| Plan Review Notes For Permit 16020495 |
| Permit Number |
16020495 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-16 13:41:19 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16020495 | | | 2/16/16 | | | | | | 1) THIS APPEARS TO BE A NEW WALK-IN COOLER INSTALLATION | | | IN AN EXISTING RESTAURANT- PLEASE PROVIDE A DIMENSIONED | | | FLOOR PLAN LAYOUT THAT CLEARLY SHOWS THE LOCATION OF | | | THE NEW COOLER. | | | 2) INDICATE ON THE PLAN THE LOCATIONS OF THE EVAPORATOR | | | AND CONDENSER UNITS, AND PROVIDE WIND LOAD ENGINEERING | | | FOR INSTALLATION OF THE EXTERIOR CONDENSER. | | | 3) PLEASE CLARIFY IF ELECTRIC IS TO BE PROVIDED UNDER | | | THIS PERMIT APPLICATION OR IF TO BE UNDER SEPARATE | | | PERMIT. | | | 4) PROVIDE A CONDENSATE DISPOSAL PLAN INCLUDING THE | | | TYPE AND SIZE OF PIPING, PIPING RUN AND DISCHARGE | | | LOCATION | | | 5) I AM CHALLENGING THE $2,858.00 VALUE ON THE PERMIT | | | APPLICATION IN ACCORDANCE WITH SECTION 109.3, WPB | | | AMENDMENTS OT THE FBC-14 BUILDING CODE. TOTAL VALUE | | | SHALL INCLUDE THE LABOR, MATERIALS, AND EQUIPMENT. | | | PLEASE PROVIDE AN ACCURATE VALUE OR A VALUE WILL BE | | | PLACED ON THE PROJECT BASED ON CURRENT VALUATION DATA | | | TABLES. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|