2016-03-09 11:01:155444 NORTH HAVERHILL ROAD
 PERMIT #16020418
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 SHEET LS1.02: A FIRE IN CORRIDOR #11237 HAS THE
 POTENTIAL TO BLOCK BOTH EXITS FROM COACH'S LOCKER
 #11415. PER SECTION 7.5.1.3.1 WHERE MORE THAN ONE EXIT,
 EXIT ACCESS, OR EXIT DISCHARGE IS REQUIRED FROM A
 BUILDING OR PORTION THEREOF, SUCH EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE ARRANGED TO MINIMIZE THE POSSIBILITY THAT
 MORE THAN
 ONE HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR
 OTHER EMERGENCY CONDITION.
  
 SHEET A2.227: 1ST FLOOR LOBBY #11711 IS OPEN TO THE
 SECOND FLOOR RECEPTION #12704. PER SECTION 8.6.9.2
 UNENCLOSED VERTICAL OPENINGS CREATED BY CONVENIENCE
 STAIRWAYS SHALL BE PERMITTED AS FOLLOWS: 1) THE
 CONVENIENCE STAIR OPENING SHALL NOT SERVE AS A REQUIRED
 MEANS OF EGRESS 2) THE CONVENIENCE STAIR OPENING SHALL
 BE PROTECTED IN ACCORDANCE WITH THE METHOD DETAILED FOR
 THE PROTECTION OF VERTICAL OPENINGS IN NFPA 13,
 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
  
 SHEET A2.324 1ST FLOOR LOBBY #11408 IS OPEN TO THE
 SECOND FLOOR CORRIDOR #12412B. PER SECTION 8.6.9.2
 UNENCLOSED VERTICAL OPENINGS CREATED BY CONVENIENCE
 STAIRWAYS SHALL BE PERMITTED AS FOLLOWS: 1) THE
 CONVENIENCE STAIR OPENING SHALL NOT SERVE AS A REQUIRED
 MEANS OF EGRESS 2) THE CONVENIENCE STAIR OPENING SHALL
 BE PROTECTED IN ACCORDANCE WITH THE METHOD DETAILED FOR
 THE PROTECTION OF VERTICAL OPENINGS IN NFPA 13,
 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
  
 SHEET E1.00: PROVIDE AMBULANCE/RESCUE VEHICLE120V SHORE
 POWER RECHARGING STATION ALONG FIRE LANE NEAR SITE PLAN
 MARKER #8.
  
 SHEET E2.411: PROVIDE AMBULANCE/RESCUE VEHICLE120V
 SHORE POWER RECHARGING STATION IN VEHICLE ENTRANCE
 TUNNEL ADJACENT TO THE BULLPEN.
  
 IN GENERAL THE EMERGENCY LIGHTING AND EXIT SIGN
 PLACEMENT IS INCONSISTENT. FOR EXAMPLE:
 SHEET E3.110: COULD ONLY LOCATE 1 EMERGENCY LIGHT
 FIXTURE.
 SHEET E3.111: CORRIDOR #11130 INDICATES A LIGHT FIXTURE
 F7 WITH AN "EM" DESIGNATION. THIS APPEARS TO BE
 POSSIBLY EMERGENCY LIGHTING BUT THE EM ABBREVIATION IS
 NOT FOUND OR DESCRIBED ON SHEET E0.01. ALSO CORRIDOR
 #11130 HAS AN EXIT SIGN LEADING OCCUPANTS THROUGH A
 HIGHER HAZARD (MAINT. SHOP) WHICH IS NOT PERMITTED.
 SHEET E3.111: NO EMERGENCY LIGHTING ON MEZZANINE AND
 ONLY 1 EXIT SIGN PROVIDED IN MAINTENANCE SHOP #11125.
 SHEET E3.118: NO EXIT SIGNS IN LOCKER ROOM #11718.
 SHEET E3.119: NO EXIT SIGNS OR EMERGENCY LIGHTS IN MLB
 EQUIP. #11917; OTHER LARGE ROOMS SIMILAR TO THIS ROOM
 HAVE BOTH.
  
 FIRE ALARM PLANS DO NOT INDICATE A SCALE.
  
 FA2.110: DOES NOT APPEAR TO BE SUFFICIENT VISUAL
 COVERAGE IN UMPIRE SHOWER #11031.
  
 FA2.113: NO NOTIFICATION PROVIDED IN SAUNAS. INADEQUATE
 COVERAGE PROVIDED FOR EAST PORTION OF WEIGHTS #11318.
 NO NOTIFICATION CONFERENCE #11301.
  
 FA2.118: NO NOTIFICATION PROVIDED IN EAST PORTION OF
 KITCHEN. NO PULL STATION PROVIDED AT GYM STAIR EXIT
 DOOR.
  
 FA2.122: NO NOTIFICATION PROVIDED IN EAST PORTION OF
 KITCHEN.
  
 FA2.124: NO NOTIFICATION IN NORTH ROOM OF COMMISSARY
 #12405 AND WEST ROOM OF CONCESSION #12404.
  
 FA2.127: NO PULL STATION AT EXIT DOOR.
  
 FA2.128: NO PULL STATION AT EXIT DOOR.
  
 FA2.134: NO NOTIFICATION IN WOMENS' RESTROOM #13414.
  
 SIGNAGE: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 SIGNAGE: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730