| 2016-04-12 15:02:48 | 1) THE SHOWER SEAT SHALL COMPLY WITH 2014 |
| | FBC-ACCESSIBILITY SEC.610.3. IN TRANSFER-TYPE SHOWERS, |
| | THE SEAT SHALL EXTEND FROM THE BACK WALL TO A POINT |
| | WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. THE |
| | TOP OF THE SEAT SHALL BE 17 INCHES (430 MM) MINIMUM AND |
| | 19 INCHES (485 MM) MAXIMUM ABOVE THE BATHROOM FINISH |
| | FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR 610.3.2. |
| | 2) SUBMIT AN ELEVATION DETAIL FOR THE DRINKING |
| | FOUNTAINS. THE FOUNTAINS SHALL COMPLY WITH FAC SEC. 307 |
| | FOR PROTRUDING OBJECTS. 307.2 PROTRUSION LIMITS. |
| | OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM) |
| | AND NOT MORE THAN 80 INCHES (2030 MM) ABOVE THE FINISH |
| | FLOOR OR GROUND SHALL PROTRUDE 4 INCHES (100 MM) |
| | MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH. AN |
| | OPTIOAAL SKIRT MAY BE REQUIRED FOR THE HIGH SIDE |
| | DRINKING FOUNTAIN. |
| | 3) SHT. P.1 - THE DOOR IN THE MEN'S ROOM SWINGS INTO |
| | THE CLEAR FLOOR SPACE FOR THE SHOWER AND THE LAVATORY |
| | AND THE DOOR IN THE WOMEN'S RESTROOM SWINGS INTO THE |
| | CLEAR FLOOR SPACEFO THE LAVATORY. THE DOOR SHALL NOT |
| | SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY |
| | FIXTURE PER THE 2014 FAC SEC, PER THE FAC SEC.603.2.3.. |
| | REFERE TO EXCEPTION #2. |
| | 4) THE WATER CLOSETS SHALL BE LOCATED A MINIMUM OF 16 |
| | INCHES AND A MAXIMUM OF 18 INCHES TO THE CENTERLINE OF |
| | THE WATER CLOSET TO AN ADJACENT WALL. 2014 FAC |
| | SEC.604.2. SHOW THIS ON THE ENLARGED PLANS ON SHT.P.2. |
| | 5) THE LOCATION OF THE GRAB BARS FOR THE WATER CLOSETS |
| | SHALL COMPLY WITH FAC SEC.604.5 THROUGH 604.5.2 & |
| | FIGURES 604.5.1 & 604.5.2. |
| | 6) SHOW THE INSIDE CLEAR DIMENSIONS ( LENGTH X WIDTH) |
| | OF BOTH TOILET ROOMS. THE DIMENSIONS SHOWN ON SHTS. P.1 |
| | & P.2 ARE NOT INSIDE DIMENSIONS. |
| | 7) SHT. P.2 - 608.2.1 TRANSFER TYPE SHOWER |
| | COMPARTMENTS. |
| | TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES |
| | (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS |
| | MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND |
| | SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE |
| | FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES |
| | (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG |
| | MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE |
| | PROVIDED. THE PLANS SHOW THE CLEAR FLOOR SPACE MEASURED |
| | FROM THE WALL OPPOSITE THE CONTROLS. |
| | 8) GRAB BARS ARE REQUIRED IN THE SHOWERS PER FAC |
| | SECS.608.3, 608.3.1. |
| | 9) THE SHOWER CONTROLS SHALL COMPLY WITH FAC |
| | SEC.608.5.1, 309.4, 608.6.SUBMIT DETAIL FOR REVIEW. |
| | 10) THE SHOWER THRESHOLD SHALL COMPLY WITH FAC |
| | SEC.608.7. |
| | 11 ) SHT. PL.2 - THE MINIMUM SIZE OF THE WATER HEATER |
| | PAN DRAIN SHALL BE 3/4 INCH PER THE 2014 FPC |
| | SEC.504.7.1.THE PLAN SHOWS 1/2". |
| | 12) THE HEATE PAN SHALL BE A MINIMUM OF 1 1/2 INCHES |
| | DEEP PER THE 2014 FPC SEC.504.7.1. |
| | 13) THE WATER RISER APPEARS TO HAVE THE HOT AND COLD |
| | WATER LINES REVERSED. CLARIFY. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |