| Plan Review Notes For Permit 16020455 |
| Permit Number |
16020455 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-16 08:08:39 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16020455 | | | 2/16/16 | | | | | | 1) PROVIDE THE SCOP RATING ON THE EQUIPMENT SCHEDULE | | | FOR THE NEW LIEBERT SYSTEM- SEE TABLE C403.2.3(10) | | | FBC-14 ENERGY CONSERVATION. | | | 2) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF | | | THE NEW CU-2 ON THE EXISTING EXTERIOR PAD.- SECTION | | | 301.15 FBC-14 MECHANICAL. | | | 3) PLEASE NOTE THAT THE PERMIT VALUE SHALL BE BASED ON | | | LABOR, MATERIALS, AND EQUIPMENT, THEREFORE THE COST OF | | | THE NEW 20-TON SYSTEM MUST BE INCLUDED IN THE TOTAL | | | PROJECT COST- SECTION 109.3 WPB AMENDMENTS TO THE | | | FBC-14 BUILDING CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|