS THAT MEET THE DESIGN |
| | PRESSURES CALCULATED BY THE ENGINEER OF RECORD. FLORIDA |
| | PRODUCT APPROVAL FL15180-R1 SUBMITTED DOESN'T MEET THE |
| | CALCULATED DESIGN PRESSURES ON SHEET S0.1. AND, NEED |
| | SIZE OF EXTERIOR SWINGING DOORS IN PLANS TO VERIFY |
| | COMPLIANCE WITH PRODUCT APPROVALS SUBMITTED. |
| | RESPONSE: NOT ADDRESSED. |
| | |
| | E) ENTRY DOOR AS SHOWN ON PLANS (IF REPLACED). |
| | RESPONSE: NOT CLEAR IF REPLACING DOOR OR NOT. SEE DEMO |
| | PLANS. |
| | |
| | 7- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.4.1 CITY |
| | AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 8- FLAT ROOF NOA 13-1217.01 SUBMITTED: |
| | A) SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014), |
| | RESPONSE: NOT ADDRESSED. |
| | |
| | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA |
| | SUBMITTED, IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES. |
| | RESPONSE: NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 9- SPECIFY ATTIC ACCESS LOCATION AND SIZE AT NEW GARAGE |
| | ADDITION. SEC. R807 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | RESPONSE: NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 10- ENERGY CALCULATIONS SUBMITTED: |
| | A) COMPLETE ALL THE INFORMATION ON THE ENERGY |
| | PERFORMANCE LEVEL (EPL) DISPLAY CARD SUBMITTED. SEC. |
| | R405.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: NOT ADDRESSED. |
| | |
| | NOTE: |
| | LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| | SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL |
| | BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING THE |
| | SOFTWARE DEFAULT FACTOR FOR GLAZING. |
| | |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWINGS. SUBMIT OLD SET FOR REFERENCE. DON"T STAPLE |
| | OLD DRAWINGS TO NEW SET. |
| | |