| 2016-03-02 13:24:35 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 NEC |
| | COMMENTS: |
| | |
| | 1.PLEASE SHOW SIZE OF THE SERVICE CONDUCTORS. FBC RES- |
| | E3603.1 |
| | 2.SHOW A INTERSYSTEM BONDING TERMINATION PER FBC RES- |
| | E3609.3 |
| | 3.PROVIDE GFCI PROTECTION FOR RECEPTACLES WITHIN 6FT OF |
| | SINK IN LAUNDRY AREA. FBC RES- E3902.7 |
| | 4.PROVIDE GFCI PROTECTION FOR RECEPTACLES IN BATHROOM |
| | AREA. FBC RES- E3902.1 |
| | 5.SHOW AN EQUIPMENT GROUNDING CONDUCTOR WITH THE FEEDER |
| | CONDUCTORS SERVING THE SUBPANEL LOADS. FBC RES- |
| | E3607.3.1 |
| | 6.PROVIDE GENERAL NOTES INDICATING AFCI FOR BRANCH |
| | CIRCUITS. FBC RES- E3902.12 |
| | 7.PROVIDE GENERAL NOTES INDICATING TAMPER RESISTANT |
| | RECEPTACLES REQUIRED PER FBC RES- E4002.14 |
| | 8.SUMP PUMP SHOWN TO HAVE GFCI PROTECTION. FBC RES |
| | E3902.3 |
| | 9.SHOW LAUNDRY OUTLET ON PANEL SCHEDULE AT 20AMP |
| | MINIMUM PER E3703.3 |
| | 10.SHOW BATHROOM OUTLET ON PANEL SCHEDULE AT 20AMP |
| | MINIMUM PER E3703.4 |
| | 11.PANEL SCHEDULES BRANCH CIRCUIT MUST ID EXACTLY WHAT |
| | AREA IS BEING PROTECTED, GEN LIGHTING ID NOT |
| | SUFFICIENT. SEE FBC RES E3706.2 |
| | 12.CORRECT TYPO ON SUB-PANEL SCHEDULE TO INDICATE 15AMP |
| | OVERCURRENT BREAKER NOT 14AMP AS SHOWN. FBC 107.3.5 |
| | 13.ZONING COMMENTS PENDING REGARDING USE OF STUCTURE AS |
| | SHOWN. |
| | 14.FEEL FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD |
| | YOU HAVE ANY QUESTIONS OR CONCERNS. |
| | |