2016-03-10 14:53:12BUILDING PLAN REVIEW/ UV PROCESS BUILDING
 W. P. B. PERMIT: 16020490
 ADD: 1009 BANYAN BLVD.
 CONT: TBD/ HEATH R. WINTZ
 TEL: ?????????
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. MARCH 04/2016
 ACTION: DENIED
  
 1) THIS PROJECT WILL NEED A RESIDENT INSPECTOR FOR THE
 WORK TO BE PERFORMED UNDER THIS PERMIT. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING
 OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE
 INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT
 REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION
 SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS
 SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A
 CERTIFICATE CALLED FOR BY ANY PROVISION OF THE
 TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS
 UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES:
 FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION, AUGER CAST PILE/ GRADE BEAMS
 BUILDINGS WITH WELDED OR BOLTED STEEL MEMBERS.
  
  
 1A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT. FORMS SENT TO: [email protected]
 03/09/2016 11:14 AM.
  
 1B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED
  
 1C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 1E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2) SHEET 116GS-14 INDICATES THE USE OF 14 INCH AGER
 CAST PILE. NO DEPTH INFORMATION IS GIVEN AS TO THE
 LENGTH OF THE PILE. SHEET 103GS-1 DOES HAVE NOTES UNDER
 THE HEADING ACIP PILE CAPACITIES DESIGN WORKING LOAD
 ALL LOADING INFORMATION OF THE AUGER CAST PILE ARE
 UNKNOWNS MARKED BY XX.XX. THE SOILS REPORT THAT WAS
 COMPLETED BY ARDAMAN & ASSOCIATES DOES NOT MENTION THE
 USE OF AUGER CAST PILE. IT SEAMS THERE ARE SOME
 UNKNOWNS THAT WILL NEED TO BE ESTABLISHED FOR THE
 DESIGN VALUES FOR THE AUGER CAST PILES. WILL THERE BE A
 GEOTECHNICAL ENGINEER ON SITE TO LOG THE DATA FOR THE
 AUGER CAST PILE? WHO WILL IT BE, NOTHING MENTIONED IN
 THE STRUCTURAL SHEETS? 2014 FBC-B 1810.2 ANALYSIS. THE
 ANALYSIS OF DEEP FOUNDATIONS FOR DESIGN SHALL BE IN
 ACCORDANCE WITH SECTIONS 1810.2.1 THROUGH 1810.2.5.
  
 1810.3.3.1.7 LOAD-BEARING CAPACITY.
 DEEP FOUNDATION ELEMENTS SHALL DEVELOP ULTIMATE LOAD
 CAPACITIES OF AT LEAST TWICE THE DESIGN WORKING LOADS
 IN THE DESIGNATED LOAD-BEARING LAYERS. ANALYSIS SHALL
 SHOW THAT NO SOIL LAYER UNDERLYING THE DESIGNATED
 LOAD-BEARING LAYERS CAUSES THE LOAD-BEARING CAPACITY
 SAFETY FACTOR TO BE LESS THAN TWO.
  
 3) SOILS REPORT BY ARDAMAN & ASSOCIATES ON PAGE 3 OF 8
 DOES INDICATE THE USE OF SHEET PILES AT NEARBY
 STRUCTURES AND PIPELINES AND THE RISK ASSOCIATED WITH
 DRIVEN SHEET PILE AND RECOMMENDS THE PUSHING THE SHEETS
 INTO THE GROUND RATHER THAN THE VIBRATING THEM INTO
 PLACE. THE SOILS REPORT DOES NOT INDICATE HOW MUCH TOE
 OR EMBEDMENT WILL BE REQUIRED TO KEEP THE SOILS FROM
 SHIFTING?
  
 FBC-B 1803.5.7 EXCAVATION NEAR FOUNDATIONS. WHERE
 EXCAVATION WILL REMOVE LATERAL SUPPORT FROM ANY
 FOUNDATION, AN INVESTIGATION SHALL BE CONDUCTED TO
 ASSESS THE POTENTIAL CONSEQUENCES AND ADDRESS
 MITIGATION MEASURES.
  
 1804.1 EXCAVATION NEAR FOUNDATIONS.
 EXCAVATION FOR ANY PURPOSE SHALL NOT REMOVE LATERAL
 SUPPORT FROM ANY FOUNDATION WITHOUT FIRST UNDERPINNING
 OR PROTECTING THE FOUNDATION AGAINST SETTLEMENT OR
 LATERAL TRANSLATION.
  
 4) SOILS REPORT BY ARDAMAN & ASSOCIATES ON PAGE 2 OF 8
 DOES INDICATE THE USE OF WELL POINTS. PLEASE PROVIDE
 ENGINEERING AND DEWATERING PLANS FOR THE WELL POINT
 SYSTEM, QUANTITIES OF WATER TO BE DISCHARGED DAILY,
 PROPOSED DISCHARGE POINT AND HOW WILL THE WATERS BE
 DISPENSED FROM THE WELL POINTS TO NOT FILTER INTO THE
 WATERS OF CLEAR LAKE? HAVE PERMITS BEEN SECURED THROUGH
 FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION?
 107.2.1.3 ADMINISTRATIVE CODE. CLEAR WATERS ACT.
  
 5) THE ARCHITECTURAL SHEETS BY SONG & ASSOCIATES ARE
 NOT SIGNED AND SEALED NOR ARE THE STRUCTURAL SHEETS
 DESIGNED BY MWH.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 FL ADMIN CODE 61G15-23.002 ENGINEERS/ EFFECTIVE DATE
 05/06/2009
  
 6) SHEET 090-17A-2 LIFE SAFETY :
 6A) THIS SHEET SHOWS THE USE OF SODIUM HYPOCHLORITE DAY
 TANK (A H3 HIGH HAZARD CLASS 3). PLEASE CONFIRM HOW
 MANY GALLONS THE DAY TANK CAN HOLD? AND THE TYPE OF
 MATERIALS THIS TANK IS MADE FROM? FBC-B 415.9
  
 6B) THE ROOM INDICATES A 12 INCH CURB FOR A SECOND
 MEANS OF CONTAINMENT, HOW MANY GALLONS OF LIQUID WILL
 THIS AREA HOLD? FBC-B415.8.2.4. LEAKAGE CONTAINMENT.
  
 6C) PLEASE PROVIDE THE MSDS SHEETS FOR THE CHEMICAL OF
 SODIUM HYPOCHLORITE. ADDITIONAL INFORMATION IS
 REQUIRED. 107.2.1.3.
  
 7) THE LIFE SAFETY SHEET SHOWS THE INTERIOR WALLS
 HAVING A 3 HOUR RATING, PLEASE PROVIDE WHAT MAKES UP
 THE 3 HOUR FIRE RATING? FBC TABLE 722.3.2.?
  
 8) SHEET 091_17A-3. EXIT DOOR TO THE ELECTRICAL ROOM
 DOOR # 17-04B . THE DOOR SCHEDULE
 (SHEET 088_GA-4) DOES NOT PROVIDE ANY INFORMATION AS TO
 HARDWARE TYPE. COMPLIANCE WITH 2014 FBC-B 1008.1.10
 PANIC HARDWARE CANNOT BE DETERMINED. ELECTRICAL ROOMS
 WITH EQUIPMENT RATED 1,200 AMPERES OR MORE AND OVER 6
 FEET (1829 MM) WIDE THAT CONTAIN OVERCURRENT DEVICES,
 SWITCHING DEVICES OR CONTROL DEVICES WITH EXIT OR EXIT
 ACCESS DOORS SHALL BE EQUIPPED WITH PANIC HARDWARE OR
 FIRE EXIT HARDWARE. THE DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL.
 9) SHEET 133_17S-7 THIS SHEET INDICATES THE
 INSTALLATION OF SKYLIGHTS WITH DETAIL S-551. PLEASE
 PROVIDE WHERE THIS DETAIL IS PROVIDED IN THE PLANS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
 10) SHEET 137_17S-11 SHOWS A LADDER TO THE ROOF WITH
 ROOF TOP ACCESS HATCH. PLEASE PROVIDE DETAILS FOR THE
 ROOF TOP LADDER. SHOW COMPLIANCE WITH: 1509.6.4.
 11) PLEASE SUPPLY THE PRODUCT APPROVALS FOR COMPLIANCE
 WITH: 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (F) SKYLIGHTS
  
 12) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 13) FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIXE.
  
 14) FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED. IF SO RAS 117
 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA ARCHITECT
 OR ENGINEER.
  
 15) FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF DECK AS WELL AS FROM
 THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2014
 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved