Plan Review Notes
Plan Review Notes For Permit 16020418
Permit Number 16020418
Review Stop P
Sequence Number 2
Notes
Date Text
2016-04-27 06:02:241) ) SHT. A3.23 - ACCESSIBLE ROLL-IN SHOWER WITH GRAB
 BAR AND SEAT DETAIL SH 3 - THIS IS CONSIDERED AS AN
 ALTERNATE ROLL-IN SHOWER DUE TO THE SIZE (36 X 60
 INCHES). THE LOCATION OF THE SHOWER SEAT SHALL COMPLY
 WITH THE 2014 FBC-ACCESSIBILITY SEC.610.3 AND THE
 LOCATION OF THE SHOWER CONTROLS SHALL COMPLY
 FBC-ACCESSIBILITY SEC.608.5.3.PROVIDE DETAILS THAT SHOW
 COMPLIANCE.
 2) DEFINE THE OCCUPANCY FOR THIS STRUCTURE. THE AMOUNT
 OF COMBUSTIBLE/FLAMMABLE LIQUID STORAGE APPEARS TO
 DEFINE THIS STRUCTURE AS AN "H" OCCUPANCY PER CHAPT.
 307.4, 307.5 & CHAPT. 4 OF THE 2014 FBC. PLEASE SUBMIT
 A COPY OF THE LETTER FROM HOWE ENGINEERS DATED MARCH23,
 2016 PROVIDED IN A RESPONSE COMMENT TO WESLEY JOLIN
 WHICH INDICATES THAT THE QUANTITIES OF THE VARIOUS
 MATERIALS STORED DO NOT REQUIRE THE BUILDING TO BE
 CONSIDERED AN "H" OCCUPANCY. I COULD NOT FIND THIS
 LETTER IN THE SUPPRTING DOCUMENT FOLDER. SEE RESPONSE
 TO PLUMBING PLAN REVIEW COMMENTS FROM HKS DATED APRIL
 14, 2016.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
 **** NOTE**** THE FOLLOWING COMMENTS ARE PROVISOS FOR
 THE PLUMBING PLAN REVIEW ONLY. THE GAS PLAN REVIEW WILL
 BE LISTED AS A SEPARATE REVIEW. THE PROVISOS SHALL BE
 SATISFIED BY THE SUBMITTAL OF THE REQUIRED INFORMATION
 PRIOR TO ANY PLUMBING INSPECTIONS BEING PERFORMED AT
 THESE AREAS. TIM LARGE, CHIEF PLUMBING INSPECTOR.
 3) SHT.IR 1.07 - SUBMIT COMPLETE DETAILS FOR THE ACID
 INJECTION SYSTEM FOR THE IRRIGATION SYSTEM, CONTAINMENT
 SYSTEM, PUMPS,VALVES,PIPING, ETC. SHOW HOW THIS AREA
 WILL BE PROTECTED AGAINST UNAUTHORIZED ENTRY. 2014 FBC
 SEC.107.2.1.
 4) SUBMIT MSDS DATA FOR THE CHEMICALS TO BE USED FOR
 THE ACID INJECTION SYSTEM FOR THE IRRIGATION SYSTEM.
 2014 FBC SEC.107.2.1.
 5) THE LAUNDRY AREAS IN THE CLUBHOUSES SHALL COMPLY
 WITH THE 2014 FBC- ACCESSIBILITY SECS .611 & 309. ALL
 WASHERS AND DRYERS SHALL COMPLY WITH THE REQUIREMENTS
 FOR CLEAR FLOOR SPACE, OPERABLE PARTS, AND HEIGHT.
 6) SHT.P4.003 - APPROVAL IS REQUIRED FROM THE PALM
 BEACH COUNTY DEPARTMENT OF ENVIRONMENTAL RESOURCE
 PROTECTION FOR THE ABOVE GROUND FUEL STORAGE TANKS PER
 PALM BEACH COUNTY ORDINANCE #2015-008.
 7) THE SANITARY AND WATER RISERS ARE INCOMPLETE AND
 DEFICIENT AND A THOROUGH AND COMPREHENSIVE REVIEW COULD
 NOT BE DONE AT THIS TIME. AS-BUILT SANITARY AND WATER
 RISERS SHALL BE SUBMITTED DURING THE INSPECTION PROCESS
 FOR THESE SYSTEMS.
 8) MANUFACTURER'S SPECIFICATIONS FOR THE FUEL
 DISPENSERS, TANKS, VALVES, ETC. SHALL BE SUBMITTED FOR
 REVIEW. 2014 FBC SEC.107.2.1.
 9) THE FUEL TANKS, DISPENSERS AND ALL ASSOCIATED PIPING
 SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 30, 2012
 EDITION AS ADOPTED BY THE 2014 FBC.
 10) SUBMIT A CONDENSATE RISER FOR REVIEW. THE
 CONDENSATE SHALL NOT DISCHARGE INTO THE SANITARY SYSTEM
 OR THE GREASY WASTE SYSTEM PER THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES AND 2014 FBC SEC.1003.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  