| Date |
Text |
| 2016-09-20 14:18:12 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16020377 |
| | ADD: 7130 OKEECHOBEE BLVD. / LEASING & RECREATION BLDG. |
| | CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER |
| | TEL: 561-891-0414 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 5TH REVIEW |
| | DATE: TUES. SEPT. 20/2016 |
| | ACTION: DENIED |
| | |
| | NOTE: THIS REVIEW IS FOR THE LEASING/ RECREATION BLDG |
| | ONLYI, NOT FOR THE SITE PLAN, OR ANY ASSOCIATED |
| | AMENITIES. |
| | |
| | 1) THE BUILDING OFFICIAL HAS APPROVED THE COST ANALYSIS |
| | AND REVIEWING THE DOCUMENTS. THE 4 SUB-PERMITS THAT ARE |
| | A NO COST IF THEY CAME IN AT THE TIME OF THE PRIME |
| | PERMIT ARE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING. |
| | IF THEY COME IN AFTER THE PRIME PERMIT WAS CREATED THEY |
| | ARE A $80.00 SUB-PERMIT, THE $80.00 IS AN |
| | ADMINISTRATIVE FEE. |
| | THE VALUE OF THE SUB-PERMITS WHERE THE VALUE OF THE |
| | PERMIT IS NOT COVERED UNDER THE PRIME PERMIT NEED TO BE |
| | DEDUCTED FROM THE $900,000.00 STATED. THESE PERMIT |
| | INCLUDE, FIRE SPRINKLERS, FIRE ALARMS, ALL LOW VOLTAGE |
| | PERMITS. THIS VALUE WILL NEED TO BE DECLARED SO WE CAN |
| | REDUCE THE OVERALL BUILDING VALUE SO WE DO NOT CHARGE |
| | YOU TWICE FOR ASSOCIATED PERMIT FEES. |
| | |
| | PLEASE NOTE ALL OTHER PERMITS NOT ASSOCIATED WITH THE |
| | BUILDING ARE CONSIDERED PROJECT COST AND WILL BE |
| | PERMITTED SEPARATELY. SITE CLEARING, DEMOLITION OF |
| | STRUCTURES, UNDERGROUND UNITIES, PAVING, SEAL COATING & |
| | STRIPING, SIDEWALKS, IRRIGATION, LANDSCAPE, POOLS, POOL |
| | DECK IF NOT INCLUDED IN THE POOL CONTRACT, FENCING, OUT |
| | BUILDINGS, SIGNAGE ETC. |
| | |
| | 2) COMPLIED. A PAPER SIGNED AND SEALED ORIGINAL SOILS |
| | REPORT ON FILE WITH CITY. |
| | |
| | |
| | 3) PROVISO: THERE ARE NO ELEVATIONS OF THE BREAK ROOM. |
| | THERE ARE CONCERNS IF THERE WILL BE A MICROWAVE AND THE |
| | PLACEMENT OF THE UNIT FOR COMPLIANCE WITH REACH RANGES |
| | AND OPERABLE PARTS UNDER BOTH THE FAIR HOUSING AND |
| | FLORIDA ACCESSIBILITY CODE. |
| | REACH RANGES UNDER 308. |
| | OPERABLE PARTS 309. |
| | |
| | 4) PROVISO: CONTRACTOR TO SUBMIT PRODUCT APPROVAL FOR |
| | ADHERED MASONRY VENEER PER FBC-B 1405.10 TO BE REVIEWED |
| | BY THE DESIGNER OF RECORD, SHOP DRAWING STAMP OF |
| | APPROVAL APPLIED BEFORE BEING SUBMITTED TO THE BUILDING |
| | DEPARTMENT. |
| | |
| | 5A) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 5B) PROVISO: COMPONENTS & CLADDING. 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 6A) PROVISO: BAHAMA SHUTTERS TO PROVIDE SHOP DRAWINGS, |
| | PLEASE NOTE I UNDERSTAND THE INTENT IS TO LEAVE THESE |
| | AWNINGS IN THE OPEN POSITION IN A HIGH WIND EVENT. |
| | 2014 FBC-B 3105.4 DESIGN. 2014 FBC-B 3105.5 RIGID |
| | AWNINGS AND CANOPY SHUTTERS. |
| | |
| | 6B) COMPLIED, N/A. 2014 FBC-B 3105.3.3.1 FABRIC USED |
| | FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL MEET THE |
| | FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 OR |
| | HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |