| 2016-03-25 14:37:31 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16020539 | | | 3/25/16 | | | | | | 1) SHEET M-1: THE O/A CALCULATIONS ARE BASED ON AN | | | OCCUPANT LOAD THAT DOES NOT MATCH THE OCCUPANT LOAD ON | | | THE PLANS OR TABLE 403.3. ADDITIONALLY, AIR | | | INFILTRATION SHALL NOT BE USED TO PROVIDE AIR BALANCE | | | OR PRESSURE EQUALIZATION- SECTION 501.4. | | | 2) PROVIDE AN EXHAUST FAN EQUIPMENT SCHEDULE ON THE | | | PLANS AND SUBMIT AN MIAMI- DADE NOA OR FLORIDA PRODUCT | | | APPROVAL FOR THE FAN OR LOUVER. | | | 3) INDICATE THE CLEARANCE DISTANCE MEASUREMENTS FOR THE | | | EXHAUST DUCT TERMINATIONS AS REQUIRED BY SECTION | | | 501.3.1 FBC-14 MECHANICAL. | | | 4) INDICATE THE TYPE AND GAGE OF METAL BATHROOM/UTILITY | | | ROOM EXHAUST DUCT TO BE USED- REFER TO CHAPTER 4 OF | | | SMACNA, AND INDICATE THE EXHAUST CFMS AT THE EXHAUST | | | INLET IN THE UTILITY ROOM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|