| 2016-05-10 16:36:50 | BUILDING PLAN REVIEW/ UV PROCESS BUILDING |
| | W. P. B. PERMIT: 16020490 |
| | ADD: 1009 BANYAN BLVD. |
| | CONT: TBD/ HEATH R. WINTZ |
| | TEL: ????????? |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: TUES. MAY 10/2016 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST. THIS PROJECT WILL NEED A RESIDENT |
| | INSPECTOR FOR THE WORK TO BE PERFORMED UNDER THIS |
| | PERMIT. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 110.3.9 OTHER INSPECTIONS SERVICES. |
| | THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY |
| | OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. HE/SHE |
| | MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED |
| | INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION |
| | HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND |
| | RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION |
| | OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH |
| | REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY |
| | A RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| | SERVICE IN THE FOLLOWING INSTANCES: |
| | FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION, AUGER CAST PILE/ GRADE BEAMS |
| | BUILDINGS WITH WELDED OR BOLTED STEEL MEMBERS. |
| | |
| | 1A) 2ND REQUEST. RESIDENT INSPECTOR FORMS MUST BE |
| | SIGNED BY ALL PARTIES NOTARIZED AND RETURNED TO THE |
| | BUILDING DEPARTMENT. FORMS SENT TO: |
| | [email protected] 03/09/2016 11:14 AM. |
| | |
| | 1B) 2ND REQUEST. FOR THE RESIDENT INSPECTOR PLEASE |
| | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED |
| | |
| | 1C) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 1D) PROVISO: NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS |
| | ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR |
| | THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS. |
| | |
| | 1E) PROVISO: PLEASE CALL THE CITY OF WEST PALM BEACHES? |
| | AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700) |
| | FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 2) SHEET 137_175-11 IS A NEW FOUNDATION DESIGN, WITH |
| | WHAT APPEARS TO BE A 2 FOOT & 2.5 FOOT THICK FOUNDATION |
| | AND THE GRADE FLOOR BEING 2 FOOT THICK. PLEASE PROVIDE |
| | WHERE THE FLOOR PLATE STEEL AND VERTICAL COLUMN STEEL |
| | CAN BE FOUND, THE INDEX IS NOT LABELED AS SUCH. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) SOILS REPORT BY ARDAMAN & ASSOCIATES, THE REPORT IS |
| | NOT DIGITALLY SIGNED. 61G15-23.005 PROCEDURES FOR |
| | SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 4) 2ND REQUEST. RESPONSE INDICATES DEWATERING PLAN TO |
| | BE SUBMITTED BY CONTRACTOR. THIS PLAN WILL NEED TO BE |
| | REVIEWED BY THE DESIGNER OF RECORD BEFORE BEING |
| | SUBMITTED TO THE BUILDING DEPARTMENT. SOILS REPORT BY |
| | ARDAMAN & ASSOCIATES ON PAGE 2 OF 8 DOES INDICATE THE |
| | USE OF WELL POINTS. PLEASE PROVIDE ENGINEERING AND |
| | DEWATERING PLANS FOR THE WELL POINT SYSTEM, QUANTITIES |
| | OF WATER TO BE DISCHARGED DAILY, PROPOSED DISCHARGE |
| | POINT AND HOW WILL THE WATERS BE DISPENSED FROM THE |
| | WELL POINTS TO NOT FILTER INTO THE WATERS OF CLEAR |
| | LAKE? HAVE PERMITS BEEN SECURED THROUGH FLORIDA |
| | DEPARTMENT OF ENVIRONMENTAL PROTECTION? 107.2.1.3 |
| | ADMINISTRATIVE CODE. CLEAR WATERS ACT. |
| | |
| | 5)2ND REQUEST. |
| | THE ARCHITECTURAL SHEETS BY SONG & ASSOCIATES ARE NOT |
| | SIGNED AND SEALED NOR ARE THE STRUCTURAL SHEETS |
| | DESIGNED BY MWH. PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| | BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE |
| | AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. |
| | FL ADMIN CODE 61G16.003 ARCHITECTS |
| | |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS/ EFFECTIVE DATE |
| | 05/06/2009 |
| | |
| | 6) SHEET 090-17A-2 LIFE SAFETY : |
| | 6A-B) COMPLIED. |
| | |
| | 6C) 2ND REQUEST. PLEASE PROVIDE THE MSDS SHEETS FOR THE |
| | CHEMICAL OF SODIUM HYPOCHLORITE. ADDITIONAL INFORMATION |
| | IS REQUIRED. 107.2.1.3. |
| | |
| | 7)2ND REQUEST. THE LIFE SAFETY SHEET SHOWS THE INTERIOR |
| | WALLS HAVING A 3 HOUR RATING, PLEASE PROVIDE WHAT MAKES |
| | UP THE 3 HOUR FIRE RATING? FBC TABLE 722.3.2.? |
| | |
| | 8) 2ND SHEET 091_17A-3. EXIT DOOR TO THE ELECTRICAL |
| | ROOM DOOR # 17-04B . THE DOOR SCHEDULE |
| | (SHEET 088_GA-4) DOES INDICATE HARDWARE GROUP 3, WHERE |
| | IS THIS INFORMATION FOUND IN THE PLANS. PLEASE NOTE WE |
| | DO NOT REVIEW JOB SPECS!!! SHOW COMPLIANCE WITH 2014 |
| | FBC-B 1008.1.10 PANIC HARDWARE CANNOT BE DETERMINED. |
| | ELECTRICAL ROOMS WITH EQUIPMENT RATED 1,200 AMPERES OR |
| | MORE AND OVER 6 FEET (1829 MM) WIDE THAT CONTAIN |
| | OVERCURRENT DEVICES, SWITCHING DEVICES OR CONTROL |
| | DEVICES WITH EXIT OR EXIT ACCESS DOORS SHALL BE |
| | EQUIPPED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE. THE |
| | DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL. |
| | |
| | 9) COMPLIED. |
| | |
| | 10)2ND REQUEST. RESPONSE SHOWED THE ROOF HATCH NOT |
| | COMPLIANCE WITH THE REQUIRED LADDER FOR ROOF ACCESS. |
| | SHEET 137_17S-11 SHOWS A LADDER TO THE ROOF WITH ROOF |
| | TOP ACCESS HATCH. PLEASE PROVIDE DETAILS FOR THE ROOF |
| | TOP LADDER. SHOW COMPLIANCE WITH: 1509.6.4. |
| | |
| | 11) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (F) SKYLIGHTS |
| | |
| | 12) DEFERRED SUBMITTAL. 107.3.4.1 THOSE PRODUCTS WHICH |
| | ARE REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 13) COMPLIED. |
| | |
| | 14) PROVISO: DEFERRED SUBMITTAL. FOR ALL ROOFING |
| | PRODUCT APPROVALS, PLEASE IDENTIFY ALL ROOFING |
| | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, AND |
| | IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| | IF SO RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A |
| | FLORIDA ARCHITECT OR ENGINEER. |
| | |
| | 15) COMPLIED, NO ROOFTOP EQUIPMENT. |
| | |
| | 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |