Plan Review Notes
Plan Review Notes For Permit 16020418
Permit Number 16020418
Review Stop M
Sequence Number 1
Notes
Date Text
2016-03-09 17:41:061ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020418
 BALLPARK OF THE PALM BEACHES
 3/8/16
  
 1) THE DESIGN PROFESSIONALS OF RECORD MUST SIGN AND
 PROVIDE THEIR PROFESSIONAL REGISTRATION NUMBERS ON PAGE
 3 OF THE ENERGY CONSERVATION FORM SUBMITTAL- SEE
 SECTION C103.1.1.1.2 FBC-14 ENERGY CONSERVATION.
 2) DISCREPANCIES BETWEEN THE ENERGY FORM AND THE
 MECHANICAL PLANS:
 A) THE FORM LISTS ERU-A-2-5 CAPACITY AT 75300 BTUH ,
 THE AC SCHEDULE ON SHEET M0.02 LISTS THE CAPACITY AT
 92000 BTUH
 B) ENERGY FORM LISTS ERU-A-2-6 AT 75300, SCHEDULE-
 92,000.
 C) ENERGY FORM LISTS COMPLIANCE DATA FOR AHU-S-2-4 ,
 HOWEVER THIS SYSTEM IS NOT INCLUDED IN THE EQUIPMENT
 SCHEDULES ON THE PLANS.
 D) THE SPLIT SYSTEMS, THE 100% O/A SYSTEMS, THE DHU'S,
 THE COMPUTER ROOM AC, AND MANY OF THE VRF SYSTEMS ARE
 NOT LISTED IN THE ENERGY CONSERVATION FORM.
 3) THE AC COOLING AND HEATING CALCULATIONS MUST BE
 SIGNED AND SEALED BY THE DESIGN PROFESSIONAL OF RECORD:
 SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
 4) DISCREPANCIES BETWEEN THE AC CALCULATIONS AND THE
 MECHANICAL PLANS:
 A) CALCULATED COOLING LOAD FOR ACC-S-4 IS 391 MBH,
 HOWEVER THE SCHEDULE ON SHEET M0.04 INDICATES THE
 CAPACITY AT 528 MBH.
 B) AHU-A-2-1 COOLING LOAD- 925 MBH / SCHEDULE ON SHEET
 M0.02 INDICATES CAPACITY AT 836 MBH
 C) AHU-N-2-1 LOAD- 695 MBH/ SCHEDULE- 835 MBH.
 D) AHU-N-2-2 LOAD- 786 MBH/ SCHEDULE- 732 MBH.
 E) AHU- S-3-1 LOAD- 121.9 MBH/SCHEDULE- 197 MBH.
 F) AHU-S-3-2 LOAD- 52.8 MBH/ SCHEDULE- 87 MBH.
 G) AHU-S-3-4 LOAD- 58 MBH/ SCHEDULE-83.
 H) AHU-S-2-4 IS SHOWN IN THE CALCS BUT NOT IN THE
 SCHEDULES.
 I) AHU-S-3-5 IS SHOWN IN THE SCHEDULE BUT NOT IN THE
 CALCS.
 J) DHU-N-2-1 LOAD- 81.3 MBH/SCHEDULE- 133 MBH.
 K) ERU-A-2-5 LOAD- 245.7 MBH/ SCHEDULE- 92 MBH
 L) ERU-A-3-1 LOAD- 131.8 MBH/ SCHEDULE- 92 MBH.
 M) ERU-N-2-5 LOAD- 180 MBH/ SCHEDULE- 112.5 MBH.
 N) ERU-N-2-6 LOAD- 286.6 MBH/ SCHEDULE- 92 MBH.
 O) CLARIFY WHICH SYSTEMS WERE SIZED UNDER THE LOAD
 CALCULATIONS PAGES TITLED "MISC" AND "SYSTEM 023": I
 CANNOT CONNECT THESE UP WITH THE AC SCHEDULES.
 IN REFERENCE TO THE DISCREPANCIES ABOVE PLEASE REFER TO
 SECTION C403.2.2 FBC-14 ENERGY CONSERVATION.
  
 2) SHEETS M0.03: INDICATE HOW EACH EXHAUST FAN IN THE
 SCHEDULE WAS SIZED: PROVIDE EXHAUST VENTILATION
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.3 FBC-14
 MECHANICAL, AND TABLE 6-4 ASHRAE 62.1-2010.
 3) M0.04: REFER TO TABLE C403.2.3(10) FBC ENERGY
 CONSERVATION AND PROVIDE THE SCOP RATING FOR THE
 COMPUTER ROOM AC UNITS.
 4) M2.03 & M2.04: THE PLANS APPEAR TO INDICATE
 MECHANICAL SYSTEMS ON THE SUITE AND ROOF LEVELS OF
 SECTOR A, HOWEVER THERE ARE NO ENLARGED PLANS FOR THOSE
 AREAS IN THE SETS AND THERE ARE ROOF TOP UNITS ON THE
 CONCOURSE LEVEL OF SECTOR A- PLEASE CLARIFY.
 5) DUCT SMOKE DETECTORS ARE REQUIRED IN RETURN AIR
 SYSTEMS WITH DESIGN CAPACITIES GREATER THAN 2000 CFM
 PER SECTION 606.2.1 FBC-14 MECHANICAL. MANY OF THE
 PROPOSED AC SYSTEMS FOR THE PROJECT HAVE RETURN AIR
 SYSTEMS EXCEEDING THAT THRESHOLD. PLEASE PROVIDE DS
 DETECTOR SYMBOLS ON THE PLANS WHERE APPLICABLE, AND
 PROVIDE NOTES AND DETAILS CLARIFYING THE SEQUENCE OF
 OPERATION FOR THE DETECTORS AND HOW THEY WILL BE
 SUPERVISED- SECTION 606.4.1. PLEASE INCLUDE AN
 INSTALLATION DETAIL FOR THE DEVICES AND A PRODUCT
 SUBMITTAL APPROVED BY THE ENGINEER OF RECORD.
 6) M2.110 AND ALL MECH. PLAN SHEETS: NUMEROUS SYMBOLS
 FOR ACCESS PANELS ARE SHOWN FOR THE ABOVE CEILING CAV'S
 AND VAV'S. REFER TO SECTION 306.1 AND PROVIDE THE
 DIMENSION AND CONSTRUCTION DETAILS FOR THE PANELS.
 PLEASE NOTE THE PANELS SHALL BE LARGE ENOUGH TO REMOVE
 AND REPLACE THE EQUIPMENT WITHOUT REMOVING PERMANENT
 CONSTRUCTION.
 7) M2.111: PROVIDE A KEY NOTE IDENTIFYING WHICH AC
 SYSTEM IS PROVIDING THE 20X16 SUPPLY AND RETURN DUCT
 DROPS.
 8) M2.111: PROVIDE KEY NOTES IDENTIFYING WHICH EXHAUST
 FANS ARE SERVICING THE EXHAUST DUCT RISERS SHOWN IN THE
 AREA OF THE CHEMICAL AND PAINT STORAGE ROOMS.
 9) M2.111: CHEMICAL AND PAINT STORAGE ROOMS: A) REFER
 TO SECTION 414.1.3 FBC-14 BUILDING: [F] 414.1.3
 INFORMATION REQUIRED.
 A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO
 SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION
 CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE
 METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT
 NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS
 AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE
 REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION
 AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON,
 FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL
 AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY.
 FOR BUILDINGS AND STRUCTURES WITH AN OCCUPANCY IN GROUP
 H, SEPARATE FLOOR PLANS SHALL BE SUBMITTED IDENTIFYING
 THE LOCATIONS OF ANTICIPATED CONTENTS AND PROCESSES SO
 AS TO REFLECT THE NATURE OF EACH OCCUPIED PORTION OF
 EVERY BUILDING AND STRUCTURE.
 B) PROVIDE ON THE PLAN AN ITEMIZED LIST OF THE
 HAZARDOUS MATERIALS TO BE STORED AND THEIR EXPECTED
 QUANTITIES, AND SUBMIT MSDS SHEETS FOR EACH ITEM. C)
 PROVIDE EXHAUST VENTILATION CALCULATIONS FOR EACH
 EXHAUST SYSTEM, INDICATE THE TYPE OF EXHAUST DUCTWORK
 TO BE INSTALLED, AND SEQUENCE OF OPERATION FOR THE
 FANS- SEE SECTIONS 502.8.1.1 & 510.1- 510.9. PLEASE
 NOTE THAT FIRE SUPPRESSION MAY BE REQUIRED FOR THE
 EXHAUST DUCTS. D) REFER TO SECTION 510.5.5 AND INDICATE
 HOW MAKE-UP AIR IS BEING PROVIDED FOR THE SYSTEMS AND
 THE RATE. PLEASE NOTE THAT THE SOURCE OF THE MAKE-UP
 AIR MUST BE DIRECTLY FROM THE OUTDOORS AND TRANSFER
 DUCTS FROM ADJOINING ROOMS CANNOT BE USED.
 10) M2.111: FIRE DAMPERS ARE REQUIRED FOR THE 12X12
 LOCKER AND RESTROOM EXHAUST DUCT PENETRATING THE
 FIRE-RATED PAINT STORAGE WALLS IN ACCORDANCE WITH
 SECTION 607.5.2 FBC-14 MECHANICAL.
 11) M2.111: PROVIDE THROUGH-PENETRATION FIRESTOPPING
 SYSTEM DETAILS FOR DUCTS PENETRATING FIRE-RATED WALLS-
 SEE SECTION 714.1.1 FBC-14 BUILDING.
 12) M2.111: INDICATE THE REQUIRED CLEARANCES FOR THE
 EXHAUST OUTLETS FROM EF S-1-1 AND EF S-1-2: REFER TO
 SECTION 501.3.1 FBC-14 MECHANICAL. IDENTIFY THE ROOMS
 IN THE MAINTENANCE MEZZANINE AND INDICATE A SOURCE OF
 MAKE-UP AIR FOR THE EXHAUST SYSTEMS.
 13) M2.111: PLEASE NOTE THAT ALL EXTERIOR EXHAUST
 OUTLET AND AIR INTAKE OPENINGS SHOWN ON THIS PLAN SHEET
 AND ALL OTHERS MUST BE PROTECTED IN ACCORDANCE WITH
 SECTIONS 1609.1.2 AND 1609.6.4.4.1 FBC-14 BUILDING.
 MIAMI-DADE NOA'S AND/OR FLORIDA PRODUCT APPROVALS SHALL
 BE SUBMITTED FOR ALL COMPONENTS AND CLADDINGS WITH
 REVIEW AND APPROVAL SIGNATURES FROM THE DESIGN
 PROFESSIONALS OF RECORD.
  
 14) M2.112, LAUNDRY: A) PROVIDE AN EQUIPMENT SCHEDULE
 ON THE PLAN FOR THE DRYERS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS REVIEWED AND APPROVED BY THE DESIGN
 PROFESSIONAL OF RECORD. B) A COMBUSTION AIR INTAKE DUCT
 IS INDICATED- PROVIDE COMBUSTION AIR CALCULATIONS FOR
 SIZING THE DUCT. C) EXPAND NUMBERED NOTE #5 TO INDICATE
 THE TYPE AND GAGE OF DUCT MATERIAL, THE INTAKE HOOD THE
 DUCT IS CONNECTED TO, AND HOW THE DUCT WILL BE
 SUPPORTED. D) EXPAND NUMBERED NOTE #1 TO INDICATE
 COMPLIANCE WITH SECTION 504.7: COMMERCIAL CLOTHES
 DRYERS.
 THE INSTALLATION OF DRYER EXHAUST DUCTS SERVING
 COMMERCIAL CLOTHES DRYERS SHALL COMPLY WITH THE
 APPLIANCE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
 EXHAUST FAN MOTORS INSTALLED IN EXHAUST SYSTEMS SHALL
 BE LOCATED OUTSIDE OF THE AIRSTREAM. IN MULTIPLE
 INSTALLATIONS, THE FAN SHALL OPERATE CONTINUOUSLY OR BE
 INTERLOCKED TO OPERATE WHEN ANY INDIVIDUAL UNIT IS
 OPERATING. DUCTS SHALL HAVE A MINIMUM CLEARANCE OF 6
 INCHES (152 MM) TO COMBUSTIBLE MATERIALS. CLOTHES DRYER
 TRANSITION DUCTS USED TO CONNECT THE APPLIANCE TO THE
 EXHAUST DUCT SYSTEM SHALL BE LIMITED TO SINGLE LENGTHS
 NOT TO EXCEED 8 FEET (2438 MM) IN LENGTH AND SHALL BE
 LISTED AND LABELED FOR THE APPLICATION. TRANSITION
 DUCTS SHALL NOT BE CONCEALED WITHIN CONSTRUCTION. E)
 SEE TABLE 403.3 AND PROVIDE OUTSIDE AIR CALCULATIONS
 FOR THE LAUNDRY AREA. F) SUBMIT SPECS FOR THE ENERVEX
 MEC 18 EXHAUST CONTROL SYSTEM REVIEWED AND APPROVED BY
 THE DESIGN PROFESSIONAL OF RECORD.
 15) M2.112: PROVIDE NUMBERED KEY NOTES AT THE MAIN
 SUPPLY AND RETURN DUCT DROPS TO IDENTIFY WHICH AC AND
 ERU SYSTEMS ARE SERVICING THE AREAS.
 16) M2.112: THE KITCHEN HOOD EXHAUST AND FIRE
 SUPPRESSION SYSTEMS SHALL BE DONE UNDER A SEPARATE
 PERMIT- PLEASE PLACE A NOTE ON THE PLAN ACCORDINGLY AND
 PROVIDE AN AIR BALANCE CALCULATION FOR THE AREA. PLEASE
 NOTE ALL OTHER KITCHEN HOOD EXHAUST AND FIRE
 SUPPRESSION SYSTEMS THROUGHOUT THE FACILITY WILL ALSO
 BE DONE UNDER SEPARATE PERMIT WITH AIR BALANCE CALCS
 REQUIRED FOR EACH.
 17) M2.112: I AM NOT SEEING ANY OUTSIDE AIR
 CALCULATIONS IN THE SCHEDULES FOR THE CORRIDOR
 SERVICING THIS SECTOR OR CALCULATIONS FOR ANY OF THE
 OTHER SECTOR CORRIDORS- REFER TO TABLE 403.3 AND
 PROVIDE THE CALCULATIONS. IT ALSO NEEDS TO BE VERIFIED
 THAT THE CORRIDORS IN ALL SECTORS ARE NOT SERVING AS
 SUPPLY, RETURN, EXHAUST, RELIEF, OR VENTILATION AIR
 DUCTS PER SECTION 601.2. AS NOTED IN SECTION 601.2.1,
 THE CEILINGS ABOVE THE CORRIDORS MAY SERVE AS RETURN
 AIR PLENUMS.
 18) M2.113: EXPAND NUMBERED NOTE #11 TO INDICATE WHICH
 AC SYSTEM
 19) M2.113: PLACE A NUMBERED NOTE ON THE PLAN TO
 INDICATE WHERE THE HVAC SYSTEMS FOR THE HYDRO ROOM CAN
 BE FOUND.
 20) INDICATE THE REQUIRED CLEARANCE DISTANCE
 MEASUREMENTS FOR THE EXHAUST OUTLET FOR EF N-1-3. REFER
 TO COMMENT #12 ABOVE FOR MORE INFO.
 21) M2.113: REFER TO COMMENTS # 13 AND 15 FOR THE
 LAUNDRY AND KITCHEN AREAS ON THIS PLAN SHEET.
 22) M2.114: PROVIDE AN EXHAUST SYSTEM AND CALCULATIONS
 FOR THE STAFF/COACHES LOCKER ROOM- SEE TABLE 403.3.
