| Permit Number |
16020490 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-06-22 06:10:36 | 1) IT APPEARS THAT THE PLUMBING PLAN REVIEW COMMENTS | | | FROM THE 5/2/16 HAVE NOT BEEN ADDRESSED AND THE | | | RESPONSE NARRATIVE DATED 6/6 ANSWERS THE SAME COMMENTS | | | FROM THE 3/15/16 REVIEW. | | | 2) THE PIPING PLANS ARE NOT IN COMPLIANCE WITH FL. | | | ADMIN. CODE RULE 61G15-23.005 FOR ELECTRONICALLY | | | SIGNING AND SEALING CONSTRUCTION DOCUMENTS. | | | 3) SHT. 17A-6 - THE GUTTERS SHALL BE SIZED IN | | | ACCORDANCE WITH TABLE 1106.6 OF THE 2014 FPC. INDICATE | | | THE SLOPE OF THE GUTTERS ON THE PLAN. I COULD NOT FIND | | | THIS INFORMATION ANYWHWERE ON SHT. 17A-6. 2ND REQUEST. | | | 4) SHT. 17A-6 - GUTTER AND DOWNSPOUT CALCULATIONS - | | | PLEASE EXPLAIN HOW THE SQUARE FOOTAGE LISTED UNDER | | | "TOTAL AREA" WAS CALCULATED. | | | 5) THE BACKFLOW PREVENTERS SHALL BE SUBMITTED AS A | | | SEPARATE PERMIT. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|