| 2016-03-09 11:01:15 | 5444 NORTH HAVERHILL ROAD |
| | PERMIT #16020418 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY |
| | REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE |
| | (2012 EDITION WITH FLORIDA AMENDMENTS.) |
| | |
| | SHEET LS1.02: A FIRE IN CORRIDOR #11237 HAS THE |
| | POTENTIAL TO BLOCK BOTH EXITS FROM COACH'S LOCKER |
| | #11415. PER SECTION 7.5.1.3.1 WHERE MORE THAN ONE EXIT, |
| | EXIT ACCESS, OR EXIT DISCHARGE IS REQUIRED FROM A |
| | BUILDING OR PORTION THEREOF, SUCH EXITS, EXIT ACCESSES, |
| | OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH |
| | OTHER AND BE ARRANGED TO MINIMIZE THE POSSIBILITY THAT |
| | MORE THAN |
| | ONE HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR |
| | OTHER EMERGENCY CONDITION. |
| | |
| | SHEET A2.227: 1ST FLOOR LOBBY #11711 IS OPEN TO THE |
| | SECOND FLOOR RECEPTION #12704. PER SECTION 8.6.9.2 |
| | UNENCLOSED VERTICAL OPENINGS CREATED BY CONVENIENCE |
| | STAIRWAYS SHALL BE PERMITTED AS FOLLOWS: 1) THE |
| | CONVENIENCE STAIR OPENING SHALL NOT SERVE AS A REQUIRED |
| | MEANS OF EGRESS 2) THE CONVENIENCE STAIR OPENING SHALL |
| | BE PROTECTED IN ACCORDANCE WITH THE METHOD DETAILED FOR |
| | THE PROTECTION OF VERTICAL OPENINGS IN NFPA 13, |
| | STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS. |
| | |
| | SHEET A2.324 1ST FLOOR LOBBY #11408 IS OPEN TO THE |
| | SECOND FLOOR CORRIDOR #12412B. PER SECTION 8.6.9.2 |
| | UNENCLOSED VERTICAL OPENINGS CREATED BY CONVENIENCE |
| | STAIRWAYS SHALL BE PERMITTED AS FOLLOWS: 1) THE |
| | CONVENIENCE STAIR OPENING SHALL NOT SERVE AS A REQUIRED |
| | MEANS OF EGRESS 2) THE CONVENIENCE STAIR OPENING SHALL |
| | BE PROTECTED IN ACCORDANCE WITH THE METHOD DETAILED FOR |
| | THE PROTECTION OF VERTICAL OPENINGS IN NFPA 13, |
| | STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS. |
| | |
| | SHEET E1.00: PROVIDE AMBULANCE/RESCUE VEHICLE120V SHORE |
| | POWER RECHARGING STATION ALONG FIRE LANE NEAR SITE PLAN |
| | MARKER #8. |
| | |
| | SHEET E2.411: PROVIDE AMBULANCE/RESCUE VEHICLE120V |
| | SHORE POWER RECHARGING STATION IN VEHICLE ENTRANCE |
| | TUNNEL ADJACENT TO THE BULLPEN. |
| | |
| | IN GENERAL THE EMERGENCY LIGHTING AND EXIT SIGN |
| | PLACEMENT IS INCONSISTENT. FOR EXAMPLE: |
| | SHEET E3.110: COULD ONLY LOCATE 1 EMERGENCY LIGHT |
| | FIXTURE. |
| | SHEET E3.111: CORRIDOR #11130 INDICATES A LIGHT FIXTURE |
| | F7 WITH AN "EM" DESIGNATION. THIS APPEARS TO BE |
| | POSSIBLY EMERGENCY LIGHTING BUT THE EM ABBREVIATION IS |
| | NOT FOUND OR DESCRIBED ON SHEET E0.01. ALSO CORRIDOR |
| | #11130 HAS AN EXIT SIGN LEADING OCCUPANTS THROUGH A |
| | HIGHER HAZARD (MAINT. SHOP) WHICH IS NOT PERMITTED. |
| | SHEET E3.111: NO EMERGENCY LIGHTING ON MEZZANINE AND |
| | ONLY 1 EXIT SIGN PROVIDED IN MAINTENANCE SHOP #11125. |
| | SHEET E3.118: NO EXIT SIGNS IN LOCKER ROOM #11718. |
| | SHEET E3.119: NO EXIT SIGNS OR EMERGENCY LIGHTS IN MLB |
| | EQUIP. #11917; OTHER LARGE ROOMS SIMILAR TO THIS ROOM |
| | HAVE BOTH. |
| | |
| | FIRE ALARM PLANS DO NOT INDICATE A SCALE. |
| | |
| | FA2.110: DOES NOT APPEAR TO BE SUFFICIENT VISUAL |
| | COVERAGE IN UMPIRE SHOWER #11031. |
| | |
| | FA2.113: NO NOTIFICATION PROVIDED IN SAUNAS. INADEQUATE |
| | COVERAGE PROVIDED FOR EAST PORTION OF WEIGHTS #11318. |
| | NO NOTIFICATION CONFERENCE #11301. |
| | |
| | FA2.118: NO NOTIFICATION PROVIDED IN EAST PORTION OF |
| | KITCHEN. NO PULL STATION PROVIDED AT GYM STAIR EXIT |
| | DOOR. |
| | |
| | FA2.122: NO NOTIFICATION PROVIDED IN EAST PORTION OF |
| | KITCHEN. |
| | |
| | FA2.124: NO NOTIFICATION IN NORTH ROOM OF COMMISSARY |
| | #12405 AND WEST ROOM OF CONCESSION #12404. |
| | |
| | FA2.127: NO PULL STATION AT EXIT DOOR. |
| | |
| | FA2.128: NO PULL STATION AT EXIT DOOR. |
| | |
| | FA2.134: NO NOTIFICATION IN WOMENS' RESTROOM #13414. |
| | |
| | SIGNAGE: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| | DOORS WITH EXIT SIGNS. |
| | |
| | SIGNAGE: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED |
| | SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED |
| | IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE |
| | ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT |
| | RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE |
| | RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION |
| | 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT |
| | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED |
| | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, |
| | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE |
| | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT |
| | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A |
| | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR |
| | VIOLATIONS OF THIS CODE. |
| | |