| Plan Review Notes For Permit 16020539 |
| Permit Number |
16020539 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-23 06:57:21 | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT. P-1 THE FLOOR PLAN DOES NOT MATCH THE REST OF | | | THE PLAN AND IS ADDRESSED DIFFERENTLY PLEASE CLARIFY. | | | PER WPB AMEND. TO FBC 107.2.1 | | | | | | 2. SHT. HC.1 THE TEXT IS PRINTED VERY BLURRY AND IS | | | UNCLEAR PLEASE PROVIDE A SHEET THAT IS PRINTED CLEARLY | | | PER WPB AMEND. TO FBC SEC. 107.2.1.4 | | | | | | 3. SHT. PL.1 WATER FOUNTAIN CAN NOT TIE INTO THE WET | | | VENT OF BATHROOM GROUP | | | PER. FBC PL SEC. 912.1 | | | | | | 4. SHT. PL.1 REFERENCES A 40 GAL. WATER HEATER FIXTURE | | | SCHEDULE ON PL.2 REFERENCES A 50 GAL. PLEASE CLARIFY. | | | PER WPB AMEND. TO FBC 107.2.1 | | | | | | 5. SHOWER SEAT SHALL COMPLY WITH FBC ACC. SEC 610 | | | PLEASE SHOW ON PLAN. | | | PER WPB AMEND. TO FBC 107.2.1 | | | | | | 6. SHT. SHOW WATER HAMMER ARRESTORS ON WATER RISER | | | DIAGRAM. | | | PER WPB AMEND. TO FBC 107.2.1 |
|