Plan Review Notes
Plan Review Notes For Permit 16020539
Permit Number 16020539
Review Stop P
Sequence Number 1
Notes
Date Text
2016-02-23 06:57:21 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. P-1 THE FLOOR PLAN DOES NOT MATCH THE REST OF
 THE PLAN AND IS ADDRESSED DIFFERENTLY PLEASE CLARIFY.
 PER WPB AMEND. TO FBC 107.2.1
  
 2. SHT. HC.1 THE TEXT IS PRINTED VERY BLURRY AND IS
 UNCLEAR PLEASE PROVIDE A SHEET THAT IS PRINTED CLEARLY
 PER WPB AMEND. TO FBC SEC. 107.2.1.4
  
 3. SHT. PL.1 WATER FOUNTAIN CAN NOT TIE INTO THE WET
 VENT OF BATHROOM GROUP
 PER. FBC PL SEC. 912.1
  
 4. SHT. PL.1 REFERENCES A 40 GAL. WATER HEATER FIXTURE
 SCHEDULE ON PL.2 REFERENCES A 50 GAL. PLEASE CLARIFY.
 PER WPB AMEND. TO FBC 107.2.1
  
 5. SHOWER SEAT SHALL COMPLY WITH FBC ACC. SEC 610
 PLEASE SHOW ON PLAN.
 PER WPB AMEND. TO FBC 107.2.1
  
 6. SHT. SHOW WATER HAMMER ARRESTORS ON WATER RISER
 DIAGRAM.
 PER WPB AMEND. TO FBC 107.2.1