| 2016-02-19 19:12:53 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 / 2008 NEC | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE APPROVED PLANS FOR THE ELECTRICAL PERMIT | | | (#15080004) WERE PRODUCED, SIGNED AND SEALED BY JOHN E. | | | SKWIOT FLORIDA LICENSED ENGINEER NO. 78805. CHANGES TO | | | THE PLAN ARE REQUIRED TO BE SIGNED AND SEALED BY HIM. | | | IF SOMEONE ELSE IS ASSUMING THE RESPONSIBILITY FOR THE | | | DESIGN, THEN THEIR PRINTED NAME, LICENSE NUMBER AND | | | ORIGINAL HANDWRITTEN SIGNATURE ARE REQUIRED TO BE ON | | | THE PLANS. FBC107.3.4.1 | | | THE NEW PLANS ARE REQUIRED TO INCLUDE ALL OF THE | | | INFORMATION REQUIRED TO SHOW CODE COMPLIANCE FROM THE | | | APPROVED PLANS AND THE PROPOSED CHANGES. | | | | | | 2) PLANS ARE REQUIRED TO BE DRAWN IN PERMANENT INK. | | | PENCIL, CRAYON OR OTHER MARKERS THAT CAN BE EASILY | | | CHANGED ARE NOT ACCEPTABLE. FBC107.2.1.4 | | | |
|