2016-02-26 10:54:11INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE ADD GENERAL NOTES INDICATING REQUIRED SEPARATE
 PERMITS FOR LIGHTNING PROTECTION, FIRE ALARM, CCTV,
 CARD READERS ETC. FBC 107.3.5 MINIMUM CRITERIA PLAN
 REVIEW.
 2.SHEET GE-4, E1 THRU E5- ADD NOTES TO ALL UNDERGROUND
 ACTIVITIES INDICATING FBC 110.3 ELECTRICAL (1). NO
 BACKFILL TO OCCUR BEFORE INSPECTIONS ARE PERFORMED.
 3.SHEET E7- PLEASE CLARIFY IF GROUND FAULT PROTECTION
 IS BEING ACHIEVED AS PER NEC 230.95, 240.13 BY THE
 TRANSFORMER RELAY SHOWN? JUST NEED CLARIFICATION.
 4.PROVIDE DETAILS FOR ALL ELECTRICAL ROOMS TO VERIFY
 CLEARANCE PER NEC 110.26, FBC 107.3.5 MINIMUM CRITERIA
 PLAN REVIEW.
 5.PROVIDE A NOTE ON MAIN ELECTRICAL ROOMS TO INDICATE
 NEC 110.26C3 FOR PERSONNEL DOORS.
 6.AT 90% DRAWINGS AS INDICATED, STILL PENDING TO SHOW
 COMPLETE ONE-LINE RISER DIAGRAM INFORMATION PER FBC
 107.3.5 MINIMUM CRITERIA PLAN REVIEW. CONDUCTOR SIZES
 FOR ALL, COMPLETE ELECTRICAL CALCULATIONS, PANEL BOARDS
 SCHEDULES, AIC CALCULATIONS AND EQUIPMENT RATINGS,
 TRANSFORMER SCHEDULES, ETC.
 7.PROVIDE NOTE TO INDICATE NEC 110.16 ARC-FLASH WARNING
 LABELS REQUIRED. ALSO NEC 110.24-THE MAXIMUM AVAILABLE
 FAULT CURRENT SHALL BE DURABLY MARKED AND DATED ON ALL
 ELECTRICAL APPARATUS.
 8.PLEASE CLARIFY IF AT 100% SUBMITTAL YOU WILL SHOW
 EITHER THE TROJAN OR WEDECO SELECTION FOR THIS PROJECT?
 IF SO ALL REFERENCE NOTES TO EITHER SYSTEM MUST BE
 DELETED FROM CONSTRUCTION DOCUMENTS. FBC 107.3.5
 MINIMUM CRITERIA PLAN REVIEW.
 9.THE EXCEPTION REGARDING THE ENERGY CODE AS SUBMITTED
 HAS BEEN ACKNOWLEDGE, THIS REVIEW DOES NOT INCLUDE ANY
 OF THE STANDARD REQUIREMENTS OF THE FBC ENERGY
 CONSERVATION 2014 5TH EDITION.
 10.FURTHER COMMENTS TO FOLLOW AT 100% SUBMITTAL. PLEASE
 FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  