| Plan Review Notes For Permit 16020513 |
| Permit Number |
16020513 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-22 08:02:57 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE REVISED PLANS SHOW THE ADDITION OF TWO (2) NEW | | | HVAC SYSTEMS (#S 4 & 5) ON THE SECOND FLOOR. NO | | | INCREASE TO THE VALUE OF WORK WAS LISTED ON THE | | | REVISION FORM. FBC 109.3 | | | | | | 2) PROVIDE THE EQUIPMENT SCHEDULES FOR THE TWO (2) NEW | | | AHUS AND CONDESERS ON THE MECHANICAL PLANS. 107.2.1 | | | | | | 3) PROVIDE LOAD CALCULATIONS FOR THE NEW SYSTEMS. | | | FBCR-M1401.3 | | | | | | | | | |
|