2016-04-22 11:08:07PLANS ARE FILED UNDER 16020418
  
 2ND ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011
 EDITION
  
 WITH THE EXCEPTION OF THE MISSING ILLUMINATION ISSUES,
 THE BELOW MENTIONED ITEMS CAN BE EASILY ADDRESSED WITH
 THE PROPER NOTES. THEREFORE A NARRATIVE ADDRESSING THE
 ISSUES CAN BE ACCEPTED AND PLANS ISSUED WITH A PROVISO
 RELATING THERETO.
  
 AS USUAL, IF DURING THE PLAN REVIEW I MISUNDERSTOOD A
 SHEET?S INTENTION AND THE COMMENTS ISSUED ARE
 NON-APPLICABLE PLEASE CORRECT ME AND EXPLAIN.
  
 CORRECTIONS REQUIRED:
 SHEET E1.00-2, E2.111, E3.127, UPLOAD CORRUPTED,
 SHEET E2.110
 1. PER NEC 680.62 HYDRO TUB OUTLETS SHALL BE GFI
 PROTECTED.
 2. NEC 210.8(B)(7) LOCKER ROOM OUTLETS WITH AN
 ASSOCIATED SHOWER FACILITY SHALL BE GFCI PROTECTED.
 SHEET E2.119, E2.112, E2.113, E2.114, E2.117,
 1. NEC 210.8(B)(7) LOCKER ROOM OUTLETS WITH AN
 ASSOCIATED SHOWER FACILITY SHALL BE GFCI PROTECTED.
 SHEET E2.127
 1. NEC 210.63 REQUIRES A GFCI PROTECTED OUTLET WITH 25?
 OF EQUIPMENT. AD.0-AE.0/A04.5-A05
 SHEET E2.129
 1. EXPLAIN 208/1PH
 2. NEC 210.63 REQUIRES A GFCI PROTECTED OUTLET WITH 25?
 OF EQUIPMENT. OUTLET SHOWN ON PLANS IS OUTSIDE THE
 ROOM. A08.3-A08.9/AD
 3. SAME APPLIES FOR ADJACENT AREA. AD-AB.5/A07.5-A08
 SHEET E2.134, E2.132,
 1. TYPICAL PADDLE FAN NOTE ADDED TO PLANS.
 SHEET E2.411, E2.128, E2.126, E2.125, E2.122,
 1. EXPLAIN 208/1 PH
 2. PANEL SCHEDULE ON SHEET E5.01 DOES NOT INDICATE ANY
 LOADS ON CKTS 76,9 OF LP-NB-1
 SHEET E2.413, E2.412,
 1. MISSING THE WEATHER-RESISTANT NOTE ADDED TO ALL
 OTHER SHEETS.
 SHEET E3.112, E3.113, E3.114, E3.115, E3.117, E3.118,
 E3.119, E3.124, E30125, E3.126, E3.128, E3.134,
 1. ADDITIONAL EMERGENCY LIGHTING REQUIRED IN ROOMS,
 1240, 1235, (SHOWER AND TOILET AREAS OF 1204, 1207),
 1211, 1214, 1301, 1310, 1313, 1406, 1413, 1414, 1417,
 1419, 1506, 1508, 1512, 1713, 1706, 1708, 1707, 1801,
 1831, 1832, 1820, 1901, 1916, 1909, 2428, 2517, 2603,
 2607, 2608, 2605, 2616, AREA OF SO5-SO6/SC.5-SB.6,
 2811, 2509,
 2. LIGHTING CONTROL MISSING IN ROOMS 1205, 1206, 1208,
 1321, 1322, 1429, 1417, 1419, 1710, AREA OF
 SO5-SO6/SC.5-SB.6, 2811, JAN CLOSET BETWEEN 3410 &
 3413, 3407, NO3-NO3.5/NC-ND,
 3. ILLUMINATION AND CONTROL MISSING IN ROOM 1806, 1907,
 1908, 2504, 2508, 2509, CORRIDOR SH-SF/S13.25-S13.5,
 3421,
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER