Plan Review Notes
Plan Review Notes For Permit 16020539
Permit Number 16020539
Review Stop E
Sequence Number 1
Notes
Date Text
2016-02-24 13:10:34APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE LABEL ON FLOOR PLAN THE CIRCUIT # FOR THE
 CORRIDOR LIGHTING SHOWN. FBC 107.3.5
 2.SHOW RECEPTACLE FOR THE SIGN OUTLET (CIRCUIT#24) ON
 FLOOR PLAN. FBC 107.3.5
 3.PROVIDE A GENERAL NOTE INDICATING LOW VOLTAGE TO BE
 PERMITTED SEPARATELY. FBC 107.3.5
 4.SHOW ON FLOOR PLAN THE EM EXIT LIGHTS AT EGRESS DOORS
 AND WHERE APPLICABLE. (CIRCUIT#21) FBC 107.3.5
 5.SHOW EXISTING RISER DIAGRAM SHOWING THE CONDUCTOR
 SIZE, OVERCURRENT SELECTION AND AIC RATING FOR THE NEW
 400A PANEL BOARD. FBC 107.3.5, NEC 310.15B16.
 6.CLARIFY IF VOLTAGE TO PANEL BOARD IS 120/240V DELTA 3
 PHASE AS SHOWN ON PANEL BOARD. IF SO COMPLY WITH NOTES
 INDICATING THE REQUIREMENTS OF NEC 408.3F1 HIGH LEG
 IDENTIFICATION.
 7.CLARIFY THE SELECTION OF #12 CONDUCTORS FOR THE RTU?S
 SHOWN ON THE PANEL SCHEDULE WITH 60A OVERCURRENT
 SELECTION. NEC 310.15B16. SHOW THE REQUIRED RECEPTACLE
 OUTLET ON FLOOR PLAN TO SERVICE THE UNITS. NEC 210.63
 8.PROVIDE A NOTE ON THE PANEL SCHEDULE FOR CIRCUIT
 #A-36 EMERGENCY LIGHTS TO HAVE A LOCK ON FEATURE PER
 NEC 700.12F EXCEPTION #1.
 9.SEE SITE SPECIFIC NOTES AND CLARIFY OR DELETE NON
 APPLICABLE NOTES NOT PERTAINING TO THIS PROJECT. SEE
 NOTE #2.
 10.ADD A NOTE TO SCHEDULE INDICATE THAT THE CEILING FAN
 BOXES ARE TO BE RATED AS PER NEC 314.27C
 11.PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  