| 2016-03-03 10:33:11 | PERMIT # 16020377 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | FAILED COMMENTS: |
| | |
| | 1) THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. |
| | INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE |
| | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1 |
| | OF NFPA 101 FLORIDA EDITION 2009. FOR NON-SEPARATED |
| | MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE |
| | SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO |
| | THE BUILDING. |
| | |
| | 2) SHEET A2.00R - THE DOOR LEADING INTO THE RESTROOMS |
| | VESTIBULE AND THE DOOR FOR THE JANITOR'S CLOSET OPEN |
| | INTO EACHOTHER. CHANGE THE SWING DIRECTION FOR ONE OF |
| | THE TWO DOORS. |
| | |
| | 3) SHEET A3.03R - STRUCTURES WITH LIGHT FRAME |
| | FLOOR/ROOF TRUSS CONSTRUCTION SHALL BE IDENTIFIED WITH |
| | A SIGN AFFIXED TO THE BUILDING. THE SIGN SHALL FEATURE |
| | A MALTESE CROSS 8-INCHES WIDE AND 8-INCHES TALL AND BE |
| | OF A BRIGHT RED REFLECTIVE COLOR AND BEAR THE |
| | APPROPRIATE LETTER R/F/RF DESIGNATION PER FLORIDA |
| | STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE |
| | 69A-60.0081. |
| | |
| | 4) REVIEW AND RESPOND TO ALL PLAN REVIEWER COMMENTS AND |
| | MAKE CORRECTIONS AS NEEDED; TO INCLUDE BUILDING, |
| | ELECTRICAL, MECHANICAL, ETC. |
| | |
| | GENERAL NOTE: SHEET A2.00R INDICATES THAT FIVE (5) |
| | EXTINGUISHERS, SIZE 4A 30BC, ARE TO BE PROVIDED. THE |
| | REQUIRED SIZE IS 2A 10BC. YOU ARE WELCOMED TO PROVIDE |
| | LARGER ONES, SUCH AS A 4A 30BC, BUT IT IS NOT REQUIRED. |
| | |
| | |
| | SUE ELLEN CALDERON |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |