2016-04-21 16:24:222ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020539
 4/21/16
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS: REFER
 TO TABLE 403.3 AND PROVIDE A O/A CALCULATION FOR THE
 STRENGTH TRAINING AREA AT 10 PERSONS PER 1000 SF. AT A
 RATE OF 20 CFM PER PERSON + .06 CFMS PER SF. OF THE
 AREA. PLEASE SEE THE CALCULATION RATES LISTED UNDER
 "OFFICES" IN THE TABLE FOR ALL OTHER ROOMS AND SPACES
 SHOWN ON THE PLANS.BASED.
 IN REGARD TO THE CALCULATIONS ON SHEET M-1, REFER TO
 SECTION 403.2 EXCEPTION: WHERE THE REGISTERED DESIGN
 PROFESSIONAL DEMONSTRATES THAT AN ENGINEERED
 VENTILATION SYSTEM DESIGN WILL PREVENT THE MAXIMUM
 CONCENTRATION OF CONTAMINANTS FROM EXCEEDING THAT
 OBTAINABLE BY THE RATE OF OUTDOOR AIR VENTILATION
 DETERMINED IN ACCORDANCE WITH SECTION 403.3, THE
 MINIMUM REQUIRED RATE OF OUTDOOR AIR SHALL BE REDUCED
 IN ACCORDANCE WITH SUCH ENGINEERED SYSTEM DESIGN. IF
 CHOOSING THIS EXCEPTION PROVIDE DETAILS AND
 SPECIFICATIONS FOR THE ENGINEERED SYSTEM. REFER TO
 SECTION 403.3 EXCEPTION: THE OCCUPANT LOAD IS NOT
 REQUIRED TO BE DETERMINED BASED ON THE ESTIMATED
 MAXIMUM OCCUPANT LOAD RATE INDICATED IN TABLE 403.3
 WHERE APPROVED STATISTICAL DATA DOCUMENT THE ACCURACY
 OF AN ALTERNATE ANTICIPATED OCCUPANT DENSITY. IF
 CHOOSING THIS EXCEPTION, APPROVED STATISTICAL DATA
 DOCUMENTATION MUST BE PROVIDED.
  
 2) PLEASE CORRECT NOTE #7 TO INDICATE THE LOCATION OF
 THE DS DETECTOR TO BE IN THE RETURN AIR SYSTEM, AND
 PROVIDE A SYMBOL ON THE PLAN TO INDICATE COMPLIANCE.
 PLACE A NOTE INDICATING THAT BOTH UNITS WILL BE LINKED
 TOGETHER FOR FAN SHUT DOWN IF THE THE DS DETECTOR
 ACTIVATES.
  
 3) PROVIDE SHUTOFF DAMPERS FOR THE O/A INTAKE ON THE
 RTU'S AND INDICATE HOW THEY WILL BE CONTROLLED- SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  