Plan Review Notes
Plan Review Notes For Permit 16020539
Permit Number 16020539
Review Stop P
Sequence Number 3
Notes
Date Text
2016-04-26 10:37:271) A FOLDING OR NON-FOLDING SEAT IS REQUIRED IN
 TRANSFER TYPE SHOWER COMPARTMENTS PER THE 2014
 FBC-ACCESSIBILITY SEC.608.4. YOUR RESPONSE TO MY
 PREVIOUS COMMENT DOES NOT MAKE SENSE TO ME AS YOU ARE
 REFERRING TO A CODE SECTION FOR ROLL-IN TYPE SHOWERS
 AND THE SIZE OF THE SHOWERS ON THE PLANS DO NOT COMPLY
 WITH THE MINIMUM DIMENSIONS REQUIRED FOR A ROLL-IN TYPE
 SHOWER PER THE FAC SEC.608.2.2. THE SIZES ON THE PLANS
 ARE FOR A TRANSFER TYPE SHOWER, NOT A ROLL-IN. 2ND
 REQUEST.
 2)THE SHOWER SEAT SHALL COMPLY WITH 2014
 FBC-ACCESSIBILITY SEC.610.3. IN TRANSFER-TYPE SHOWERS,
 THE SEAT SHALL EXTEND FROM THE BACK WALL TO A POINT
 WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. THE
 TOP OF THE SEAT SHALL BE 17 INCHES (430 MM) MINIMUM AND
 19 INCHES (485 MM) MAXIMUM ABOVE THE BATHROOM FINISH
 FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR 610.3.2. 2ND
 REQUEST
 3) SUBMIT AN ELEVATION OF THE WING WALLS AND SHOW THE
 HEIGHT. ANY PORTION OF THE WING WALL LOCATED GREATER
 THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE
 FINISH FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES
 MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH PER 2014
 FAC SEC. 307.2. WHY NOT PUT AN OPTIONAL SKIRT ON THE
 HIGH SIDE DRINKING FOUNTAIN TO KEEP THE LEADING EDGE
 BELOW 27 INCHES?
 4) SHT. P-2 - THE SIDE WALL GRAB BAR FOR THE WATER
 CLOSET SHALL COMPLY WITH FAC SEC.604.5.1. SHOW THE
 DIMENSIONS ON THE PLANS.2ND REQUEST.
 5) THE GRAB BARS IN THE SHOWERS SHALL BE LOCATED ACROSS
 THE CONTROL WALL AND BACK WALL TO A POINT 18 INCHES
 FROM THE CONTROL WALL. SHOW THIS ON THE PLANS. SEE FAC
 FIGURE 608.3.1.
 6) THE SHOWER CONTROLS SHALL BE LOCATED A MAXIMUM OF 15
 INCHES FROM THE CENTERLINE OF THE REQUIRED SEAT TOWARD
 THE SHOWER OPENING. SHOW THIS ON THE PLANS.
 7) THE FIRST WATER CLOSET THAT IS CONNECTED TO THE
 BUILDING DRAIN CREATES PLUMBING CODE VIOLATIONS. THE
 LOCATION OF THE WATER CLOSETS CREATES A WET VENT FOR
 THE WATER CLOSETS AND THE FIXTURES DISCHARGING INTO THE
 WET VENT VIOLATES THE 2014 FBC-PLUMBING SEC.912.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  