Plan Review Notes
Plan Review Notes For Permit 16020418
Permit Number 16020418
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-02-24 16:00:495444 NORTH HAVERHILL ROAD
 PERMIT #16020418
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 SHEET LS1.02: A FIRE IN CORRIDOR #11237 HAS THE
 POTENTIAL TO BLOCK BOTH EXITS FROM COACH'S LOCKER
 #11415. PER SECTION 7.5.1.3.1 WHERE MORE THAN ONE EXIT,
 EXIT ACCESS, OR EXIT DISCHARGE IS REQUIRED FROM A
 BUILDING OR PORTION THEREOF, SUCH EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE ARRANGED TO MINIMIZE THE POSSIBILITY THAT
 MORE THAN
 ONE HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR
 OTHER EMERGENCY CONDITION.
  
 SHEET A2.227: 1ST FLOOR LOBBY #11711 IS OPEN TO THE
 SECOND FLOOR RECEPTION #12704. PER SECTION 8.6.9.2
 UNENCLOSED VERTICAL OPENINGS CREATED BY CONVENIENCE
 STAIRWAYS SHALL BE PERMITTED AS FOLLOWS: 1) THE
 CONVENIENCE STAIR OPENING SHALL NOT SERVE AS A REQUIRED
 MEANS OF EGRESS 2) THE CONVENIENCE STAIR OPENING SHALL
 BE PROTECTED IN ACCORDANCE WITH THE METHOD DETAILED FOR
 THE PROTECTION OF VERTICAL OPENINGS IN NFPA 13,
 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
  
 SHEET A2.324 1ST FLOOR LOBBY #11408 IS OPEN TO THE
 SECOND FLOOR CORRIDOR #12412B. PER SECTION 8.6.9.2
 UNENCLOSED VERTICAL OPENINGS CREATED BY CONVENIENCE
 STAIRWAYS SHALL BE PERMITTED AS FOLLOWS: 1) THE
 CONVENIENCE STAIR OPENING SHALL NOT SERVE AS A REQUIRED
 MEANS OF EGRESS 2) THE CONVENIENCE STAIR OPENING SHALL
 BE PROTECTED IN ACCORDANCE WITH THE METHOD DETAILED FOR
 THE PROTECTION OF VERTICAL OPENINGS IN NFPA 13,
 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
  
 ALL OF THE E2 AND E3 SERIES ELECTRICAL DRAWINGS ARE
 CORRUPT FILES OR THE PLANS HAVE NOT BEEN COMPLETED.
  
 SHEET E5-04 FIRE ALARM RISER: FILE IS CORRUPT OR PLAN
 HAS NOT BEEN COMPLETED.
  
 ALL OF THE FA2 SERIES FIRE ALARM DRAWINGS ARE CORRUPT
 FILES OR THE PLANS HAVE NOT BEEN COMPLETED.
  
 SIGNAGE: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 SIGNAGE: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  