| 2016-04-26 10:37:27 | 1) A FOLDING OR NON-FOLDING SEAT IS REQUIRED IN |
| | TRANSFER TYPE SHOWER COMPARTMENTS PER THE 2014 |
| | FBC-ACCESSIBILITY SEC.608.4. YOUR RESPONSE TO MY |
| | PREVIOUS COMMENT DOES NOT MAKE SENSE TO ME AS YOU ARE |
| | REFERRING TO A CODE SECTION FOR ROLL-IN TYPE SHOWERS |
| | AND THE SIZE OF THE SHOWERS ON THE PLANS DO NOT COMPLY |
| | WITH THE MINIMUM DIMENSIONS REQUIRED FOR A ROLL-IN TYPE |
| | SHOWER PER THE FAC SEC.608.2.2. THE SIZES ON THE PLANS |
| | ARE FOR A TRANSFER TYPE SHOWER, NOT A ROLL-IN. 2ND |
| | REQUEST. |
| | 2)THE SHOWER SEAT SHALL COMPLY WITH 2014 |
| | FBC-ACCESSIBILITY SEC.610.3. IN TRANSFER-TYPE SHOWERS, |
| | THE SEAT SHALL EXTEND FROM THE BACK WALL TO A POINT |
| | WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. THE |
| | TOP OF THE SEAT SHALL BE 17 INCHES (430 MM) MINIMUM AND |
| | 19 INCHES (485 MM) MAXIMUM ABOVE THE BATHROOM FINISH |
| | FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR 610.3.2. 2ND |
| | REQUEST |
| | 3) SUBMIT AN ELEVATION OF THE WING WALLS AND SHOW THE |
| | HEIGHT. ANY PORTION OF THE WING WALL LOCATED GREATER |
| | THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE |
| | FINISH FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES |
| | MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH PER 2014 |
| | FAC SEC. 307.2. WHY NOT PUT AN OPTIONAL SKIRT ON THE |
| | HIGH SIDE DRINKING FOUNTAIN TO KEEP THE LEADING EDGE |
| | BELOW 27 INCHES? |
| | 4) SHT. P-2 - THE SIDE WALL GRAB BAR FOR THE WATER |
| | CLOSET SHALL COMPLY WITH FAC SEC.604.5.1. SHOW THE |
| | DIMENSIONS ON THE PLANS.2ND REQUEST. |
| | 5) THE GRAB BARS IN THE SHOWERS SHALL BE LOCATED ACROSS |
| | THE CONTROL WALL AND BACK WALL TO A POINT 18 INCHES |
| | FROM THE CONTROL WALL. SHOW THIS ON THE PLANS. SEE FAC |
| | FIGURE 608.3.1. |
| | 6) THE SHOWER CONTROLS SHALL BE LOCATED A MAXIMUM OF 15 |
| | INCHES FROM THE CENTERLINE OF THE REQUIRED SEAT TOWARD |
| | THE SHOWER OPENING. SHOW THIS ON THE PLANS. |
| | 7) THE FIRST WATER CLOSET THAT IS CONNECTED TO THE |
| | BUILDING DRAIN CREATES PLUMBING CODE VIOLATIONS. THE |
| | LOCATION OF THE WATER CLOSETS CREATES A WET VENT FOR |
| | THE WATER CLOSETS AND THE FIXTURES DISCHARGING INTO THE |
| | WET VENT VIOLATES THE 2014 FBC-PLUMBING SEC.912.1. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |