Plan Review Notes
Plan Review Notes For Permit 16020490
Permit Number 16020490
Review Stop B
Sequence Number 4
Notes
Date Text
2016-08-01 14:32:33BUILDING PLAN REVIEW/ UV PROCESS BUILDING
 W. P. B. PERMIT: 16020490
 ADD: 1009 BANYAN BLVD.
 CONT: POOLE & KENT
 TEL: 305-325-1930
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 4THREVIEW
 DATE: MON. AUG. 01/2016
 ACTION: BUILDING PROVISO
  
 1) BUILDING PROVISO: REQUIRED BEFORE START OF
 WORK!!!!!! RESPONSE INDICATES THE DEWATERING PLAN TO BE
 SUBMITTED BY THE CONTRACTOR. RESPONSE INDICATES
 DEWATERING PLAN TO BE SUBMITTED BY CONTRACTOR. THIS
 PLAN WILL NEED TO BE REVIEWED BY THE DESIGNER OF RECORD
 BEFORE BEING SUBMITTED TO THE BUILDING DEPARTMENT.
 SOILS REPORT BY ARDAMAN & ASSOCIATES ON PAGE 2 OF 8
 DOES INDICATE THE USE OF WELL POINTS. PLEASE PROVIDE
 ENGINEERING AND DEWATERING PLANS FOR THE WELL POINT
 SYSTEM, QUANTITIES OF WATER TO BE DISCHARGED DAILY,
 PROPOSED DISCHARGE POINT AND HOW WILL THE WATERS BE
 DISPENSED FROM THE WELL POINTS TO NOT FILTER INTO THE
 WATERS OF CLEAR LAKE? HAVE PERMITS BEEN SECURED THROUGH
 FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION?
 107.2.1.3 ADMINISTRATIVE CODE. CLEAR WATERS ACT.
  
 2) PROVISO: DATE. 6/05/2016 THE LIFE SAFETY SHEET
 092-17A-2 NOR SHOWS THE INTERIOR WALLS HAVING A 3 HOUR
 RATING THE SHEET 087.4 GA-6 INDICATES WALL TYPE W8 AND
 W9 ARE TO BE A 3 HOUR FIRE RATED BLOCK AND BE IN
 ACCORDANCE WITH UL LISTING U 904, CLASS C-BLOCK IS TO
 BE CERTIFIED BY UNDERWRITERS LABORATORIES INC>, AND
 BEAR A STAMP "CLASSIFIED UL CLASS C-3".
  
  
 3) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (F) SKYLIGHTS
  
 4) DEFERRED SUBMITTAL. 107.3.4.1 THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) PROVISO: DEFERRED SUBMITTAL. FOR ALL ROOFING PRODUCT
 APPROVALS, PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND
 THEIR ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW
 THE PRODUCT APPROVAL LIMITATIONS, AND IF ENHANCED
 FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. IF SO RAS
 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA
 ARCHITECT OR ENGINEER.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  