| 2016-05-19 09:41:07 | MECHANICAL PROVISOS |
| | 5/19/16 |
| | |
| | SEPARATE PERMITS ARE REQUIRED FOR ALL KITCHEN EXHAUST |
| | HOODS AND FIRE SUPPRESSION SYSTEMS. |
| | REVISIONS TO THE APPROVED PLANS SHALL BE PROVIDED TO |
| | SHOW COMPLIANCE WITH THE FOLLOWING PROVISIONS. |
| | |
| | 1) DUCT SMOKE DETECTORS SHALL BE PROVIDED IN THE RETURN |
| | AIR SYSTEMS OF THE ERUS. PROVIDE A NOTE IN THE |
| | EQUIPMENT SCHEDULE. |
| | |
| | 2) THE DRYER EXHAUST DUCTS SHALL NOT EXTEND THROUGH THE |
| | RETURN AIR PLENUMS. THE DUCTS SHALL BE RE-ROUTED OR |
| | INSTALLED IN AN ENCLOSURE. |
| | |
| | 3) THE CONTRACTOR SHALL SUBMIT APPROVED SHOP DRAWINGS |
| | FOR EQUIPMENT ACCESS PANELS. |
| | |
| | 4) CHEMICAL AND PAINT STORAGE ROOMS: PROVIDE ON THE |
| | ARCHITECTURAL PLANS A COMPLETE LIST OF CHEMICALS AND |
| | PAINTS TO BE STORED IN THE ROOMS, THE HAZARD |
| | CLASSIFICATIONS FOR EACH PRODUCT, THE MAXIMUM ALLOWABLE |
| | QUANTITIES FOR EACH, AND THE ACTUAL AMOUNTS TO BE |
| | STORED. |
| | |
| | 5) FIRE DAMPER LOCATIONS, SCHEDULES, AND INSTALLATION |
| | DETAILS. |
| | |
| | 6) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S |
| | FOR ALL EXTERIOR MECHANICAL EQUIPMENT INCLUDING RTU AND |
| | FAN CURBS, ROOF AND WAL-MOUNTED FANS, AC STANDS, AND |
| | LOUVERS ETC. SHALL BE REVIEWED AND APPROVED BY THE EOR, |
| | AND SUBMITTED TO THE BUILDING DEPARTMENT FOR REVIEW AND |
| | APPROVAL PRIOR TO 1ST INSPECTION. |
| | |
| | 7) PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, |
| | THE REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE |
| | EVIDENCE OF MECHANICAL SYSTEM COMMISSIONING AND |
| | COMPLETION IN ACCORDANCE WITH SECTION C408.2.4 AND |
| | C408.2.5 FBC-14 ENERGY CONSERVATION. |
| | |
| | 8) REVISE SHEETS M2.114 & M2.117 TO INDICATE ADEQUATE |
| | EXHAUST CAPACITIES IN THE LOCKER AND BATH ROOMS PER THE |
| | CALCULATIONS ON SHEET M0.07. |
| | |