| 2016-02-24 13:10:34 | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 NEC |
| | COMMENTS: |
| | |
| | 1.PLEASE LABEL ON FLOOR PLAN THE CIRCUIT # FOR THE |
| | CORRIDOR LIGHTING SHOWN. FBC 107.3.5 |
| | 2.SHOW RECEPTACLE FOR THE SIGN OUTLET (CIRCUIT#24) ON |
| | FLOOR PLAN. FBC 107.3.5 |
| | 3.PROVIDE A GENERAL NOTE INDICATING LOW VOLTAGE TO BE |
| | PERMITTED SEPARATELY. FBC 107.3.5 |
| | 4.SHOW ON FLOOR PLAN THE EM EXIT LIGHTS AT EGRESS DOORS |
| | AND WHERE APPLICABLE. (CIRCUIT#21) FBC 107.3.5 |
| | 5.SHOW EXISTING RISER DIAGRAM SHOWING THE CONDUCTOR |
| | SIZE, OVERCURRENT SELECTION AND AIC RATING FOR THE NEW |
| | 400A PANEL BOARD. FBC 107.3.5, NEC 310.15B16. |
| | 6.CLARIFY IF VOLTAGE TO PANEL BOARD IS 120/240V DELTA 3 |
| | PHASE AS SHOWN ON PANEL BOARD. IF SO COMPLY WITH NOTES |
| | INDICATING THE REQUIREMENTS OF NEC 408.3F1 HIGH LEG |
| | IDENTIFICATION. |
| | 7.CLARIFY THE SELECTION OF #12 CONDUCTORS FOR THE RTU?S |
| | SHOWN ON THE PANEL SCHEDULE WITH 60A OVERCURRENT |
| | SELECTION. NEC 310.15B16. SHOW THE REQUIRED RECEPTACLE |
| | OUTLET ON FLOOR PLAN TO SERVICE THE UNITS. NEC 210.63 |
| | 8.PROVIDE A NOTE ON THE PANEL SCHEDULE FOR CIRCUIT |
| | #A-36 EMERGENCY LIGHTS TO HAVE A LOCK ON FEATURE PER |
| | NEC 700.12F EXCEPTION #1. |
| | 9.SEE SITE SPECIFIC NOTES AND CLARIFY OR DELETE NON |
| | APPLICABLE NOTES NOT PERTAINING TO THIS PROJECT. SEE |
| | NOTE #2. |
| | 10.ADD A NOTE TO SCHEDULE INDICATE THAT THE CEILING FAN |
| | BOXES ARE TO BE RATED AS PER NEC 314.27C |
| | 11.PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY |
| | QUESTIONS REGARDING THIS PROJECT. |
| | |