| Plan Review Notes For Permit 16020490 |
| Permit Number |
16020490 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-21 15:25:13 | PLAN DENIED | | | | | | 1) PROVIDE A DETAIL SHOWING PUMP SUPPORTS AND | | | ANCHORING ( PROVIDE ANCHOR SIZE AND TYPE ) | | | PER SECTION 107 FBC 2014 | | | 2) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS | | | ON HARNESSED JOINT | | | 3) REFER TO SECTION 1206.4 PIPE PENETRATIONS AND | | | 1206.6 CONTACT WITH BUILDING MATERIALS 1214 FBC (M) | | | 4) REFER TO DETAIL H-114 PAGE GH-2 CONDENSATE CAN NOT | | | TIE INTO FLOOR DRAIN OR FLOOR SINK. PER SECTION 90-126 | | | (B) (5) | | | WEST PALM BEACH ORDNANCE. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|