| Date |
Text |
| 2016-03-16 06:00:22 | 1) ALL COMMENTS FROM THE PREVIOUS REVIEW MUST BE |
| | ADDRESSED. |
| | 2) SUBMIT 2 COPIES OF THE SURVEY THAT SHOWS THE |
| | LOCATION OF THE GENERATOR AND THE DISTANCE FROM THE |
| | BUILDING WALL TO THE GENERATOR AND ALSO ANY WALL |
| | OPENINGS TO THE GENERATOR. 2014 FBC SEC. 107.1. |
| | 3) THE MINIMUM DISTANCE OF THE GENERATOR TO THE |
| | BUILDING WALL SHALL BE 5 FT. PER NFPA 37 & 2014 FGC |
| | SEC. 616.1. |
| | GENERATORS : NFPA 37 - SEC.4.1.4 |
| | ENGINES LOCATED OUTDOORS |
| | ENGINES AND THEIR WEATHERPROOF HOUSINGS IF PROVIDED, |
| | THAT ARE INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 5 |
| | FT. FROM OPENINGS IN WALLS AND AT LEAST 5 FT. FROM |
| | STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM |
| | SEPARATION SHALL NOT BE REQUIRED WHERE THE FOLLOWING |
| | CONDITIONS EXIST: |
| | (1) THE ADJACENT WALL OF THE STRUCTURE HAS A FIRE |
| | RESISTANCE RATING OF AT LEAST 1 HOUR. |
| | (2) THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF |
| | NONCOMBUSTIBLE MATERIALS, AND IT HAS BEEN DEMONSTRATED |
| | THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE |
| | COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE. |
| | |
| | 4) SUBMIT 2 COPIES OF THE GENERATOR INSTALLATION |
| | MANUAL. 2014 FBC SEC. 107.2.1. |
| | 5) SUBMIT DOCUMENTATION FROM GENERAC FOR THIS GENERATOR |
| | MODEL THAT ALLOWS A REDUCTION OF THE REQUIRED DISTANCE |
| | FROM THE STRUCTURE AS MANDATED IN NFPA 37 SEC. 4.1.4. |
| | 6) THE GENERATOR EXHAUST VENT SHALL BE LOCATED A |
| | MINIMUM OF 10 FEET FROM THE PROPERTY LINE; 3 FEET FROM |
| | EXTERIOR WALLS AND ROOFS AND 10 FEET FROM OPERABLE |
| | OPENINGS INTO BUILDINGS PER 2014 FLORIDA MECHANICAL |
| | CODE SEC.501.3. |
| | 7) SHOW THE LOCATION OF THE GAS METER ON THE SURVEY.FBC |
| | SEC. 107.1. |
| | 8) I AM QUESTIONING THE VALUE OF THIS JOB AT $950.00 |
| | THIS SEEMS LOW FOR THIS TYPE OF INSTALLATION. SUBMIT A |
| | COPY OF THE SIGNED CONTRACT FOR THIS WORK. 2014 FBC |
| | SECTION 109.3. THE COST OF THE GENERATOR MUST BE |
| | INCLUDED IN THE VALUE EVEN IF IT IS BEING PROVIDED BY |
| | THE OWNER. |
| | 9) REMOVE ALL THE OLD DOCUMENTS FROM THE PERMIT PACKAGE |
| | THAT ARE NO LONGER APPLICABLE AND SUBMIT 2 COMPLETE |
| | SETS OF PLANS FOR REVIEW. FBC 107.1. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |