| 2016-02-26 10:54:11 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | NFPA 70- 2011 NEC |
| | COMMENTS: |
| | |
| | 1.PLEASE ADD GENERAL NOTES INDICATING REQUIRED SEPARATE |
| | PERMITS FOR LIGHTNING PROTECTION, FIRE ALARM, CCTV, |
| | CARD READERS ETC. FBC 107.3.5 MINIMUM CRITERIA PLAN |
| | REVIEW. |
| | 2.SHEET GE-4, E1 THRU E5- ADD NOTES TO ALL UNDERGROUND |
| | ACTIVITIES INDICATING FBC 110.3 ELECTRICAL (1). NO |
| | BACKFILL TO OCCUR BEFORE INSPECTIONS ARE PERFORMED. |
| | 3.SHEET E7- PLEASE CLARIFY IF GROUND FAULT PROTECTION |
| | IS BEING ACHIEVED AS PER NEC 230.95, 240.13 BY THE |
| | TRANSFORMER RELAY SHOWN? JUST NEED CLARIFICATION. |
| | 4.PROVIDE DETAILS FOR ALL ELECTRICAL ROOMS TO VERIFY |
| | CLEARANCE PER NEC 110.26, FBC 107.3.5 MINIMUM CRITERIA |
| | PLAN REVIEW. |
| | 5.PROVIDE A NOTE ON MAIN ELECTRICAL ROOMS TO INDICATE |
| | NEC 110.26C3 FOR PERSONNEL DOORS. |
| | 6.AT 90% DRAWINGS AS INDICATED, STILL PENDING TO SHOW |
| | COMPLETE ONE-LINE RISER DIAGRAM INFORMATION PER FBC |
| | 107.3.5 MINIMUM CRITERIA PLAN REVIEW. CONDUCTOR SIZES |
| | FOR ALL, COMPLETE ELECTRICAL CALCULATIONS, PANEL BOARDS |
| | SCHEDULES, AIC CALCULATIONS AND EQUIPMENT RATINGS, |
| | TRANSFORMER SCHEDULES, ETC. |
| | 7.PROVIDE NOTE TO INDICATE NEC 110.16 ARC-FLASH WARNING |
| | LABELS REQUIRED. ALSO NEC 110.24-THE MAXIMUM AVAILABLE |
| | FAULT CURRENT SHALL BE DURABLY MARKED AND DATED ON ALL |
| | ELECTRICAL APPARATUS. |
| | 8.PLEASE CLARIFY IF AT 100% SUBMITTAL YOU WILL SHOW |
| | EITHER THE TROJAN OR WEDECO SELECTION FOR THIS PROJECT? |
| | IF SO ALL REFERENCE NOTES TO EITHER SYSTEM MUST BE |
| | DELETED FROM CONSTRUCTION DOCUMENTS. FBC 107.3.5 |
| | MINIMUM CRITERIA PLAN REVIEW. |
| | 9.THE EXCEPTION REGARDING THE ENERGY CODE AS SUBMITTED |
| | HAS BEEN ACKNOWLEDGE, THIS REVIEW DOES NOT INCLUDE ANY |
| | OF THE STANDARD REQUIREMENTS OF THE FBC ENERGY |
| | CONSERVATION 2014 5TH EDITION. |
| | 10.FURTHER COMMENTS TO FOLLOW AT 100% SUBMITTAL. PLEASE |
| | FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| | REGARDING THIS PROJECT. |
| | |