Plan Review Notes
Plan Review Notes For Permit 16020418
Permit Number 16020418
Review Stop G
Sequence Number 1
Notes
Date Text
2016-04-27 15:02:261) THE RESPONSE FROM WSP FOR COMMENT #32 DOES NOT
 SATISFY THE COMMENT. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION SIZE AND TERMINATION OF ALL GAS VENTS FROM
 EQUIPMENT AND APPLIANCES THAT ARE REQUIRED TO BE VENTED
 TO THE EXTERIOR.2014 FGC SECS.502 THRU 505. THE REVIEW
 COMMENT WAS NOT SPECIFIC AS TO THE TYPE OF VENT
 INFORMATION THAT WAS BEING REQUESTED.
 2) SUBMIT A GAS EQUIPMENT SCHEDULE LISTING EACH GAS
 APPLIANCE/ PIECE OF EQUIPMENT, THE BTU VALUE, THE TAG /
 ITEM NUMBER AND THE PIPE SIZE FOR THE APPLIANCE
 /EQUIPMENT. I HAVE ALREADY REVIEWED THE K DRAWINGS.
 3) SHT. P5.401 & P5.401.3 - THE RISER SHOWS THE TOTAL
 BTU LOAD ON THE MAIN AND AT THE METER AS 9258 MBH.
 AFTER THE TWO GWH-2 WATER HEATERS THE LOAD IS REDUCED
 TO 5358 MBH. PLEASE CLARIFY AS TO HOW 9258 MBH MINUS
 1980 MBH EQUALS 5358 MBH. MY CALCULATION COMES TO 7278
 MBH .THIS LINE IS UNDERSIZED AND NEEDS TO BE 4 INCHES
 IN SIZE. THE ENTIRE LINE SHALL BE CHECKED FOR PROPER
 SIZING IN ACCORDANCE WITH 2014 FGC TABLE 402.4 (5).
 CLARIFY.
 4) A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MEDIUM PRESSURE REGULATOR.
 2014 FGC SEC.409.4.
 5) SHT. P5.401 & P5.401.1 - THE 1 1/4 INCH LINE TO
 APPLIANCES #1047 & #1048 IS UNDERSIZED. THE MAXIMUM BTU
 LOAD ON A 1 INCH PIPE AT 30 FT. DEVELOPED LENGTH IS 583
 MBH PER FGC TABLE 402.4 (1).
 6) SHT. P5.401.1 - SIZE THE GAS LINE TO GWH-3 AND SHOW
 THE BTU LOAD ON THE RISER.
 7) SHT. P5.401.2 - SIZE THE PIPE TO GWH-3 DOWNSTREAM OF
 THE MP REGULATOR. THE LINE SHALL BE A MINIMUM OF 1 INCH
 PER FGC TABLE 402.4 (1).THE MEDIUM PRESSURE SIDE SHALL
 ALSO BE 1 INCH PER TABLE 403.4 (5).
 8) SHT. P5.402.1 - THE 3/4 INCH LINE TO ITEM #243 IS
 UNDERSIZED.THE MAXIMUM MBH ON A 3/4 INCH LINE AT 20 FT.
 IS 188 MBH. THE 1 INCH LINE CARRYING 440 MBH IS
 UNDERSIZED. THE MAXIMUM BTU LOAD ON A 1 INCH LINE AT 20
 FT. IS 353 MBH PER TABLE 402.4 (1) OF FGC.
 9) SHT. P5.402.1 - SIZE THE LINES TO UNITS MUA-A-2-2
 AND ERU-A-3-1 DOWNSTREAM OF THE MP REGULATOR. THE SIZE
 OF THE LINE TO ERU-A-3-1 SHALL BE A MINIMUM OF 1 INCH.
 FGC TABLE 402.4 (1).
 10) SIZE ALL SECTIONS OF PIPING DOWNSTREAM OF ALL MP
 REGULATORS.
 11) SHT. P5.402.1- THE LOW PRESSURE LINE SUPPLYING 440
 MBH TO ITEMS # 243, 246 & 247 IS UNDERSIZED. THE
 MINIMUM SIZE PIPE SHALL BE 1 1/4 INCHES. FGC TABLE
 402.4 (1).
 12) SHT. P5.402.1 - THE 3/4 INCH LOW PRESSURE LINE TO
 ITEM # 243 IS UNDERSIZED. THE MINIMUM SIZE SHALL BE 1
 INCH PER FGC TABLE 402.4.(1).
 13) SHT. P5.402.2 - SIZE THE LOW PRESSURE LINE
 DOWNSTREAM OF THE MP REGULATOR TO UNIT MUA-A-2-1.
 14) SHT. P5.402.2 - THE RISER SHOWS A 3/4 INCH LOW
 PRESSURE LINE TO ITEM #L2 CARRYING 350 MBH. THE MAXIMUM
 MBH ON A 3/4 INCH LINE AT 20 FT. IS 188 MBH. THE
 MINIMUM SIZE OF THIS LINE SHALL BE 1 INCH PER FGC TABLE
 402.4 (1).
 15) SHT. P5.402.2 - THE RISER SHOWS A 3/4 INCH LINE TO
 ITEM # L2 WITH A BTU LOAD OF 350 MBH AND ALSO A 1 INCH
 LINE SUPPLYING TWO ITEMS WITH THE SAME MBH LOAD OF 350.
 CLARIFY AND SHOW THE CORRECT PIPE SIZE.
 16) SHT. P5.402.2 - SIZE THE LOW PRESSURE LINE
 DOWNSTREAM OF THE PRESSURE REGULATOR AT GWH-1 AND TO
 EACH HEATER AND SHOW THE MBH LOAD FOR BOTH HEATERS.
 COMPLY WITH FGC TABLE 402.4 (1).
 17) SHT. P-5.402.2 - SIZE THE LOW PRESSURE LINES
 DOWNSTREAM OF THE MP REGULATOR TO EQUIPMENT ITEMS
 ERU-A-2-5 AND ERU-A-2-6.
 18) SHT. P5.403.1 - SIZE THE LOW PRESSURE LINE TO THE
 FUTURE POOL HEATER DOWNSTREAM OF THE MP REGULATOR. THE
 LINE SHALL BE A MINIMUM OF 1 1/4 INCHES PER 2014 FGC
 TABLE 402.4 (1).
 19) SHT. P5.403.1 - SIZE THE LOW PRESSURE LINE TO UNIT
 ERU-N-2-5 DOWNSTREAM OF THE MP REGULATOR. THE MINIMUM
 SIZE SHALL BE 1 INCH. SHOW THE BTU LOAD AND SIZE THE
 LINE UPSTREAM OF THE MP REGULATOR.
 20.) SHT. P5.403.1 - SIZE THE LOW PRESSURE LINE TO
 ITEMS # 146 & #148. THE MINIMUM SIZE SHALL BE 1 INCH.
 TABLE 402.4 (1) FGC.
 21) SHT. P5403.1 - THE 3/4 INCH MEDIUM PRESSURE LINE TO
 ITEMS #146 AND 148 IS UNDERSIZED. THE MINIMUM SIZE
 SHALL BE 1 INCH. TABLE 402.4 (5) FGC.
 22) SHT.P5.403.1 - THERE IS 1 INCH LOW PRESSURE LINE
 SERVING OUTLETS ADJACENT TO ITEMS # 146 AND # 148 WITH
 350 MBH. THIS LINE IS UNDERSIZED AND SHALL BE 1 1/4
 INCHES. ALSO, IDENTIFY THE APPLIANCES ON THESE OUTLETS.
 FGC TABLE 402.4 (1). THERE IS ALSO A 3/4 INCH LOW
 PRESSURE LINE CARRYING 175 MBH. THIS LINE IS
 UNDERSIZED. THE MINIMUM SIZE SHALL BE 1 INCH.
 23) SHT. P5.403.1 - SIZE THE LOW PRESSURE LINE TO
 DHU-N-2-1. THE MINIMUM SIZE OF THIS LINE SHALL BE 1
 INCH. FGC TABLE 402.4 (1).
