| 2016-02-26 08:12:16 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #16020377 |
| | 2/26/16 |
| | |
| | 1) SHEETS M1 & M2: THE VENTILATION SCHEDULE INDICATES |
| | 342 CFM O/A FOR THE HEALTH CLUB/WEIGHT ROOM, HOWEVER |
| | AH/CU-1 SUPPLYING THAT AREA IS ONLY PROVIDING 200 CFM |
| | O/A AIR PER THE SCHEDULE. THERE IS ONE 350 CFM DIFFUSER |
| | FROM AH/CU-2 SUPPLYING THE AREA BUT IT DOES NOT APPEAR |
| | THE PERCENTAGE OF O/A FROM THAT DIFFUSER WOULD MAKE UP |
| | THE DIFFERENCE. |
| | 2) M1 & M2: PLEASE CLARIFY WHY AH/CU- 2, 4, & 5 SHOWN |
| | IN THE AC SCHEDULE TO BE 3.5-TON SYSTEMS ARE ONLY |
| | PROVIDING APPROXIMATELY 2/3 (800 CFM EACH) OF THEIR |
| | RESPECTIVE 1100 CFM SUPPLY AIR CAPACITIES. PLEASE NOTE |
| | THAT THE 3-TON UNITS WILL SUPPLY UP TO 1000 CFM. IT |
| | APPEARS THAT THE 3.5 TON SYSTEMS MAY BE OVERSIZED. |
| | 3) THE COMPLIANCE DATA FOR THE AC SYSTEMS LISTED IN THE |
| | SUBMITTED ENERGY CONSERVATION FORM CONFLICTS WITH THE |
| | AC EQUIPMENT SCHEDULE. THE FORM LISTS SYSTEM 1 AT 13 |
| | SEER/ HOWEVER THE SCHEDULE INDICATES 14 SEER, FORM |
| | LISTS SYSTEM 5 AS BOTH THE 42,000 CAPACITY SYSTEM AND A |
| | 6000 CAPACITY SYSTEM EACH AT 13 SEER. THE 6000 APPEARS |
| | TO BE A TYPO AND SHOULD BE CORRECTED TO 60,000. THE |
| | SCHEDULE LISTS THE 60,000 SYSTEM AT 13.25 SEER, AND |
| | LISTS 4- 46,200 CAPACITY SYSTEMS AT 14 SEER. PLEASE |
| | CORRECT ALL THESE CONFLICTS. |
| | |