Plan Review Notes
Plan Review Notes For Permit 16020377
Permit Number 16020377
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2016-04-07 14:36:35PERMIT # 16020377
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW
 APPROVED PROVISO:
  
 1) NO CORRECTIONS MADE ON THIS SHEET. CORRECTION AND
 COMPLIANCE WILL BE VERIFIED IN THE FIELD -- SHEET
 A2.00R - THE DOOR LEADING INTO THE RESTROOMS VESTIBULE
 AND THE DOOR FOR THE JANITOR'S CLOSET OPEN INTO
 EACHOTHER. CHANGE THE SWING DIRECTION FOR ONE OF THE
 TWO DOORS.
 NOTE: ALLOWABLE TRAVEL DISTANCE FOR A NON-SPRINKLERED
 BUILDING IS 200 FEET. NOTE ON SHEET INCORRECTLY STATES
 250 FEET.
  
 2) NO CORRECTIONS MADE ON THIS SHEET. COMPLIANCE WILL
 BE VERIFIED IN THE FIELD. - - SHEET A3.03R - STRUCTURES
 WITH LIGHT FRAME FLOOR/ROOF TRUSS CONSTRUCTION SHALL BE
 IDENTIFIED WITH A SIGN AFFIXED TO THE BUILDING. THE
 SIGN SHALL FEATURE A MALTESE CROSS 8-INCHES WIDE AND
 8-INCHES TALL AND BE OF A BRIGHT RED REFLECTIVE COLOR
 AND BEAR THE APPROPRIATE LETTER R/F/RF DESIGNATION PER
 FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE
 69A-60.0081.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  
  


Account Summary | Usage Policy | Privacy Policy