2016-02-26 08:12:161ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020377
 2/26/16
  
 1) SHEETS M1 & M2: THE VENTILATION SCHEDULE INDICATES
 342 CFM O/A FOR THE HEALTH CLUB/WEIGHT ROOM, HOWEVER
 AH/CU-1 SUPPLYING THAT AREA IS ONLY PROVIDING 200 CFM
 O/A AIR PER THE SCHEDULE. THERE IS ONE 350 CFM DIFFUSER
 FROM AH/CU-2 SUPPLYING THE AREA BUT IT DOES NOT APPEAR
 THE PERCENTAGE OF O/A FROM THAT DIFFUSER WOULD MAKE UP
 THE DIFFERENCE.
 2) M1 & M2: PLEASE CLARIFY WHY AH/CU- 2, 4, & 5 SHOWN
 IN THE AC SCHEDULE TO BE 3.5-TON SYSTEMS ARE ONLY
 PROVIDING APPROXIMATELY 2/3 (800 CFM EACH) OF THEIR
 RESPECTIVE 1100 CFM SUPPLY AIR CAPACITIES. PLEASE NOTE
 THAT THE 3-TON UNITS WILL SUPPLY UP TO 1000 CFM. IT
 APPEARS THAT THE 3.5 TON SYSTEMS MAY BE OVERSIZED.
 3) THE COMPLIANCE DATA FOR THE AC SYSTEMS LISTED IN THE
 SUBMITTED ENERGY CONSERVATION FORM CONFLICTS WITH THE
 AC EQUIPMENT SCHEDULE. THE FORM LISTS SYSTEM 1 AT 13
 SEER/ HOWEVER THE SCHEDULE INDICATES 14 SEER, FORM
 LISTS SYSTEM 5 AS BOTH THE 42,000 CAPACITY SYSTEM AND A
 6000 CAPACITY SYSTEM EACH AT 13 SEER. THE 6000 APPEARS
 TO BE A TYPO AND SHOULD BE CORRECTED TO 60,000. THE
 SCHEDULE LISTS THE 60,000 SYSTEM AT 13.25 SEER, AND
 LISTS 4- 46,200 CAPACITY SYSTEMS AT 14 SEER. PLEASE
 CORRECT ALL THESE CONFLICTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER