| Plan Review Notes For Permit 16020515 |
| Permit Number |
16020515 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-18 09:46:45 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY PLUMBING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS SPECIFY THE JANDY FLO PRO FHPM 1.0-2 POOL | | | PUMP. THIS IS THE 2 SPEED 1 HP MODEL PUMP. ON SHEET P-2 | | | THE PUMP CURVE FOR THE FHPM .75 HP WAS USED TO | | | DETERMINE THE FLOW RATE IN GPM. THE CALCULATIONS WILL | | | NEED TO BE REDONE USING THE HIGHER SPEED PUMP CURVE. | | | FBCR 4501.6.3 | | | | | | 2) PLUMBING NOTE 3 ON N-1 INCORRECTLY CITES SECTION | | | 605.21 FOR THE REQUIRED PURPLE PRIMER. THE CORRECT | | | SECTION IS 605.22.2. | | | | | | 3) NOTE 1 AND NOTE 11 CITE SECTIONS R4101. IN THE 2014 | | | FBC RESIDENTIAL CODE PRIVATE SWIMMING POOLS HAVE BEEN | | | MOVED TO CHAPTER 45. PLEASE UPDATE THE CODE REFERENCES. | | | | | | |
|