2016-05-19 09:41:07MECHANICAL PROVISOS
 5/19/16
  
 SEPARATE PERMITS ARE REQUIRED FOR ALL KITCHEN EXHAUST
 HOODS AND FIRE SUPPRESSION SYSTEMS.
 REVISIONS TO THE APPROVED PLANS SHALL BE PROVIDED TO
 SHOW COMPLIANCE WITH THE FOLLOWING PROVISIONS.
  
 1) DUCT SMOKE DETECTORS SHALL BE PROVIDED IN THE RETURN
 AIR SYSTEMS OF THE ERUS. PROVIDE A NOTE IN THE
 EQUIPMENT SCHEDULE.
  
 2) THE DRYER EXHAUST DUCTS SHALL NOT EXTEND THROUGH THE
 RETURN AIR PLENUMS. THE DUCTS SHALL BE RE-ROUTED OR
 INSTALLED IN AN ENCLOSURE.
  
 3) THE CONTRACTOR SHALL SUBMIT APPROVED SHOP DRAWINGS
 FOR EQUIPMENT ACCESS PANELS.
  
 4) CHEMICAL AND PAINT STORAGE ROOMS: PROVIDE ON THE
 ARCHITECTURAL PLANS A COMPLETE LIST OF CHEMICALS AND
 PAINTS TO BE STORED IN THE ROOMS, THE HAZARD
 CLASSIFICATIONS FOR EACH PRODUCT, THE MAXIMUM ALLOWABLE
 QUANTITIES FOR EACH, AND THE ACTUAL AMOUNTS TO BE
 STORED.
  
 5) FIRE DAMPER LOCATIONS, SCHEDULES, AND INSTALLATION
 DETAILS.
  
 6) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S
 FOR ALL EXTERIOR MECHANICAL EQUIPMENT INCLUDING RTU AND
 FAN CURBS, ROOF AND WAL-MOUNTED FANS, AC STANDS, AND
 LOUVERS ETC. SHALL BE REVIEWED AND APPROVED BY THE EOR,
 AND SUBMITTED TO THE BUILDING DEPARTMENT FOR REVIEW AND
 APPROVAL PRIOR TO 1ST INSPECTION.
  
 7) PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION,
 THE REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE
 EVIDENCE OF MECHANICAL SYSTEM COMMISSIONING AND
 COMPLETION IN ACCORDANCE WITH SECTION C408.2.4 AND
 C408.2.5 FBC-14 ENERGY CONSERVATION.
  
 8) REVISE SHEETS M2.114 & M2.117 TO INDICATE ADEQUATE
 EXHAUST CAPACITIES IN THE LOCKER AND BATH ROOMS PER THE
 CALCULATIONS ON SHEET M0.07.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  