2016-06-07 08:37:12BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020377
 ADD: 7130 OKEECHOBEE BLVD. / LEASING & RECREATION BLDG.
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 4TH REVIEW
 DATE: TUES. JUNE 07/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS FOR THE LEASING/ RECREATION BLDG
 ONLYI, NOT FOR THE SITE PLAN, OR ANY ASSOCIATED
 AMENITIES.
  
 1)THE BUILDING OFFICIAL IS IN RECEIPT OF COST ANALYSIS
 AND REVIEWING THE DOCUMENTS.
 CONTRACTOR TO BRING IN A EVALUATION BY A CPA. THE
 PERMIT APPLICATION VALUE OF $900,000,00 DOLLARS IS
 ACTUALLY HIGH IN RELATION TO THE AUGUST 2015 ICC
 VALUATION TABLES. THE MEP AND ROOFING PERMITS, ARE
 SUB-PERMITS AND IF NOT SUBMITTED AT THE TIME OF PERMIT
 ARE A $80.00 SUB-PERMIT AND ARE INCLUDED IN THE VALUE
 OF THE BUILDING COST. ALL OTHER SUB-PERMITS ARE FEED
 PERMITS. PLEASE PROVIDE A LIST OF ALL OTHER SUB-PERMITS
 FOR THE BUILDING, SUBMIT A LIST OF PERMITS AND
 BREAK-OUT THE VALUE FROM THE TOTAL COST TO DETERMINE
 THE FINAL VALUATION OF THE BUILDING PERMIT.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 2) COMPLIED.
  
 2F) NOTICE ONLY, FOR PAPER PLANS 3 SETS OF DOCUMENTS
 ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
  
 2G) NOTICE ONLY, NO ACTION IS REQUIRED. PLEASE CALL THE
 CITY OF WEST PALM BEACHES AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 2H) NOTICE ONLY, NO ACTION IS REQUIRED. 109.3.6
 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3) COMPLIED/ ADDRESSING
  
 4) 4TH REQUEST.
 SUBMITTED IS A 195 PAGE DOCUMENT FOR PHASE I
 ENVIRONMENTAL SITE ASSESSMENT, NOT FOR MINIMUM BEARING
 VALUE, IT WOULD APPEAR A LAKE ONSITE WILL BE FILED IN
 AND THERE IS NO INFORMATION AS TO HOW THE FILE WILL BE
 COMPACTED, NO INFORMATION ON SOILS BORING TEST NOR THE
 DEVELOPMENT OF THE PADS FOR THE FOUNDATION. MISSING
 FROM THE SUPPORTING DOCUMENT FOLDER IS COMPLIANCE WITH:
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5) COMPLIED.
  
 6) SEMI-COMPLIED. SEE MECHANICAL COMMENTS.
  
 7A-C) COMPLIED.
  
 7D) PROVISO: THERE ARE NO ELEVATIONS OF THE BREAK ROOM.
 THERE ARE CONCERNS IF THERE WILL BE A MICROWAVE AND THE
 PLACEMENT OF THE UNIT FOR COMPLIANCE WITH REACH RANGES
 AND OPERABLE PARTS UNDER BOTH THE FAIR HOUSING AND
 FLORIDA ACCESSIBILITY CODE.
 REACH RANGES UNDER 308.
 OPERABLE PARTS 309.
  
 8A) PROVISO: THE DESIGNER INDICATES 45 MIN. WINDOW,
 DOORS AND FRAMES. THE CONTRACTOR IN RESPONSE INDICATES
 THESE OPENINGS WILL HAVE PRODUCT TESTING FOR BOTH FIRE
 RESISTANCE RATING AND LARGE MISSILE IMPACT RESISTANCE
 TESTING. IF THE UNIT COST ARE TOO HIGH FOR THESE TYPE
 OF UNITS THEN FIRE RATED WINDOWS AND STORM SHUTTERS AND
 OR PANELS WILL BE REQUIRED. IF STORM PANELS ARE TO BE
 INSTALLED, THEN STORAGE WITHIN THE RECREATION CENTER
 WILL BE A REQUIREMENT.
  
 SHEET A3.01R THE RIGHT SIDE OR ELEVATION SHOWS THE
 WINDOWS AND DOORS AS PROTECTED, WINDOWS A 1 HOUR FIRE
 RATING AND THE DOORS 45 MINUTES. THE 2014 FBC-B TABLE
 716.5 FOR EXTERIOR WALLS THAT REQUIRE A 1 HOUR FIRE
 RATING THE OPENING PROTECTIVE WILL ONLY REQUIRE 45
 MINUTE PROTECTIVE. PLEASE INDICATE ON THE WINDOWS HOW
 THIS WILL BE ACCOMPLISHED, FIRE SHUTTERS, FIRE RATED
 GLAZING AND FRAME? ? PLEASE ALSO BE AWARE THAT THERE
 ARE VERY FEW WINDOWS THAT ARE TESTED FOR A FIRE RATING
 AS WELL AS LARGE MISSILE IMPACT TESTING.
  
 8B) PROVISO: CONTRACTOR TO SUBMIT PRODUCT APPROVAL FOR
 ADHERED MASONRY VENEER PER FBC-B 1405.10 TO BE REVIEWED
 BY THE DESIGNER OF RECORD, SHOP DRAWING STAMP OF
 APPROVAL APPLIED BEFORE BEING SUBMITTED TO THE BUILDING
 DEPARTMENT.
  
 9) COMPLIED.
 .
 10A) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 10B) PROVISO: COMPONENTS & CLADDING. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 10C) PROVISO: 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10D) PROVISO: FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIXE.
  
 10E) PROVISO: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO
 RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA
 ARCHITECT OR ENGINEER.
  
 10F) COMPLIED. SHEET A8.03 DETAIL # 1 AC/ COMPRESSORS
 BEING TIED DOWN TO CONCRETE PADS
  
 11A) PROVISO: BAHAMA SHUTTERS TO PROVIDE SHOP DRAWINGS,
 PLEASE NOTE I UNDERSTAND THE INTENT IS TO LEAVE THESE
 AWNINGS IN THE OPEN POSITION IN A HIGH WIND EVENT.
 2014 FBC-B 3105.4 DESIGN. 2014 FBC-B 3105.5 RIGID
 AWNINGS AND CANOPY SHUTTERS.
  
 11B) COMPLIED, N/A. 2014 FBC-B 3105.3.3.1 FABRIC USED
 FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL MEET THE
 FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 OR
 HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 12) COMPLIED.
  
 13) 4TH REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) BEFORE PERMIT ISSUANCE CAN OCCUR ONE SET OF SIGNED
 AND SEALED DOCUMENTS (PLANS, SOILS REPORTS, & ENERGY
 CALCULATIONS) WILL BE SUBMITTED TO THE BUILDING
 DEPARTMENT FOR THE RECORD RETENTION PROGRAM AND
 REVIEWED WITH THE ELECTRONIC PLANS FOR ACCURACY AND
 CODE COMPLIANCE.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER