| 2016-02-27 05:19:39 | 1) AS DRAWN, THE SANITARY RISER FOR TOILET ROOMS #118 & | | | #119 DOES NOT COMPLY WITH THE 2014 FPC SEC. 912.1. ONLY | | | THE TYPE AND NUMBER OF FIXTURES IN THE BATHROOM GROUP | | | SHALL CONNECT TO THE HORIZONTAL WET VENT (SEE THE | | | DEFINITION OF "BATHROOM GROUP" IN THE DEFINITIONS). A | | | MAXIMUM OF 2 WATER CLOSETS AND 2 LAVATORIES ARE | | | PERMITTED ON THE WET VENT AND URINALS ARE NOT PERMITTED | | | ON THE WET VENT. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|