| Date |
Text |
| 2016-03-11 12:03:25 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- ALL PLANS NEED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OF RECORD AS REQUIRED BY CHAPTER 481 F.S. |
| | AND, TITLE BLOCK TO PROVIDE ARCHITECT'S COMPLETE |
| | INFORMATION AS REQUIRED BY FLORIDA ADMINISTRATIVE CODE |
| | SEC. 61G1-16.004 |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 3- PROVIDE SPECIFICATIONS FOR GARAGE DOOR LEADING TO |
| | THE LIVING AREA TO SHOW COMPLIANCE WITH ALL THE |
| | REQUIREMENTS OF SEC. R302.5.1 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014), INCLUDING SELF CLOSING DEVICE. |
| | |
| | 4- PROVIDE ICC EVALUATION REPORT (2 COPIES) FOR ICYNENE |
| | INSULATION SPECIFIED ON PLANS. ARCHITECT OF RECORD TO |
| | REVIEW AND APPROVE IN WRITING PRIOR TO SUBMITTAL. SEC. |
| | R316 OF FBC-RESIDENTIAL, 5TH EDITION (2014), |
| | |
| | 5- PROVIDE COMPLETE AND CLEAR INFORMATION FOR WINDOWS |
| | AND DOORS. SPECIFY SIZE FOR ALL DOORS AND WINDOWS TO |
| | VERIFY COMPLIANCE WITH THE PRODUCT APPROVALS SUBMITTED. |
| | . AND SPECIFY SIZE AND TYPE OF EXISTING BEDROOM WINDOWS |
| | TO BE REPLACED TO VERIFY COMPLIANCE WITH SEC. 704 OF |
| | FBC-EXISTING BUILDING, 5TH EDITION (2014). NOTE: NEW |
| | BEDROOM WINDOWS NEED TO COMPLY WITH SEC. R310 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014), |
| | |
| | 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | INSTALLATION OF DECORATIVE SHUTTERS SHOWN ON EXTERIOR |
| | ELEVATIONS. SPECIFY MATERIALS AND SHUTTERS INSTALLATION |
| | TO RESIST THE WINDOW LOADS OF SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 7- NEW COVERED PATIO ROOF PITCH SHOWN ON EAST ELEVATION |
| | ON SHEET B-202 IS INCORRECT. REVISE AS REQUIRED. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 8- SHEET S0.1: PROVIDE ROOFING MATERIALS WIND LOADS FOR |
| | THE FLAT ROOF ON THE NEW COVERED PATIO. SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). (NOTE: ROOFING |
| | WIND LOADS SHOWN SEEM TO BE FOR ROOF ZONE #2 AND #3 FOR |
| | HIP ROOFS). |
| | |
| | 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| | DESIGNER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL |
| | NUMBER NEXT TO EACH CONNECTOR. |
| | |
| | B) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | C) FLORIDA PRODUCT APPROVAL FL14138-R4 SUBMITTED IS FOR |
| | SLIDING GLASS DOORS. PLANS DON'T SHOW ANY SLIDING GLASS |
| | DOORS. CLARIFY WHY SUBMITTING THIS PRODUCT APPROVAL. |
| | |
| | D) GARAGE DOOR THAT MEETS THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER OF RECORD. FLORIDA PRODUCT |
| | APPROVAL FL15371-R2 SUBMITTED DOESN'T MEET THE DESIGN |
| | PRESSURES SHOWN ON SHEET S0.1. |
| | |
| | E) SWINGING EXTERIOR DOORS THAT MEET THE DESIGN |
| | PRESSURES CALCULATED BY THE ENGINEER OF RECORD. FLORIDA |
| | PRODUCT APPROVAL FL15180-R1 SUBMITTED DOESN'T MEET THE |
| | CALCULATED DESIGN PRESSURES ON SHEET S0.1. AND, NEED |
| | SIZE OF EXTERIOR SWINGING DOORS IN PLANS TO VERIFY |
| | COMPLIANCE WITH PRODUCT APPROVALS SUBMITTED. |
| | |
| | F) ENTRY DOOR AS SHOWN ON PLANS (IF REPLACED). |
| | |
| | G) FRENCH DOORS WITH SIDELITES AS SHOWN ON PLANS. |
| | |
| | 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.4.1 |
| | CITY AMENDMENTS. |
| | |
| | 11- FLAT ROOF NOA 13-1217.01 SUBMITTED: |
| | A) SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014), |
| | |
| | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA |
| | SUBMITTED, IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES. |
| | |
| | 12-SPECIFY ATTIC ACCESS LOCATION AND SIZE AT NEW GARAGE |
| | ADDITION. SEC. R807 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | 13- ENERGY CALCULATIONS SUBMITTED: |
| | A) OWNER/AGENT TO CERTIFY AT THE BOTTOM OF THE COVER |
| | PAGE AS REQUIRED BY SEC. R103.1.1.2 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) PROVIDE COMPLETE INFORMATION ON TOP OF COVER FORM, |
| | INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE |
| | AND JURISDICTION. SEC. R101.5.1.1.2 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | C) REVISE ROOF MATERIAL SPECIFIED ON PAGE 2 OF 5 TO |
| | MATCH PLANS. SEC. R101.5.1.1.2 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | D) CEILING R VALUE SHOWN ON PAGE 3 OF 5 DOESN'T MATCH |
| | CEILING INFORMATION SHOWN ON PAGE 1 OF 5. SEC. |
| | R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | E) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION SHOWN |
| | ON PAGE 3 OF 5 TO MATCH PLANS AND ELEVATIONS. SEC. |
| | R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | F) COMPLETE ALL THE INFORMATION ON THE ENERGY |
| | PERFORMANCE LEVEL (EPL) DISPLAY CARD SUBMITTED. SEC. |
| | R405.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | NOTE: |
| | LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| | SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL |
| | BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING THE |
| | SOFTWARE DEFAULT FACTOR FOR GLAZING. |
| | |
| | 14- INFORMATION SHOWN ON PLANS AND ENERGY CALCULATIONS |
| | NEED TO MATCH. REVISE INSULATION R-VALUE FOR WALLS, |
| | CEILING, ETC, TO MATCH. SEC. R103.2 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | 15- ARCHITECTURAL PLANS AND STRUCTURAL PLANS DON'T SHOW |
| | DIMENSIONS FOR THE WIDTH OF THE NEW COVERED PATIO. |
| | PROVIDE ALL DIMENSIONS. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWINGS. SUBMIT OLD SET FOR REFERENCE. DON"T STAPLE |
| | OLD DRAWINGS TO NEW SET. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |