| 2016-03-08 08:59:02 | 1) SHT.C9.21 - GREASE/WATER SEPARATOR DETAIL - THE CITY |
| | DETAIL ON THE PLAN IS AN OUTDATED DETAIL. REFER TO |
| | DETAIL GS 7 ISSUED IN 2015. |
| | 2) SHT. IR1.07 - SUBMIT COMPLETE DETAILS FOR THE ACID |
| | INJECTION SYSTEM FOR THE IRRIGATION SYSTEM, CONTAINMENT |
| | SYSTEM, PUMPS, VALVES, PIPING, ETC. FBC 107.2.1. SHOW |
| | HOW THIS AREA WILL BE PROTECTED AGAINST UNAUTHORIZED |
| | ENTRY. |
| | 3) SUBMIT MSDS DATA FOR THE CHEMICALS USED FOR THE ACID |
| | INJECTION SYSTEM FOR THE IRRIGATION SYSTEM.FBC 107.2.1. |
| | 4) SHT. A1.22 - DETAIL #2 - THE GUTTERS FOR THE BATTING |
| | TUNNEL ROOF SHALL BE SIZED IN ACCORDANCE WITH TABLE |
| | 1106.6 OF THE 2014 FL. PLUMBING CODE. CLEARLY THE |
| | LOCATION OF ALL GUTTERS ON THE PLAN. |
| | 5) THE ROOM FINISH PLAN ON SHT. A3.40 SHOWS THE WALLS |
| | IN SOME OF THE RESTROOMS AND TOILET ROOMS AS PAINT. |
| | 2014 FBC SEC. 1210.2.2 REQUIRES WALLS AND PARTITIONS |
| | WITHIN 2 FEET OF SERVICE SINKS, URINALS AND WATER |
| | CLOSETS TO HAVE A SMOOTH, HARD, NONABSORBENT SURFACE TO |
| | A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE |
| | FLOOR.EXCEPTION:TOILET ROOMS THAT ARE NOT ACCESSIBLE TO |
| | THE PUBLIC AND WHICH HAVE NOT MORE THAN ONE WATER |
| | CLOSET. |
| | 6) SINKS LOCATED IN BREAK ROOM AREAS SHALL COMPLY WITH |
| | THE 2014 FAC SEC.212 & 606. |
| | 7) THE LAUNDRY AREAS SHALL COMPLY WITH THE 2014 FAC |
| | SEC.611. |
| | 8) SHT. A2.913 - DETAIL # 01 - THE WATER CLOSET SHALL |
| | BE LOCATED DIAGONALLY OF THE COMPARTMENT DOOR PER 2014 |
| | FAC SEC.604.8.1.2. |
| | 9) SHT. A2.914 - DETAILS # 3 & #4 - THE DOOR SHALL BE |
| | LOCATED PER FAC SEC.604.8.1.2. |
| | 10) SHT.A3.23 - DETAIL EWC 3 - THE SPOUT ON THE HIGH |
| | SIDE DRINKING FOUNTAIN SHALL BE LOCATED 38-43 INCHES |
| | ABOVE THE FINISH FLOOR OR GROUND PER THE FAC SEC.602.7. |
| | 11) SHT.A#.23 - ACCESSIBLE ROLL IN SHOWER WITH GRAB BAR |
| | AND SEAT - THIS IS CONSIDERED AN ALTERNATE ROLL- IN |
| | TYPE SHOWER DUE TO THE SIZE (36" X 60") AND THE |
| | LOCATION OF THE SHOWER SEAT SHALL COMPLY WITH THE 2014 |
| | FAC SEC.610.3 AND THE LOCATION OF THE CONTROLS SHALL |
| | COMPLY WITH SEC.608.5.3. |
| | 12) SHT. A3.23 - ACCESSIBLE SHOWER TRANSFER - THE |
| | CONTROLS SHALL BE A MINIMUM OF 38 INCHES AND A MAXIMUM |
| | OF 48 INCHES ABOVE THE SHOWER FLOOR AND SHALL BE |
| | LOCATED ON THE CONTROL WALL 15 INCHES MAXIMUM FROM THE |
| | CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING. FAC |
| | SEC.608.5.1. |
| | 13) TOILET PAPER DISPENSERS IN THE ACCESSIBLE TOILET |
| | ROOMS/COMPARTMENTS SHALL BE LOCATED A MINIMUM OF 7 |
| | INCHES AND A MAXIMUM OF 9 INCHES IN FRONT OF THE WATER |
| | CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER. FAC |
| | SEC.604.7. |
| | 14) SHT. A8.21 - ALL NEWLY INSTALLED UNDERGROUND |
| | HYDRAULIC PRESSURE CYLINDERS SHALL BE ENCASED IN OUTER |
| | PLASTIC CONTAINMENT TO MINIMIZE ELECTROLYTIC CORROSION |
| | BETWEEN THE METAL CYLINDER AND GROUND CATHODE. 2014 FBC |
| | SEC.3011.1. |
| | 15) SHT. P0.03 - THE PLUMBING FIXTURE SCHEDULE SHOWS |
| | LAVATORY FAUCETS 2B & 2C WITH COLD WATER ONLY. HOT OR |
| | TEMPERED SHALL BE SUPPLIED TO THE LAVATORIES PER FPC |
| | SEC.607.1.THE WATER RISERS SHALL CLEARLY SHOW |
| | HOT/TEMPERED WATER TO THE REQUIRED FIXTURES. |
| | 16) SHT. P2.001, 002 & 003 - THE OVERALL PLANS ARE |
| | PEPPERED WITH DARK MARKS AND ARE IMPOSSIBLE TO SEE WHAT |
| | THEY REPRESENT. CLARIFY. |
| | 17) SHT. P2.114 - THERE IS A GREASY WASTE LINE THAT |
| | APPEARS TO BE ALSO LABELED AS A SANITARY LINE.SEE AREA |
| | BETWEEN GRID LINES S17 & S18 AND SG & SH. PLEASE CHECK |
| | ALL SHEETS TO ENSURE THE DRAINAGE LINES ARE PROPERLY |
| | LABELED. |
| | 18) SHT.P4.003 - APPROVAL IS REQUIRED FROM THE PALM |
| | BEACH COUNTY DEPT. OF ENVIRONMENTAL RESOURCE PROTECTION |
| | FOR THE ABOVE GROUND FUEL STORAGE TANKS. PBC ORD. # |
| | 2015 - 008. |
| | 19) SHT. P4.003 - THE FUELING SCHEMATIC REFERS TO |
| | SEVERAL DETAILS ( A,B,C, ETC.) WHERE ARE THESE DETAILS? |
| | CLARIFY. |
| | 20) SHT.P4.003 - NUMBERED NOTE #1 REFERS TO A ONE |
| | THOUSAND GALLON DIVIDED FUEL TANK BUT THE FUELING |
| | SYSTEM SCHEMATIC SHOWS A DIVIDED 2500 GALLON TANK. |
| | CLARIFY. |
| | 21) THE SANITARY AND WATER RISERS ARE INCOMPLETE AND |
| | DEFICIENT AND A THOROUGH AND COMPREHENSIVE REVIEW COULD |
| | NOT BE DONE AT THIS TIME. AS-BUILT SANITARY AND WATER |
| | RISERS WILL BE SUBMITTED DURING THE INSPECTION PROCESS. |
| | 22) PLACE THE ROOM NUMBERS ON THE ENLARGED PLANS. IT IS |
| | DIFFICULT TO LOCATE THESE AREAS ON THE PLAN VIEW |
| | LAYOUT. FBC 107.2.1. |
| | 23) SAMPLING PORTS ARE REQUIRED ON THE DISCHARGE SIDE |
| | OF EACH GREASE INTERCEPTOR PER THE CWPB STANDARD |
| | DRAWING GS-7.1. |
| | 24) SUBMIT MANUF. SPECIFICATIONS FOR THE RETROCEPTOR |
| | SHOWN IN THE STADIUM SUITE LEVEL PARTY DECK. |
| | 25) SHT. S5.101.5 - THERE ARE NUMBERED NOTE TAGS ON THE |
| | RISER DIAGRAM BUT THERE ARE NO NUMBERED NOTES ON THE |
| | DRAWING. CLARIFY. |
| | 26) SHT.P5.401 - THE SHEET DRAWING NUMBERS THAT SHOW |
| | THE CONTINUATION OF THE FUEL GAS SYSTEM ARE ILLEGIBLE . |
| | SUBMIT A PLAN THAT CLEARLY SHOWS THE SHEET DRAWING |
| | NUMBERS. FBC 107.2.1. |
| | 27) CLEARLY SHOW THE LOCATION OF ALL MEDIUM PRESSURE |
| | GAS REGULATORS ON THE GAS RISERS. FBC 107.2.1. |
| | 28) CLEARLY SHOW THE PIPE SIZES OF THE PIPING |
| | DOWNSTREAM OF THE MP REGULATOR.FBC 107.2.1. |
| | 29) SIZE ALL SECTIONS OF THE PIPING ON ALL GAS |
| | RISERS.FBC 107.2.1. |
| | 30) IDENTIFY THE GAS METER ON THE GAS RISER ON |
| | SHT.P5.401. |
| | 31) IDENTIFY EACH PIECE OF GAS EQUIPMENT ON THE GAS |
| | RISER AND THE BTU LOAD FOR EACH PICE OF |
| | EQUIPMENT/APPLIANCE.FBC 107.2.1. |
| | 31) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 |
| | FBC-FUEL GAS CODE SEC.304.1. |
| | 32) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| | AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS |
| | SECS. 502 THRU 505. |
| | 33) ALL EQUIPMENT SHALL BE LISTED AND LABELED IN |
| | ACCORDANCE WITH 2014 FGC SEC.301.3. |
| | 34) SHT. P5.401 - MEP EQUIPMENT SCHEDULE SHOWS THE |
| | GWH-2 AS 1950 MBH BUT SHEET P5.401.1 APPEARS TO SHOW |
| | GWH-2 WITH LESS BTU'S. CLARIFY. |
| | 35) SHT. P5.401.3 - SUBMIT AN EXPANDED GAS RISER |
| | DIAGRAM FOR THE WATER HEATERS AND SHOW THE REGULATOR. |
| | IT IS IMPOSSIBLE TO SEE WHERE THE MEDIUM PRESSURE AND |
| | LOW PRESSURE PIPING BEGINS AND ENDS. |
| | 36) THE FOLLOWING COMMENTS ARE ALL FOR SHT. P5.402 - |
| | THE 2" MEP LINE IS UNDERSIZED.TABLE 402.4 (5) LIMITS A |
| | 2' LINE TO 2010MBH.THE DRAWING SHOWS A BTU LOAD FROM |
| | 2010 MBH UP TO 3030 MBH. |
| | 37) THE 1 1/4 " LINE WITH 700MBH IS UNDERSIZED.MAXIMUM |
| | ALLOWED BY TABLE 402.4 (5) IS 695 MBH. THE LINE SHALL |
| | BE 1 1/2" MINIMUM. |
| | 38) THE 1" MEDIUM PRESSURE LINE WITH 440 MBH IS |
| | UNDERSIZED. MAXIMUM IS 339MBH.THE LINE SHALL BE 1 1/4". |
| | 39) THE 1 1/2" MEDIUM PRESSURE LINE CARRYING 1640MBH |
| | NEEDS TO BE 2" PER TABLE 402.4 (5). |
| | 40) THE 1 1/2" MEDIUM PRESSURE LINE CARRYING 1440 MBH |
| | NEEDS TO BE 2". |
| | 41) THE 1"MP LINE CARRYING 440 MBH NEEDS TO BE 1 1/4". |
| | 42) SHT. P5.402.1 - THE FOLLOWING COMMENTS ARE ALL |
| | APPLICABLE TO SHT.P5.402.1. |
| | 43) THE 1 1/4" MP LINE CARRYING 700 MBH IS UNDERSIZED. |
| | IT NEEDS TO BE 1 1/2". |
| | 44) THE 1" MP & LOW PRESSURE LINE CARRYING 440 MBH IS |
| | UNDERSIZED. BOTH LINES NEED TO BE 1 1/4". |
| | 45) THE 3/4" MP LINE CARRYING 300 MBH IS UNDERSIZED. IT |
| | NEEDS TO BE 1". THE LOW PRESSURE SAID NEEDS TO BE 1 |
| | 1/4". |
| | 46) THE 1 1/2" MP LINE CARRYING 1440 MBH IS UNDERSIZED. |
| | IT NEEDS TO BE 2". TABLE 402.4 (5). |
| | 47) THE 1 1/2" MP LINE CARRYING 1640MBH IS UNDERSIZED. |
| | IT NEEDS TO BE 2". TABLE 402.4 (5). |
| | 48)SHT. P5.402.2. - THE FOLLOWING COMMENTS ARE ALL |
| | APPLICABLE TO SHT. P5.402.2. - |
| | 49) THE 1 1/2" MP LINE CARRYING 1640MBH IS UNDERSIZED. |
| | IT NEEDS TO BE 2". |
| | 50) THE 2" MP LINE CARRYING 2080MBH IS UNDERSIZED. IT |
| | NEEDS TO BE 2 1/2". TABLE 402.4 (5). |
| | 51) THE 1" MP LINE CARRYING 440MBH IS UNDERSIZED. IT |
| | NEEDS TO BE 1 1/4". |
