| 2016-04-19 12:34:07 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16020377 |
| | ADD: 7000 OKEECHOBEE BLVD. / LEASING & RECREATION BLDG. |
| | CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER |
| | TEL: 561-891-0414 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: TUES. APRIL 19/2016 |
| | ACTION: DENIED |
| | |
| | NOTE: THIS REVIEW IS FOR THE LEASING/ RECREATION BLDG |
| | ONLYI, NOT FOR THE SITE PLAN, OR ANY ASSOCIATED |
| | AMENITIES. |
| | |
| | 1) 2ND REQUEST. THE PERMIT APPLICATION VALUE OF |
| | $9,000,000.00 DOLLARS IS ACTUALLY HIGH IN RELATION TO |
| | THE AUGUST 2015 ICC VALUATION TABLES. THE MEP AND |
| | ROOFING PERMITS, ARE SUB-PERMITS AND IF NOT SUBMITTED |
| | AT THE TIME OF PERMIT ARE A $80.00 SUB-PERMIT AND ARE |
| | INCLUDED IN THE VALUE OF THE BUILDING COST. ALL OTHER |
| | SUB-PERMITS ARE FEED PERMITS. PLEASE PROVIDE A LIST OF |
| | ALL OTHER SUB-PERMITS FOR THE BUILDING, SUBMIT A LIST |
| | OF PERMITS AND BREAK-OUT THE VALUE FROM THE TOTAL COST |
| | TO DETERMINE THE FINAL VALUATION OF THE BUILDING |
| | PERMIT. |
| | |
| | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 2) PLEASE NOTE THIS BUILDING DOES NOT REQUIRE A |
| | THRESHOLD OR A RESIDENT INSPECTOR. PLEASE CONFIRM THAT |
| | THE CONTRACTOR IS GOING TO CALL IN INSPECTIONS FOR THE |
| | CITY INSPECTORS WILL BE DOING THE STRUCTURAL |
| | INSPECTIONS FOR THIS BUILDING OR WILL THE THRESHOLD |
| | INSPECTOR ALSO COMPLETE THE STRUCTURAL INSPECTIONS FOR |
| | THIS BUILDING AS WELL. |
| | |
| | THRESHOLD BUILDING BY STATE STATUTE, THRESHOLD BUILDING |
| | FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY |
| | BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) 2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN. |
| | THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) COMPLIED/ MAY 02/16.2ND REQUEST. THRESHOLD |
| | INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION |
| | SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY FL S S 553.79(5) |
| | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| | |
| | 2C)COMPLIED W.P.B. AMENDMENT 110.3.7.4./ 633 FLORIDA |
| | STATUTE. |
| | |
| | 2D) COMPLIED/ MAY 02/16. 2ND REQUEST. FOR THE SPECIAL |
| | INSPECTOR PLEASE PROVIDE A RESUME' OF INSPECTION |
| | EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' MUST BE |
| | ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED HEREIN. |
| | THE BUILDING OFFICIAL OR HIS DESIGNEE WILL REVIEW THE |
| | RESUME'. AFTER THE RESUME' IS REVIEWED, A INTERVIEW |
| | MAYBE SCHEDULED. UNDER NO CIRCUMSTANCES WILL AN |
| | INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING |
| | THE ABOVE CRITERIA. |
| | |
| | 2E) COMPLIED/ MAY 02/16. 2ND REQUEST. THE CONTRACTOR |
| | WILL PRODUCE A JOB SUMMARY OR HISTORY FOR THIS TYPE OF |
| | CONSTRUCTION. |
| | |
| | |
| | 2F) NOTICE ONLY, FOR PAPER PLANS 3 SETS OF DOCUMENTS |
| | ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE.. |
| | |
| | 2G)NOTICE ONLY, NO ACTION IS REQUIRED. PLEASE CALL THE |
| | CITY OF WEST PALM BEACHES AUTOMATED TELEPHONE |
| | INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING |
| | INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT |
| | THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF |
| | JOB, NO INSPECTION ACTIVITY. |
| | |
| | 2H) NOTICE ONLY, NO ACTION IS REQUIRED. 109.3.6 |
| | THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD |
| | INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED |
| | ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED |
| | FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 3) COMPLIED/ ADDRESSING |
| | |
| | 4) 2ND REQUEST. MISSING FROM THE SUPPORTING DOCUMENT |
| | FOLDER IS COMPLIANCE WITH: 2014 FBC-B 1803.5.2 |
| | QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH |
| | OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A |
| | LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| | PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| | BE CONDUCTED. |
| | |
| | 5A) 2ND REQUEST. MISSING FROM THE SUPPORTING DOCUMENT |
| | FOLDER IS A SURVEY. 2014 FLORIDA BUILDING CODE W 2014 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | SURVEY / FLOOD ZONE/ ASSUMED PROPERTY LINE |
| | |
| | 5B) COMPLIED. ASSUMED PROPERTY LINE BETWEEN THE VARIOUS |
| | BUILDINGS WITH THE PERCENTAGE OF ALLOWABLE OPENINGS |
| | |
| | 6) 2ND REQUEST. UNDER THE 2014 ENERGY CODE THIS |
| | BUILDING IS USING ASHRAE 90 FORMS FOR CODE COMPLIANCE. |
| | THE INPUT DATA REPORT ON PAGES 2 & 3 INDICATES THE USE |
| | OF ? INCH ISO BETWEEN ? INCH FURRING. PAGE 7 UNDER THE |
| | MATERIALS USED ALSO INDICATES THE USE OF 4.8/ 0.75 INCH |
| | ISO BETWEEN FURRING 24 INCHES ON CENTER. WHEREAS SHEET |
| | A.302R INDICATES R4.1 AL-FOIL INSULATION BETWEEN 1 X2 |
| | PT FURRING STRIPS. NOTE THERE IS A DISCREPANCY BETWEEN |
| | THE ENERGY CALCULATIONS AND THE WALL INSULATION |
| | INDICATED ON THE PLANS. |
| | |
| | 7A) COMPLIED. SHEET A2.00 R IS THE LIFE SAFETY PLAN FOR |
| | THE LEASING AND RECREATION CENTER. THE SHEET INDICATES |
| | UNDER THE OCCUPANCY TYPE AN A3 FOR THE RECREATION |
| | CENTER. THE LEASING AREA OF THE BUILDING IS |
| | APPROXIMATELY 936 SQ. FT. OR 0.18 % OF THE FLOOR PLATE |
| | MAKING THIS A MIXED USE OCCUPANCY BETWEEN AN A3 |
| | OCCUPANCY AND A BUSINESS OCCUPANCY. IN THE 2014 FBC-B |
| | TABLE 508.4 BETWEEN AN A3 AND BUSINESS OCCUPANCY |
| | REQUIRES 2 HOUR SEPARATION FOR NON-SPRINKLERED |
| | BUILDINGS. THE DESIGNER OF RECORD HAS NOT DECLARED IF |
| | THE PLANS WERE DEVELOPED AS SEPARATION OF |
| | OCCUPANCIES(508.2.4) OR NON-SEPARATED OCCUPANCIES |
| | (508.3). |
| | |
| | 7B) COMPLIED. THE RECREATION AND LEASING BUILDING WILL |
| | NOT ONLY NEED TO MEET THE REQUIREMENTS OF FAIR HOUSING |
| | BUT THE FBC-ACCESSIBILITY CODE AS WELL. THE FITNESS |
| | ROOM THE EXERCISE MACHINE AND EQUIPMENT WILL NEED TO |
| | MEET THE REQUIREMENTS OF FBC-ACCESSIBILITY CODE 1004.1. |
| | |
| | 7C) COMPLIED. KITCHEN/ BREAK ROOM SINK |
| | |
| | 7D) PROVISO: THERE ARE NO ELEVATIONS OF THE BREAK ROOM. |
| | THERE ARE CONCERNS IF THERE WILL BE A MICROWAVE AND THE |
| | PLACEMENT OF THE UNIT FOR COMPLIANCE WITH REACH RANGES |
| | AND OPERABLE PARTS UNDER BOTH THE FAIR HOUSING AND |
| | FLORIDA ACCESSIBILITY CODE. |
| | REACH RANGES UNDER 308. |
| | OPERABLE PARTS 309. |
| | |
| | 8A) SEMI-COMPLIED. DESIGNER WILL PROVIDE 45 MIN. WINDOW |
| | AND FRAMES. WILL NEED TO SUPPLY STORM SHUTTERS AS WELL. |
| | WILL THE BAHAMA STYLE SUN SHADE BE TESTED FOR HURRICANE |
| | IMPACT TESTING THAT CAN BE DROPPED INCASE OF A |
| | HURRICANE AS THE LARGE MISSILE RESISTANT COVERING? IS |
| | SO SUPPLY THE PRODUCT APPROVAL. |
| | |
| | SHEET A3.01R THE RIGHT SIDE OR ELEVATION SHOWS THE |
| | WINDOWS AND DOORS AS PROTECTED, WINDOWS A 1 HOUR FIRE |
| | RATING AND THE DOORS 45 MINUTES. THE 2014 FBC-B TABLE |
| | 716.5 FOR EXTERIOR WALLS THAT REQUIRE A 1 HOUR FIRE |
| | RATING THE OPENING PROTECTIVE WILL ONLY REQUIRE 45 |
| | MINUTE PROTECTIVE. PLEASE INDICATE ON THE WINDOWS HOW |
| | THIS WILL BE ACCOMPLISHED, FIRE SHUTTERS, FIRE RATED |
| | GLAZING AND FRAME? ? PLEASE ALSO BE AWARE THAT THERE |
| | ARE VERY FEW WINDOWS THAT ARE TESTED FOR A FIRE RATING |
| | AS WELL AS LARGE MISSILE IMPACT TESTING. |
| | |
