Plan Review Notes
Plan Review Notes For Permit 16020406
Permit Number 16020406
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-02 13:24:35INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE SHOW SIZE OF THE SERVICE CONDUCTORS. FBC RES-
 E3603.1
 2.SHOW A INTERSYSTEM BONDING TERMINATION PER FBC RES-
 E3609.3
 3.PROVIDE GFCI PROTECTION FOR RECEPTACLES WITHIN 6FT OF
 SINK IN LAUNDRY AREA. FBC RES- E3902.7
 4.PROVIDE GFCI PROTECTION FOR RECEPTACLES IN BATHROOM
 AREA. FBC RES- E3902.1
 5.SHOW AN EQUIPMENT GROUNDING CONDUCTOR WITH THE FEEDER
 CONDUCTORS SERVING THE SUBPANEL LOADS. FBC RES-
 E3607.3.1
 6.PROVIDE GENERAL NOTES INDICATING AFCI FOR BRANCH
 CIRCUITS. FBC RES- E3902.12
 7.PROVIDE GENERAL NOTES INDICATING TAMPER RESISTANT
 RECEPTACLES REQUIRED PER FBC RES- E4002.14
 8.SUMP PUMP SHOWN TO HAVE GFCI PROTECTION. FBC RES
 E3902.3
 9.SHOW LAUNDRY OUTLET ON PANEL SCHEDULE AT 20AMP
 MINIMUM PER E3703.3
 10.SHOW BATHROOM OUTLET ON PANEL SCHEDULE AT 20AMP
 MINIMUM PER E3703.4
 11.PANEL SCHEDULES BRANCH CIRCUIT MUST ID EXACTLY WHAT
 AREA IS BEING PROTECTED, GEN LIGHTING ID NOT
 SUFFICIENT. SEE FBC RES E3706.2
 12.CORRECT TYPO ON SUB-PANEL SCHEDULE TO INDICATE 15AMP
 OVERCURRENT BREAKER NOT 14AMP AS SHOWN. FBC 107.3.5
 13.ZONING COMMENTS PENDING REGARDING USE OF STUCTURE AS
 SHOWN.
 14.FEEL FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  