 24) SHT. P5.403.2 - THE 1 1/4 INCH LOW PRESSURE LINE TO
 THE FOUR L2 ITEMS IS UNDERSIZED. THE MINIMUM SIZE SHALL
 BE 1 1/2 INCHES. A MAXIMUM OF 583 MBH IS ALLOWED ON A 1
 1/4 INCH LINE, 284 MBH ON A 1 INCH LINE, AND 151MBH ON
 A 3/4 INCH LINE. THESE LINES ARE ALSO UNDERSIZED. THE
 RISER SHOWS 700 MBH ON THIS LINE. ALSO, SHOW THE SIZE
 OF THE DROPS TO THE EQUIPMENT AND THE BTU LOAD OF AT
 EACH OUTLET. SIZE ALL SECTIONS OF THE SYSTEM AT THIS
 AREA. FGC TABLE 402.4 (1).
 25) SHT. P5.403.2 - THE 1 INCH AND 3/4 INCH LOW
 PRESSURE LINES TO ITEMS #37 AND #38 ARE UNDERSIZED. THE
 MAXIMUM MBH LOAD ON A 3/4 INCH LINE AT 30 FT. IS 151
 MBH AND 284 MBH ON A 1 INCH LINE. THESE LINES SHALL BE
 INCREASED TO 1 INCH AND 1 1/4 INCHES. FGC TABLE 402.4
 (1).
 26) SHT.P5.403.2 - THE 2 1/2 INCH LOW PRESSURE LINE TO
 THE TWO GWH-1 WATER HEATERS IS UNDERSIZED. THE MAXIMUM
 MBH ON A 2 1/2 INCH LINE AT 30 FT. IS 2680 MBH. THE
 LINE NEEDS TO BE 3 INCH. TABLE 402.4 (1).
 27) SHT. K2.111.1 - ITEM #38 IS SHOWN WITH A 3/4 INCH
 GAS SIZE BUT THE SCHEDULE ON SHT. P5.403 SHOWS THE GAS
 SIZE AS 1 1/4 INCH. CLARIFY.
 28) SHT. K2.112.1 - THE UTILITY SCHEDULE SHOWS ITEM
 3146 WITH A 3/4 INCH GAS SIZE BUT SHT. P5.403 SHOWS AN
 1 1/4 GAS SIZE. CLARIFY.
 29) SHT. K2.113.1 - THE UTILITY SCHEDULE SHOWS ITEM #
 246 WITH A 3/4 INCH GAS SIZE BUT SHT. P5.402 SCHEDULE
 SHOWS 1 1/4 INCHES.CLARIFY.
 30) SHT.K2.114.1 - THE UTILITY SCHEDULE SHOWS ITEM #
 354 WITH A 3/4 INCH GAS SIZE BUT SHT. P5.402 SCHEDULE
 SHOWS 1 1/4 INCHES. CLARIFY.
 31) IDENTIFY THE L 2 APPLIANCE. I COULD NOT FIND THIS
 ON THE UTILITY SCHEDULE.
 32) ENSURE THE GAS PIPE SIZES ON THE UTILITY SCHEDULES
 CORRELATE WITH THE SCHEDULES ON THE GAS PLANS.2014 FBC
 107.2.1.
 33) THERE ARE STILL NUMEROUS AREAS ON THE GAS RISERS
 WHERE PIPE SIZES ARE NOT SHOWN AND EQUIPMENT NOT
 LABELED.ENSURE ALL SECTIONS ARE CLEARLY SIZED AND
 OUTLETS LABELED AS TO THE EQUIPMENT BEING SERVED. 2014
 FBC 107.2.1.
 34) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 LOUVERS BEING USED TO PROVIDE THE COMBUSTION AIR FOR
 THE DRYERS AND SHOW THE LOCATIONS OF THE LOUVERS ON THE
 ARCHITECTURAL AND PLUMBING PLANS. LOUVERS SHALL COMPLY
 WITH THE 2014 FBC SEC.1609.1.2.1. SUBMIT PRODUCT
 APPROVALS FOR THE LOUVERS SHOWING COMPLIANCE FOR WIND
 LOAD REQUIREMENTS.
 35) WHERE ARE COMBUSTION AIR CALCULATIONS FOR THE REST
 OF THE APPLIANCES SUCH AS THE COOKING EQUIPMENT IN THE
 CONCESSION AREAS AND OTHER AREAS WHERE GAS FUELED
 EQUIPMENT IS LOCATED IN ROOMS, AREAS OR OTHER TYPE OF
 ENCLOSURES? 2014 FGC SEC.304.1, 304.5.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR