Plan Review Notes
Plan Review Notes For Permit 16020418
Permit Number 16020418
Review Stop E
Sequence Number 2
Notes
Date Text
2016-03-10 18:57:591ST ELECTRICAL REVIEW NOTES FOR REVISION #:
 16020418, 16020417, 16020419
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 SHEET E0.01
 0. INCLUDE ON THE SHEET DRAWINGS THE DRAWING SCALE
 BEING USED. CITY OF WEST PALM BEACH AMENDMENTS LIMITS
 DRAWINGS TO NO LESS THAN 1/8? SCALE.
 1. THIS SYMBOL MAY INTERFERE OR BE CONFUSED WITH THAT
 OF THE EXIT LIGHTS.
 2. NEC 406.9(B), WEATHER-PROOF RECEPTACLES IN ?WET
 LOCATIONS? SHALL BE LISTED ?WEATHER-RESISTANT?.
 3. INDICATE ON THE LIGHTING LEGEND WHICH OF THE
 FIXTURES WILL HAVE A BATTERY PACK OR BE TIED INTO AN
 EMERGENCY LIGHTING CIRCUIT.
 SHEET E0.02
 1. INDICATE ON THE FIXTURE SCHEDULE WHICH OF THE
 FIXTURES WILL HAVE BATTERY BALLAST.
 SHEET E2.110, E2.111, E2.112, E2.113, E2.114, E2.115,
 E2.117, E2.118, E2.119, E2.121, E2.122, E2.123, E2.124,
 E2.125, E2.126, E2.127, E2.128, E2.129, E2.132, E2.134,
 E2.135, E2.136, E2.137, E2.145, E2.411, E2.412, E2.413,
 1. NEC 210.8(B)(7) RECEPTACLES IN LOCKER ROOMS WITH
 ASSOCIATED SHOWERS SHALL BE GFCI PROTECTED.
 2. NEC 408.9(B) .....AND BE LISTED "WEATHER-RESISTANT"
 "WR".
 SHEET E2.113
 1. IDENTIFY OR CORRECT THE ?NG? FOLLOWING THE NUMERIC
 RATING IN THE NUMBERED NOTES.
 SHEETS E2.116, E2.130, E2131, E2.140, E2.141, E2.142,
 E2.143, E2.144, E3.116,
 1. THESE SHEETS ARE MISSING. IS THIS PAGE INTENTIONALLY
 SKIPPED OR IS IT AN ERROR.
 SHEET E2.126 STORE AREA
 1. NEC 210.62 SHOW WINDOW REQUIREMENT, THERE SHALL BE A
 120 VAC OUTLET WITH 18? OF THE TOP OF EVERY SHOW WINDOW
 FOR EVERY 12? OF SHOW WINDOW OR MAJOR PORTION THEREOF.
 2. NEC 600.5 SIGN OUTLET REQUIREMENT. THERE SHALL BE A
 DEDICATED SIGN OUTLET AT EVERY PEDESTRIAN ENTRY DOOR.
 SHEET E3.110, E3.111,
 1. IN ADDITION TO THE MISSING EMERGENCY LIGHTING, YOU
 SHALL SHOW COMPLIANCE WITH FBC-EC405 FOR LIGHT
 REDUCTION.
 2. ACCORDING TO THE FIXTURE SCHEDULE THE EXIT LIGHTS DO
 NOT HAVE BATTERY BACK UP. (TYPICAL)
 SHEET E3.513
 1. EXHAUST FANS REQUIRED FOR THE TOILET ROOMS.
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER