| 2016-02-24 17:18:16 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #16020539 |
| | 2/24/16 |
| | |
| | 1) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING AND |
| | PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | OCCUPIED ROOMS AND SPACES OF THE NEW FITNESS CENTER- |
| | SEE TABLE 403.3 FBC-14 MECHANICAL. |
| | 2) AC COOLING AND HEATING CALCULATIONS ARE REQUIRED FOR |
| | THE NEW RT SEE SECTION C403.2.1 CALCULATION OF HEATING |
| | AND COOLING LOADS, FBC-14 ENERGY CONSERVATION. |
| | 3) REFER TO SECTION C101.4.4 FBC-14 ENERGY |
| | CONSERVATION: THE PROPOSED NEW A3 OCCUPANCY IS A CHANGE |
| | OF OCCUPANCY FROM THE PREVIOUS B OCCUPANCY AND |
| | THEREFORE MUST BE IN COMPLIANCE WITH THE ENERGY CODE. |
| | PLEASE SEE SECTIONS C101.5.1 AND C101.5.1.1 AND SUBMIT |
| | COMPLIANCE FORMS USING EITHER THE PRECRIPTIVE OR |
| | PERFORMANCE- BASED METHOD. |
| | 4) SHEET M-1: PLEASE LABEL EACH OF THE AC SYSTEMS SHOWN |
| | ON THE PLAN AND INDICATE WHETHER THEY ARE NEW OR |
| | EXISTING. INDICATE ON THE PLAN WHERE THE RTU'S ARE |
| | LOCATED AND SHOW OUTLINES OF THEIR SUPPLY AND RETURN |
| | PLENUMS |
| | 5) M-1: INDICATE THE FLEX DUCT SIZES, AND ANY BRANCH |
| | DUCTS NOT SIZED. |
| | 6) PROVIDE RETURN AIR SYSTEMS FOR BOTH OF THE RTU'S- |
| | SECTION 601.5 FBC-14 MECHANICAL. |
| | 7) M-2: THE RTU MOUNTING DETAIL SHOWN AT THE TOP OF THE |
| | PLAN SHEET IS MISSING- NO DIAGRAM IS SHOWN. |
| | 8) M-2: PLEASE CLARIFY IF TWO NEW RTU'S ARE BEING |
| | INSTALLED: THE TWO MOUNTING DETAILS ON THIS SHEET- ONE |
| | WITH CURB ADAPTOR, AND ONE WITHOUT- APPEAR TO INDICATE |
| | TWO DIFFERENT UNITS. CLARIFY IF A NEW ROOF OPENING IN |
| | THE STRUCTURE MUST BE ACCOMPLISHED TO INSTALL THE NEW |
| | RTU AND PROVIDE ENGINEERED STRUCTURAL DETAILS IF |
| | APPLICABLE. |
| | 9) PROVIDE COMPLETE EQUIPMENT SCHEDULES FOR THE RTU'S |
| | 10) PROVIDE A ROOF PLAN SHOWING THE LOCATIONS OF THE |
| | RTU'S AND CLEARANCE DISTANCE MEASUREMENTS FROM ANY |
| | EXHAUST OR VENT OUTLETS TO THE AIR INTAKES. |
| | 11) PLEASE NOTE THAT THERE MAY BE ADDITIONAL COMMENTS |
| | WHEN REVISED, CORRECTED PLANS HAVE BEEN SUBMITTED. |
| | |
| | CHRISTOPHER L. COLE |