| | 52) THE 2" MP LINE CARRYING 2130 IS UNDERSIZED. IT |
| | NEEDS TO BE 2 1/2". |
| | 53) THE 1 1/4" LOW PRESSURE LINE CARRYING 700MBH IS |
| | UNDERSIZED. IT NEEDS TO BE 1 1/2". |
| | 54) THE 2" MP LINE CARRYING 3030MBH IS UNDERSIZED.IT |
| | NEEDS TO BE 2 1/2". |
| | 55) THE 3" MP LINE CARRYING 6930MBH IS UNDERSIZED. IT |
| | NEEDS TO BE 4". |
| | 56) THE 2 1/2" MP LINE CARRYING 3900 IS UNDERSIZED. IT |
| | NEEDS TO BE 3". |
| | 57) THE 2" LOW PRESSURE LINE CARRYING 1950MBH IS |
| | UNDERSIZED. IT NEEDS TO BE 2 1/2'. |
| | 58) THE FOLLOWING COMMENTS ARE ALL APPLICABLE TO |
| | SHT.P5.403. |
| | 59) PROVIDE THE TEXT FOR NUMBERED NOTE #1. |
| | 60) THE 1" MP LINE CARRYING 500MBH IS UNDERSIZED. IT |
| | NEEDS TO BE 1 1/4". |
| | 61) THE 1 1/2" MP LINE CARRYING 1320MBH IS UNDERSIZED. |
| | IT NEEDS TO BE 2". |
| | 62) THE 1 1/4"MP LINE CARRYING 700MBH IS UNDERSIZED. IT |
| | NEEDS TO BE 1 1/2". |
| | 63) THE 2" MP LINE CARRYING 2020MBH, 2220MBH, AND 2320 |
| | MBH IS UNDERSIZED. IT NEEDS TO BE 2 1/2". |
| | 64) THE 3/4" MP LINE CARRYING 200MBH IS UNDERSIZED. IT |
| | NEEDS TO BE 1". |
| | 65) THE 1 1/2" MP LINE CARRYING 1320MBH IS UNDERSIZED. |
| | IT NEEDS TO BE 2". |
| | 66) THE 3" MP LINE CARRYING 6970 MBH IS UNDERSIZED. IT |
| | NEEDS TO BE 4". |
| | 67) THE 2 1/2" MP LINE CARRYING 3900MBH IS UNDERSIZED. |
| | IT NEEDS TO BE 3". |
| | 68) SHT.P5.403.1 - CHECK THE ENTIRE RISER FOR CORRECT |
| | SIZING AND COMPLY WITH 2014 FGC TABLES 402.4 (1) AND |
| | 402.4 (5). THE RISER IS UNDERSIZED FOR THE BTU LOAD. |
| | 69) SHT. P5.403.2 - CHECK THE ENTIRE RISER FOR CORRECT |
| | SIZING AND COMPLY WITH 2014 FGC TABLES 402.4 (1) AND |
| | 402.4 (5). THE RISER IS UNDERSIZED FOR THE BTU LOAD. |
| | 70) SHT.P4.003 - SUBMIT A LEGEND FOR ALL THE COMPONENT |
| | TAGS THAT ARE SHOWN ON THE PLAN. FBC 107.2.1. |
| | 71) INDICATE THE LIQUID CLASS FOR THE GASOLINE ON THE |
| | PLANS IN ACCORDANCE WITH CHAPT.2 OF 2014 FBC. |
| | 72) MANUFACTURER'S SPECIFICATIONS FOR DISPENSERS, |
| | TANKS, VALVES, ETC. SHALL BE SUBMITTED FOR REVIEW. THE |
| | DOCUMENTS CAN BE SUBMITTED NOW OR BE A DEFERRED |
| | SUBMITTAL IN ACCORDANCE WITH FBC 107.3.4.2. |
| | 73) DEFINE THE OCCUPANCY FOR THIS STRUCTURE. THE AMOUNT |
| | OF COMBUSTIBLE/FLAMMABLE LIQUID STORAGE APPEARS TO |
| | DEFINE THIS STRUCTURE AS AN "H" OCCUPANCY PER CHAPT. |
| | 307.4, 307.5 & CHAPT. 4 OF THE 2014 FBC. |
| | 74) THE TANKS,DISPENSERS AND ALL ASSOCIATED PIPING AND |
| | CONSTRUCTION OF THE ENCLOSURE SHALL COMPLY WITH NFPA 30 |
| | AND 2014 FBC. |
| | 75) SUBMIT A CONDENSATE RISER FOR REVIEW. THE |
| | CONDENSATE SHALL NOT DISCHARGE TO THE SANITARY PER CITY |
| | ORDINANCE OR TO THE GREASY WASTE SYSTEM. 2014 FBC SEC. |
| | 1003.2. |
| | |