| 2016-03-10 18:57:59 | 1ST ELECTRICAL REVIEW NOTES FOR REVISION #: |
| | 16020418, 16020417, 16020419 |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 |
| | NFPA 70 2011 (NEC) |
| | |
| | CORRECTIONS REQUIRED: |
| | SHEET E0.01 |
| | 0. INCLUDE ON THE SHEET DRAWINGS THE DRAWING SCALE |
| | BEING USED. CITY OF WEST PALM BEACH AMENDMENTS LIMITS |
| | DRAWINGS TO NO LESS THAN 1/8? SCALE. |
| | 1. THIS SYMBOL MAY INTERFERE OR BE CONFUSED WITH THAT |
| | OF THE EXIT LIGHTS. |
| | 2. NEC 406.9(B), WEATHER-PROOF RECEPTACLES IN ?WET |
| | LOCATIONS? SHALL BE LISTED ?WEATHER-RESISTANT?. |
| | 3. INDICATE ON THE LIGHTING LEGEND WHICH OF THE |
| | FIXTURES WILL HAVE A BATTERY PACK OR BE TIED INTO AN |
| | EMERGENCY LIGHTING CIRCUIT. |
| | SHEET E0.02 |
| | 1. INDICATE ON THE FIXTURE SCHEDULE WHICH OF THE |
| | FIXTURES WILL HAVE BATTERY BALLAST. |
| | SHEET E2.110, E2.111, E2.112, E2.113, E2.114, E2.115, |
| | E2.117, E2.118, E2.119, E2.121, E2.122, E2.123, E2.124, |
| | E2.125, E2.126, E2.127, E2.128, E2.129, E2.132, E2.134, |
| | E2.135, E2.136, E2.137, E2.145, E2.411, E2.412, E2.413, |
| | 1. NEC 210.8(B)(7) RECEPTACLES IN LOCKER ROOMS WITH |
| | ASSOCIATED SHOWERS SHALL BE GFCI PROTECTED. |
| | 2. NEC 408.9(B) .....AND BE LISTED "WEATHER-RESISTANT" |
| | "WR". |
| | SHEET E2.113 |
| | 1. IDENTIFY OR CORRECT THE ?NG? FOLLOWING THE NUMERIC |
| | RATING IN THE NUMBERED NOTES. |
| | SHEETS E2.116, E2.130, E2131, E2.140, E2.141, E2.142, |
| | E2.143, E2.144, E3.116, |
| | 1. THESE SHEETS ARE MISSING. IS THIS PAGE INTENTIONALLY |
| | SKIPPED OR IS IT AN ERROR. |
| | SHEET E2.126 STORE AREA |
| | 1. NEC 210.62 SHOW WINDOW REQUIREMENT, THERE SHALL BE A |
| | 120 VAC OUTLET WITH 18? OF THE TOP OF EVERY SHOW WINDOW |
| | FOR EVERY 12? OF SHOW WINDOW OR MAJOR PORTION THEREOF. |
| | 2. NEC 600.5 SIGN OUTLET REQUIREMENT. THERE SHALL BE A |
| | DEDICATED SIGN OUTLET AT EVERY PEDESTRIAN ENTRY DOOR. |
| | SHEET E3.110, E3.111, |
| | 1. IN ADDITION TO THE MISSING EMERGENCY LIGHTING, YOU |
| | SHALL SHOW COMPLIANCE WITH FBC-EC405 FOR LIGHT |
| | REDUCTION. |
| | 2. ACCORDING TO THE FIXTURE SCHEDULE THE EXIT LIGHTS DO |
| | NOT HAVE BATTERY BACK UP. (TYPICAL) |
| | SHEET E3.513 |
| | 1. EXHAUST FANS REQUIRED FOR THE TOILET ROOMS. |
| | |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |