Plan Review Notes
Plan Review Notes For Permit 16020490
Permit Number 16020490
Review Stop P
Sequence Number 3
Notes
Date Text
2016-06-22 06:10:361) IT APPEARS THAT THE PLUMBING PLAN REVIEW COMMENTS
 FROM THE 5/2/16 HAVE NOT BEEN ADDRESSED AND THE
 RESPONSE NARRATIVE DATED 6/6 ANSWERS THE SAME COMMENTS
 FROM THE 3/15/16 REVIEW.
 2) THE PIPING PLANS ARE NOT IN COMPLIANCE WITH FL.
 ADMIN. CODE RULE 61G15-23.005 FOR ELECTRONICALLY
 SIGNING AND SEALING CONSTRUCTION DOCUMENTS.
 3) SHT. 17A-6 - THE GUTTERS SHALL BE SIZED IN
 ACCORDANCE WITH TABLE 1106.6 OF THE 2014 FPC. INDICATE
 THE SLOPE OF THE GUTTERS ON THE PLAN. I COULD NOT FIND
 THIS INFORMATION ANYWHWERE ON SHT. 17A-6. 2ND REQUEST.
 4) SHT. 17A-6 - GUTTER AND DOWNSPOUT CALCULATIONS -
 PLEASE EXPLAIN HOW THE SQUARE FOOTAGE LISTED UNDER
 "TOTAL AREA" WAS CALCULATED.
 5) THE BACKFLOW PREVENTERS SHALL BE SUBMITTED AS A
 SEPARATE PERMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  