| | 8B) PROVISO: CONTRACTOR TO SUBMIT PRODUCT APPROVAL FOR |
| | ADHERED MASONRY VENEER PER FBC-B 1405.10 TO BE REVIEWED |
| | BY THE DESIGNER OF RECORD, SHOP DRAWING STAMP OF |
| | APPROVAL APPLIED BEFORE BEING SUBMITTED TO THE BUILDING |
| | DEPARTMENT. |
| | |
| | 9) SHEET S-3 REC BUILDING NOTES. |
| | 9A)2ND REQUEST, THERE IS A BLOCKED OUT SQUARE WHERE THE |
| | CONSTRUCTION TYPE IS LOCATED. |
| | THE DESIGN PARAMETERS LIST THIS CONSTRUCTION AS |
| | BUILDING TYPE VB. WHEREAS THE LIFE SAFETY SHEET A2.00 |
| | INDICATES THE BUILDING TYPE IIIB. DISCREPANCY IN PLANS. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 9B) COMPLIED. |
| | 9C) COMPLIED. WIND DESIGN. |
| | 10A) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 10B) PROVISO: COMPONENTS & CLADDING. 2014 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 10C) PROVISO: 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 10D) PROVISO: FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIXE. |
| | |
| | 10E) PROVISO: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO |
| | RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA |
| | ARCHITECT OR ENGINEER. |
| | |
| | 10F) SHEET A8.03 DETAIL # 1 INDICATES AC/ COMPRESSORS |
| | BEING TIED DOWN TO CONCRETE PADS WITH 1 ? INCH HILTI |
| | POWER ACTUATED DRIVE PINS @ EACH CORNER THRU THE |
| | COMPRESSOR PAN. SHEET M4 SHOW A DIFFERENT TYPE OF TIE |
| | DOWN DISCREPANCY IN PLANS. |
| | |
| | 11A) 2ND REQUEST. SHEET A3.02 INDICATES AN AWNING |
| | DETAIL FOUND ON SHEET A8.01, THIS SHEET IS LOADED FOR |
| | THIS REVIEW BUT THERE IS NO DETAIL 06.PLEASE PROVIDE |
| | DOCUMENTATION AS TO IS THIS A FABRIC AWNING OR A RIGID |
| | FIXED AWNING? PLEASE PROVIDE TO WHICH DESIGN CRITERIA |
| | THE AWNING IS TO BE DESIGNED TOO? THE SHUTTER |
| | FABRICATOR NEEDS TO KNOW TO WHAT WIND SPEED THE SHUTTER |
| | DESIGN NEEDS TO MEET. IS THE DESIGN INTENT TO LEAVE THE |
| | SHUTTER OPEN IN THE FIXED POSITION IN THE EVENT OF A |
| | HIGH WIND EVENT |
| | 2014 FBC-B 3105.4 DESIGN. 2014 FBC-B 3105.5 RIGID |
| | AWNINGS AND CANOPY SHUTTERS. |
| | |
| | 11B) COMPLIED, N/A. 2014 FBC-B 3105.3.3.1 FABRIC USED |
| | FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL MEET THE |
| | FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 OR |
| | HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 12) COMPLIED. |
| | |
| | 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 14) BLUE LINE RAMP AND DECK MODULAR STRUCTURE PLAN IS |
| | NOT SIGNED NOR SEALED. PLANS, SPECIFICATIONS, REPORTS |
| | OR OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL |
| | AND BEING FILED FOR PUBLIC RECORD SHALL HAVE THE |
| | SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL ADMIN CODE 61G16.003 ARCHITECTS |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | |
| | 15) NEITHER THE ARCHITECTURAL SHEETS NOR THE STRUCTURAL |
| | SHEETS HAVE ELECTRONIC SIGNATURES. THE CITY NO LONGER |
| | ACCEPTS THE PEDDS SIGNATURE, 61G15-23.005 PROCEDURES |
| | FOR SIGNING AND SEALING ELECTRONICALLY TRANSMITTED |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL |
| | SIGNATURE TO SEAL ENGINEERING WORK SHALL HAVE THEIR |
| | IDENTITY AUTHENTICATED BY A CERTIFICATION AUTHORITY AND |
| | SHALL ASSURE THAT THE DIGITAL SIGNATURE IS: |
| | (A) UNIQUE TO THE PERSON USING IT; |
| | (B) CAPABLE OF VERIFICATION; |
| | (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; |
| | (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE |
| | ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE |
| | DOCUMENT ARE CHANGED. |
| | |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| | ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |