| 2016-05-13 13:53:41 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16020377 |
| | ADD: 7130 OKEECHOBEE BLVD. / LEASING & RECREATION BLDG. |
| | CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER |
| | TEL: 561-891-0414 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 3RD REVIEW |
| | DATE: FRI. MAY 13 19/2016 |
| | ACTION: DENIED |
| | |
| | NOTE: THIS REVIEW IS FOR THE LEASING/ RECREATION BLDG |
| | ONLYI, NOT FOR THE SITE PLAN, OR ANY ASSOCIATED |
| | AMENITIES. |
| | |
| | 1) CONTRACTOR TO BRING IN A EVALUATION BY A CPA. THE |
| | PERMIT APPLICATION VALUE OF $9,000,000.00 DOLLARS IS |
| | ACTUALLY HIGH IN RELATION TO THE AUGUST 2015 ICC |
| | VALUATION TABLES. THE MEP AND ROOFING PERMITS, ARE |
| | SUB-PERMITS AND IF NOT SUBMITTED AT THE TIME OF PERMIT |
| | ARE A $80.00 SUB-PERMIT AND ARE INCLUDED IN THE VALUE |
| | OF THE BUILDING COST. ALL OTHER SUB-PERMITS ARE FEED |
| | PERMITS. PLEASE PROVIDE A LIST OF ALL OTHER SUB-PERMITS |
| | FOR THE BUILDING, SUBMIT A LIST OF PERMITS AND |
| | BREAK-OUT THE VALUE FROM THE TOTAL COST TO DETERMINE |
| | THE FINAL VALUATION OF THE BUILDING PERMIT. |
| | |
| | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 2) COMPLIED. |
| | |
| | 2F) NOTICE ONLY, FOR PAPER PLANS 3 SETS OF DOCUMENTS |
| | ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE.. |
| | |
| | 2G) NOTICE ONLY, NO ACTION IS REQUIRED. PLEASE CALL THE |
| | CITY OF WEST PALM BEACHES AUTOMATED TELEPHONE |
| | INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING |
| | INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT |
| | THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF |
| | JOB, NO INSPECTION ACTIVITY. |
| | |
| | 2H) NOTICE ONLY, NO ACTION IS REQUIRED. 109.3.6 |
| | THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD |
| | INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED |
| | ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED |
| | FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 3) COMPLIED/ ADDRESSING |
| | |
| | 4) 3RD REQUEST. MISSING FROM THE SUPPORTING DOCUMENT |
| | FOLDER IS COMPLIANCE WITH: 2014 FBC-B 1803.5.2 |
| | QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH |
| | OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A |
| | LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| | PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| | BE CONDUCTED. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) SEMI-COMPLIED. SEE MECHANICAL COMMENTS. |
| | |
| | 7A-C) COMPLIED. |
| | |
| | 7D) PROVISO: THERE ARE NO ELEVATIONS OF THE BREAK ROOM. |
| | THERE ARE CONCERNS IF THERE WILL BE A MICROWAVE AND THE |
| | PLACEMENT OF THE UNIT FOR COMPLIANCE WITH REACH RANGES |
| | AND OPERABLE PARTS UNDER BOTH THE FAIR HOUSING AND |
| | FLORIDA ACCESSIBILITY CODE. |
| | REACH RANGES UNDER 308. |
| | OPERABLE PARTS 309. |
| | |
| | 8A) PROVISO: THE DESIGNER INDICATES 45 MIN. WINDOW, |
| | DOORS AND FRAMES. THE CONTRACTOR IN RESPONSE INDICATES |
| | THESE OPENINGS WILL HAVE PRODUCT TESTING FOR BOTH FIRE |
| | RESISTANCE RATING AND LARGE MISSILE IMPACT RESISTANCE |
| | TESTING. IF THE UNIT COST ARE TOO HIGH FOR THESE TYPE |
| | OF UNITS THEN FIRE RATED WINDOWS AND STORM SHUTTERS AND |
| | OR PANELS WILL BE REQUIRED. IF STORM PANELS ARE TO BE |
| | INSTALLED, THEN STORAGE WITHIN THE RECREATION CENTER |
| | WILL BE A REQUIREMENT. |
| | |
| | SHEET A3.01R THE RIGHT SIDE OR ELEVATION SHOWS THE |
| | WINDOWS AND DOORS AS PROTECTED, WINDOWS A 1 HOUR FIRE |
| | RATING AND THE DOORS 45 MINUTES. THE 2014 FBC-B TABLE |
| | 716.5 FOR EXTERIOR WALLS THAT REQUIRE A 1 HOUR FIRE |
| | RATING THE OPENING PROTECTIVE WILL ONLY REQUIRE 45 |
| | MINUTE PROTECTIVE. PLEASE INDICATE ON THE WINDOWS HOW |
| | THIS WILL BE ACCOMPLISHED, FIRE SHUTTERS, FIRE RATED |
| | GLAZING AND FRAME? ? PLEASE ALSO BE AWARE THAT THERE |
| | ARE VERY FEW WINDOWS THAT ARE TESTED FOR A FIRE RATING |
| | AS WELL AS LARGE MISSILE IMPACT TESTING. |
| | |
| | 8B) PROVISO: CONTRACTOR TO SUBMIT PRODUCT APPROVAL FOR |
| | ADHERED MASONRY VENEER PER FBC-B 1405.10 TO BE REVIEWED |
| | BY THE DESIGNER OF RECORD, SHOP DRAWING STAMP OF |
| | APPROVAL APPLIED BEFORE BEING SUBMITTED TO THE BUILDING |
| | DEPARTMENT. |
| | |
| | 9) COMPLIED. |
| | . |
| | 10A) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 10B) PROVISO: COMPONENTS & CLADDING. 2014 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 10C) PROVISO: 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 10D) PROVISO: FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIXE. |
| | |
| | 10E) PROVISO: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO |
| | RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA |
| | ARCHITECT OR ENGINEER. |
| | |
| | 10F) COMPLIED. SHEET A8.03 DETAIL # 1 AC/ COMPRESSORS |
| | BEING TIED DOWN TO CONCRETE PADS |
| | |
| | 11A) PROVISO: BAHAMA SHUTTERS TO PROVIDE SHOP DRAWINGS, |
| | PLEASE NOTE I UNDERSTAND THE INTENT IS TO LEAVE THESE |
| | AWNINGS IN THE OPEN POSITION IN A HIGH WIND EVENT. |
| | 2014 FBC-B 3105.4 DESIGN. 2014 FBC-B 3105.5 RIGID |
| | AWNINGS AND CANOPY SHUTTERS. |
| | |
| | 11B) COMPLIED, N/A. 2014 FBC-B 3105.3.3.1 FABRIC USED |
| | FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL MEET THE |
| | FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 OR |
| | HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 12) COMPLIED. |
| | |
| | 13)3RD REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 14) BEFORE PERMIT ISSUANCE CAN OCCUR ONE SET OF SIGNED |
| | AND SEALED DOCUMENTS (PLANS, SOILS REPORTS, & ENERGY |
| | CALCULATIONS) WILL BE SUBMITTED TO THE BUILDING |
| | DEPARTMENT FOR THE RECORD RETENTION PROGRAM AND |
| | REVIEWED WITH THE ELECTRONIC PLANS FOR ACCURACY AND |
| | CODE COMPLIANCE. |
| | |
| | 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |