2016-02-24 17:18:161ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020539
 2/24/16
  
 1) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 OCCUPIED ROOMS AND SPACES OF THE NEW FITNESS CENTER-
 SEE TABLE 403.3 FBC-14 MECHANICAL.
 2) AC COOLING AND HEATING CALCULATIONS ARE REQUIRED FOR
 THE NEW RT SEE SECTION C403.2.1 CALCULATION OF HEATING
 AND COOLING LOADS, FBC-14 ENERGY CONSERVATION.
 3) REFER TO SECTION C101.4.4 FBC-14 ENERGY
 CONSERVATION: THE PROPOSED NEW A3 OCCUPANCY IS A CHANGE
 OF OCCUPANCY FROM THE PREVIOUS B OCCUPANCY AND
 THEREFORE MUST BE IN COMPLIANCE WITH THE ENERGY CODE.
 PLEASE SEE SECTIONS C101.5.1 AND C101.5.1.1 AND SUBMIT
 COMPLIANCE FORMS USING EITHER THE PRECRIPTIVE OR
 PERFORMANCE- BASED METHOD.
 4) SHEET M-1: PLEASE LABEL EACH OF THE AC SYSTEMS SHOWN
 ON THE PLAN AND INDICATE WHETHER THEY ARE NEW OR
 EXISTING. INDICATE ON THE PLAN WHERE THE RTU'S ARE
 LOCATED AND SHOW OUTLINES OF THEIR SUPPLY AND RETURN
 PLENUMS
 5) M-1: INDICATE THE FLEX DUCT SIZES, AND ANY BRANCH
 DUCTS NOT SIZED.
 6) PROVIDE RETURN AIR SYSTEMS FOR BOTH OF THE RTU'S-
 SECTION 601.5 FBC-14 MECHANICAL.
 7) M-2: THE RTU MOUNTING DETAIL SHOWN AT THE TOP OF THE
 PLAN SHEET IS MISSING- NO DIAGRAM IS SHOWN.
 8) M-2: PLEASE CLARIFY IF TWO NEW RTU'S ARE BEING
 INSTALLED: THE TWO MOUNTING DETAILS ON THIS SHEET- ONE
 WITH CURB ADAPTOR, AND ONE WITHOUT- APPEAR TO INDICATE
 TWO DIFFERENT UNITS. CLARIFY IF A NEW ROOF OPENING IN
 THE STRUCTURE MUST BE ACCOMPLISHED TO INSTALL THE NEW
 RTU AND PROVIDE ENGINEERED STRUCTURAL DETAILS IF
 APPLICABLE.
 9) PROVIDE COMPLETE EQUIPMENT SCHEDULES FOR THE RTU'S
 10) PROVIDE A ROOF PLAN SHOWING THE LOCATIONS OF THE
 RTU'S AND CLEARANCE DISTANCE MEASUREMENTS FROM ANY
 EXHAUST OR VENT OUTLETS TO THE AIR INTAKES.
 11) PLEASE NOTE THAT THERE MAY BE ADDITIONAL COMMENTS
 WHEN REVISED, CORRECTED PLANS HAVE BEEN SUBMITTED.
  