 23) M2.115 & M2.412: THE 8" ROUND UNDERGROUND EXHAUST
 DUCT FROM THE DUGOUT SHALL BE CONSTRUCTED OF PVC HAVING
 A MINIMUM PIPE STIFFNESS OF 8 PSI AT 5-PERCENT
 DEFLECTION WHEN TESTED IN ACCORDANCE WITH ASTM D2412.
 PROVIDE A SUBMITTAL FOR THE DUCT REVIEWED AND APPROVED
 BY THE DESIGN PROFESSIONAL OF RECORD.
 24) M2.115: PROVIDE A NUMBERED KEY NOTE IDENTIFYING
 WHICH AC SYSTEM THE 24X14 SUPPLY AND 26X20 RETURN DUCT
 DROPS ARE CONNECTED TO.
  
 25) SHEETS M2.117, 118, & 119- CLUBHOUSE SECTORS H, J,
 & K: MANY OF THE COMMENTS PRINTED ABOVE FOR SHEETS
 M2.111, 112, 113, 114, & 115 (NATIONAL'S CLUBHOUSE) CAN
 APPLIED TO THESE PLAN SHEETS AND SECTORS FOR THE ASTROS
 CLUBHOUSE INCLUDING: A) REQUIRED EXHAUST SYSTEM AND
 CALCULATIONS FOR THE MLB COACHES LOCKER ROOM (M2.117).
 B) LAUNDRY AND KITCHEN AREAS. C) AC SYSTEM
 IDENTIFICATIONS AT DUCT DROPS. D) EXHAUST OUTLET AND
 AIR INLET CLEARANCE DISTANCES. E) NOA?S AND PRODUCT
 APPROVALS. F) OUTSIDE AIR FOR CORRIDORS.
 26) M2.120: EXPAND GENERAL NOTE A TO INDICATE THE GAGE
 OF ALUMINUM DUCTWORK.
 27) M2.120, 121, 122, 123, 127, 128, 129, 132, 134,
 135, 136, 137, 138, 139, 145: WIND LOAD ENGINEERING IS
 REQUIRED FOR THE ROOF-MOUNTED ERU'S, AHU'S, ACC'S CU'S,
 EF'S, MUA'S, DUH'S, GIH'S, AND ALL OTHER ROOF MOUNTED
 EQUIPMENT, COMPONENTS, AND DUCTWORK- SECTION 301.15
 PROVIDE STRUCTURAL DETAILS ACCORDINGLY INCLUDING
 SECTION CUTS INDICATING CURB HEIGHTS ABOVE THE ROOF
 SURFACES, CURB TO STRUCTURE AND UNIT TO CURB
 ATTACHMENTS, STAND TO STRUCTURE AND UNIT TO STAND
 ATTACHMENTS ETC. IF THE DETAILS ARE FOUND ON
 ARCHITECTURAL OR STRUCTURAL SHEETS PLEASE PLACE NOTES
 ON THE PLAN INDICATING THE SHEET AND DETAIL NUMBERS.
 28) M2.125: A) PROVIDE EXHAUST OUTLET CLEARANCE
 DISTANCES FOR EF-S-2-5 AND PROTECTION FOR THE OPENING.
 B) IDENTIFY WITH A NUMBERED NOTE WHICH AC SYSTEM IS
 PROVIDING THE O/A DROP. C) SEPARATE PERMITS REQUIRED
 FOR THE KITCHEN HOOD GREASE EXHAUST AND FIRE
 SUPPRESSION SYSTEMS D) IDENTIFY WITH A NOTE WHICH AC
 SYSTEM IS PROVIDING THE 28X20 SA AND RA DROPS. E)
 NUMBERED NOTE #5 INDICATES CONDENSATE FROM AC S-2-1 &
 S-2-4 DISCHARGING INTO A PLUMBING DRAIN- PLEASE NOTE
 THAT THIS CONDENSATE AND ALL OTHER CONDENSATE FROM AC
 COOLING COILS IS PROHIBITED TO DRAIN INTO THE WPB
 SANITY SEWER SYSTEM PER SEC. 90-126 WPB CODE OF
 ORDINANCES.
 29) M2.126: IDENTIFY WITH A NOTE WHICH AC SYSTEM IS
 PROVIDING THE 20X12 AND 18X12 SA AND RA DROPS.
 30) M2.129: I AM NOT SEEING MAU S-3-6 IN THE EQUIPMENT
 SCHEDULES- PLEASE INDICATE WHERE IT IS LOCATED. PLEASE
 NOTE THAT THE VENTILATION CALCULATION AND EQUIPMENT
 SCHEDULES DO NOT LIST THIS UNIT. MAU-N-2-6 & MAU-N-2-7
 ARE LISTED IN THE VENTILATION SCHEDULES HOWEVER I CAN?T
 FIND THEM ON THE PLANS ON IN THE EQUIPMENT SCHEDULES-
 PLEASE CLARIFY AND INDICATE HOW THESE SYSTEMS WERE
 SIZED.
 31) M2.132, 134, 135 & M0.07: THE VENTILATION
 CALCULATIONS ARE INCORRECT FOR THE SUITES AND OTHER
 SPECTATOR AREAS ON THE SUITE LEVEL. REFER TO TABLE
 403.3 FBC-14 MECHANICAL: SPECTATOR AREAS ARE CALCULATED
 AT 150 PEOPLE PER 1000 SQ.FT. AND REQUIRE 7.5 CFM PER
 PERSON- PLEASE CORRECT. A) PROVIDE ACCESS PANEL SYMBOLS
 FOR THE FCU?S AND DIMENSIONED DETAILS FOR INSTALLATION
 OF THE PANELS.
 32) M4.01, 402: EXPAND NOTE #3 TO INDICATE WHICH AC
 SYSTEM IS PROVIDING THE SA AND RA DROPS TO THE AREAS.
 33) M4.02: PROVIDE AN EQUIPMENT SCHEDULE FOR THE SF
 N-1-4, AND DETAILS FOR WIND LOAD ENGINEERING FOR
 ANCHORING THE FAN AND DUCTWORK- SECTION 301.15.
 34) M4.02 & 403.: THE REFRIGERANT PIPING DIAGRAMS ARE
 INCOMPLETE: PROVIDE DIAGRAMS FOR ALL SYSTEMS AND
 INCLUDE PIPE AND PIPE INSULATION SPECIFICATIONS, AND
 FIRESTOPPING DETAILS FOR ALL PIPES PENETRATING
 FIRE-RATED WALLS OR FLOOR/CEILING ASSEMBLIES
 34) M.602 & 603: PROVIDE SUPPORT AND HANGING DETAILS
 FOR INSTALLATION OF THE FCU?S, THE VAV AND CAV BOXES,
 THE INLINE FANS, THE G90 AND ALUMINUM DUCTWORK, AND THE
 FLEX DUCTS. INCLUDE CONNECTION AND REINFORCEMENT
 DETAILS FOR ALL DUCTWORK, AND TYPES AND SIZES OF
 HANGERS AND FASTENERS- REFER TO TABLE C403.2.7.2 FBC-14
 ENERGY CONSERVATION AND SMACNA HVAC DUCT CONSTRUCTION
 STANDARDS-2005.
  
 35) REFER TO SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION: PROVIDE SHUTOFF DAMPER CONTROLS FOR
 OUTDOOR AIR SUPPLY AND EXHAUST DUCTS WHERE REQUIRED.
 36) REFER TO SECTION C408: COMMISSIONING OF THE
 MECHANICAL AND ELECTRICAL POWER AND LIGHTING SYSTEMS IS
 REQUIRED. PLEASE REVIEW ALL SUB-SECTIONS UNDER C408 AND
 SUBMIT A COMMISSIONING PLAN FOR REVIEW.
 37) PROVIDE A SUBMITTAL PACKAGE FOR ALL MECHANICAL
 EQUIPMENT AND COMPONENTS INCLUDING BUT NOT LIMITED TO
 THE AC SYSTEMS, EXHAUST AND SUPPLY FANS, ROOF TOP CURBS
 AND STANDS, EXHAUST OUTLET AND AIR INLET LOUVERS, DUCT
 SMOKE DETECTORS, FIRE DAMPERS, THE DRYERS, ETC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  