2016-05-12 07:47:134TH REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020539
 5/12/16
  
 1) M-1: REFER TO SECTION 401.2 FBC-14 MECHANICAL: EVERY
 OCCUPIED SPACE SHALL BE VENTILATED EITHER BY NATURAL OR
 MECHANICAL MEANS. THE CALCULATIONS SHOWN ON THE PLAN
 INDICATE BOTH METHODS ARE BEING COMBINED TO ACHIEVE THE
 REQUIRED 1058 CFM'S OF OUTDOOR AIR FOR THE PROPOSED
 OCCUPANCY. AS NOTED IN 2012 INTERNATIONAL CODE
 COMMENTARY "THERE ARE NO PROVISIONS IN THE CODE FOR A
 VENTILATION SYSTEM THAT DEPENDS SIMULTANEOUSLY ON BOTH
 NATURAL AND MECHANICAL VENTILATION". THE DESIGN
 PROFESSIONALS CALCULATIONS THE RTU'S ARE SUPPLYING A
 TOTAL OF 828 CFMS OF O/A WHICH IS APPROXIMATELY 230
 CFMS SHORT OF THE REQUIREMENT. PLEASE NOTE THE
 FOLLOWING: A) THE TERM "MAKE-UP" AIR SHOULD BE REPLACED
 ON THE PLAN WITH "VENTILATION AIR" AS NOTED IN SECTION
 401.2. B) REFER TO SECTION 402.1 NATURAL VENTILATION:
 NATURAL VENTILATION OF AN OCCUPIED SPACE SHALL BE
 THROUGH WINDOWS, DOORS, LOUVERS OR OTHER OPENINGS TO
 THE OUTDOORS. THE OPERATING MECHANISM FOR SUCH OPENINGS
 SHALL BE PROVIDED WITH READY ACCESS SO THAT THE
 OPENINGS ARE READILY CONTROLLABLE BY THE BUILDING
 OCCUPANTS. THE PLANS APPEAR TO INDICATE THAT "NATURAL
 VENTILATION" WOULD NOT BE A REASONABLE WAY TO PROVIDE
 VENTILATION TO THE SPACE BECAUSE THERE ARE NO OPERABLE
 OPENINGS EXCEPT THE ENTRY DOORS WHICH WOULD TYPICALLY
 BE KEPT CLOSED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719