2016-03-25 14:37:312ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020539
 3/25/16
  
 1) SHEET M-1: THE O/A CALCULATIONS ARE BASED ON AN
 OCCUPANT LOAD THAT DOES NOT MATCH THE OCCUPANT LOAD ON
 THE PLANS OR TABLE 403.3. ADDITIONALLY, AIR
 INFILTRATION SHALL NOT BE USED TO PROVIDE AIR BALANCE
 OR PRESSURE EQUALIZATION- SECTION 501.4.
 2) PROVIDE AN EXHAUST FAN EQUIPMENT SCHEDULE ON THE
 PLANS AND SUBMIT AN MIAMI- DADE NOA OR FLORIDA PRODUCT
 APPROVAL FOR THE FAN OR LOUVER.
 3) INDICATE THE CLEARANCE DISTANCE MEASUREMENTS FOR THE
 EXHAUST DUCT TERMINATIONS AS REQUIRED BY SECTION
 501.3.1 FBC-14 MECHANICAL.
 4) INDICATE THE TYPE AND GAGE OF METAL BATHROOM/UTILITY
 ROOM EXHAUST DUCT TO BE USED- REFER TO CHAPTER 4 OF
 SMACNA, AND INDICATE THE EXHAUST CFMS AT THE EXHAUST
 INLET IN THE UTILITY ROOM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  