Plan Review Notes
Plan Review Notes For Permit 16020377
Permit Number 16020377
Review Stop B
Sequence Number 1
Notes
Date Text
2016-02-17 15:49:33BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020377
 ADD: 7000 OKEECHOBEE BLVD. / LEASING & RECREATION BLDG.
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. FEB. 17/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS FOR THE LEASING/ RECREATION BLDG
 ONLYI, NOT FOR THE SITE PLAN, OR ANY ASSOCIATED
 AMENITIES.
  
 1) THE PERMIT APPLICATION VALUE OF $9,000,000.00
 DOLLARS IS ACTUALLY HIGH IN RELATION TO THE AUGUST 2015
 ICC VALUATION TABLES. THE MEP AND ROOFING PERMITS, ARE
 SUB-PERMITS AND IF NOT SUBMITTED AT THE TIME OF PERMIT
 ARE A $80.00 SUB-PERMIT AND ARE INCLUDED IN THE VALUE
 OF THE BUILDING COST. ALL OTHER SUB-PERMITS ARE FEED
 PERMITS. PLEASE PROVIDE A LIST OF ALL OTHER SUB-PERMITS
 FOR THE BUILDING, SUBMIT A LIST OF PERMITS AND
 BREAK-OUT THE VALUE FROM THE TOTAL COST TO DETERMINE
 THE FINAL VALUATION OF THE BUILDING PERMIT.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 2) PLEASE NOTE THIS BUILDING DOES NOT REQUIRE A
 THRESHOLD OR A RESIDENT INSPECTOR. PLEASE CONFIRM THAT
 THE CONTRACTOR IS GOING TO CALL IN INSPECTIONS FOR THE
 CITY INSPECTORS WILL BE DOING THE STRUCTURAL
 INSPECTIONS FOR THIS BUILDING OR WILL THE THRESHOLD
 INSPECTOR ALSO COMPLETE THE STRUCTURAL INSPECTIONS FOR
 THIS BUILDING AS WELL.
  
 THRESHOLD BUILDING BY STATE STATUTE, THRESHOLD BUILDING
 FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 A INTERVIEW MAYBE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
  
 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
  
 2G)NOTICE ONLY, NO ACTION IS REQUIRED. PLEASE CALL THE
 CITY OF WEST PALM BEACH?S AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 2H) NOTICE ONLY, NO ACTION IS REQUIRED. 109.3.6
 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3) PLEASE NOTE THE SITE ADDRESS HAS BEEN PROVIDED AS
 7000 OKEECHOBEE BLVD. PLEASE CONTACT THE CITY?S
 ADDRESSING SPECIALIST FOR ADDRESSING CONCERNS, EITHER
 STREET NAMES OR NUMERICAL ADDRESSES TO IDENTIFY EACH
 BUILDING. CITY MUNI CODE SEC.78-6 (1-7).
 (2) LOCATION, BUILDINGS CONTAINING MORE THAN ONE
 ADDRESS. ALL ADDRESSES SHALL BE POSTED ON THAT PORTION
 OF THE STRUCTURE FRONTING OR FACING UPON THE STREET OR
 PRINCIPAL VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE
 READILY VISIBLE TO APPROACHING VEHICLES. OWNERS OR
 TENANTS OF ALL HOUSES AND BUILDINGS USING A SERVICE
 ALLEY SHALL ALSO POST A NUMBER ON THE SIDE OF THE
 BUILDINGS ADJACENT TO AND FACING SUCH ALLEY. IF THE
 HOUSE OR BUILDING IS OBSTRUCTED BY A FENCE, THEN THE
 NUMBER SHALL BE POSTED ON THE FENCE. THE PLACEMENT OF
 NUMBERS ON BUILDINGS OR FENCES, AS THE CASE MAY BE,
 SHALL BE SUBJECT TO THE DIRECTION OR APPROVAL OF THE
 CITY'S CONSTRUCTION SERVICES DEPARTMENT. BUILDINGS
 WHICH CONTAIN MORE THAN ONE RESIDENTIAL, COMMERCIAL,
 INDUSTRIAL, OR INSTITUTIONAL ADDRESS SHALL POST A
 SEPARATE ADDRESS MEETING THE REQUIREMENTS OF THIS
 SECTION AT THE EXTERIOR ENTRANCE TO EACH INDIVIDUAL
 ADDRESS OR COMMON EXTERIOR ENTRANCE TO SEVERAL
 ADDRESSES THEREIN, AND THE UNIT NUMBER SHALL ALSO BE
 POSTED ON THE EXTERIOR DOOR OF EACH UNIT SERVED BY SUCH
 A COMMON EXTERIOR ENTRANCE.
 (3) MONUMENT SIGNS. ALL MONUMENT SIGNS FOR MULTIPLE
 RESIDENTIAL, COMMERCIAL, INDUSTRIAL, OR INSTITUTIONAL
 DEVELOPMENTS SHALL POST THE ADDRESS RANGE FOR THE
 DEVELOPMENT. THE POSTED ADDRESS RANGE SHALL MEET THE
 REQUIREMENTS OF THIS SECTION.
  
 CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/
 INFORMATION TECHNOLOGY
 TEL: 561-494-1040
  
 4) MISSING FROM THE SUPPORTING DOCUMENT FOLDER IS
 COMPLIANCE WITH: 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5A) MISSING FROM THE SUPPORTING DOCUMENT FOLDER IS A
 SURVEY. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 SURVEY / FLOOD ZONE/ ASSUMED PROPERTY LINE
  
 5B) MISSING FROM THE PLANS IS A SITE PLAN THAT SHOWS
 THE ASSUMED PROPERTY LINE BETWEEN THE VARIOUS BUILDINGS
 WITH THE PERCENTAGE OF ALLOWABLE OPENINGS. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 SURVEY / FLOOD ZONE/ ASSUMED PROPERTY LINE
  
 6) UNDER THE 2014 ENERGY CODE THIS BUILDING IS USING
 ASHRAE 90 FORMS FOR CODE COMPLIANCE. THE INPUT DATA
 REPORT ON PAGES 2 & 3 INDICATES THE USE OF ? INCH ISO
 BETWEEN ? INCH FURRING. PAGE 7 UNDER THE MATERIALS USED
 ALSO INDICATES THE USE OF 0.75 INCH ISO BETWEEN FURRING
 24 INCHES ON CENTER. WHERE AS SHEET A.302R INDICATES
 R4.1 AL-FOIL INSULATION BETWEEN 1 X3 PT FURRING STRIPS.
 NOTE THERE IS A DISCREPANCY BETWEEN THE ENERGY
 CALCULATIONS AND THE WALL INSULATION INDICATED ON THE
 PLANS.
  
 7A) SHEET A2.00 R IS THE LIFE SAFETY PLAN FOR THE
 LEASING AND RECREATION CENTER. THE SHEET INDICATES
 UNDER THE OCCUPANCY TYPE AN A3 FOR THE RECREATION
 CENTER. THE LEASING AREA OF THE BUILDING IS
 APPROXIMATELY 936 SQ. FT. OR 0.18 % OF THE FLOOR PLATE
 MAKING THIS A MIXED USE OCCUPANCY BETWEEN AN A3
 OCCUPANCY AND A BUSINESS OCCUPANCY. IN THE 2014 FBC-B
 TABLE 508.4 BETWEEN AN A3 AND BUSINESS OCCUPANCY
 REQUIRES 2 HOUR SEPARATION FOR NON-SPRINKLERED
 BUILDINGS. THE DESIGNER OF RECORD HAS NOT DECLARED IF
 THE PLANS WERE DEVELOPED AS SEPARATION OF
 OCCUPANCIES(508.2.4) OR NON-SEPARATED OCCUPANCIES
 (508.3).
  
 7B) THE RECREATION AND LEASING BUILDING WILL NOT ONLY
 NEED TO MEET THE REQUIREMENTS OF FAIR HOUSING BUT THE
 FBC-ACCESSIBILITY CODE AS WELL. THE FITNESS ROOM THE
 EXERCISE MACHINE AND EQUIPMENT WILL NEED TO MEET THE
 REQUIREMENTS OF FBC-ACCESSIBILITY CODE 1004.1.
  
 7C) THIS SHEET SHOWS A KITCHEN/ BREAK ROOM. THE PLANS
 DO NOTE THAT THE SINK WILL BE LOCATED IN THE COUNTER
 TOP AT 34 INCHES ABOVE FLOOR LEVEL. THERE ARE NO OTHER
 DETAILS TO SHOW COMPLIANCE WITH FAIR HOUSING NOR THE
 FLORIDA ACCESSIBILITY CODE.
  
 7D) THERE ARE NO ELEVATIONS OF THE BREAK ROOM. THERE
 ARE CONCERNS IF THERE WILL BE A MICROWAVE AND THE
 PLACEMENT OF THE UNIT FOR COMPLIANCE WITH REACH RANGES
 AND OPERABLE PARTS UNDER BOTH THE FAIR HOUSING AND
 FLORIDA ACCESSIBILITY CODE.
 REACH RANGES UNDER 308.
 OPERABLE PARTS 309.
  
 8A) SHEET A3.01R THE RIGHT SIDE OR ELEVATION SHOWS THE
 WINDOWS AND DOORS AS PROTECTED, WINDOWS A 1 HOUR FIRE
 RATING AND THE DOORS 45 MINUTES. THE 2014 FBC-B TABLE
 716.5 FOR EXTERIOR WALLS THAT REQUIRE A 1 HOUR FIRE
 RATING THE OPENING PROTECTIVE WILL ONLY REQUIRE 45
 MINUTE PROTECTIVE. PLEASE INDICATE ON THE WINDOWS HOW
 THIS WILL BE ACCOMPLISHED, FIRE SHUTTERS, FIRE RATED
 GLAZING AND FRAME? ? PLEASE ALSO BE AWARE THAT THERE
 ARE VERY FEW WINDOWS THAT ARE TESTED FOR A FIRE RATING
 AS WELL AS LARGE MISSILE IMPACT TESTING.
  
 8B) SHEET A3.01R & A3.02R BOTH INDICATE THE USE OF
 CULTURED STONE. THERE IS A NOTE ON THE PLANS STONE
 VENEER BY CULTURED STONE LEDGE STONE VENEER TYPE. THIS
 PRODUCT HAS CODE COMPLIANCE EVALUATION AND LISTING,
 TEST ICC-ESESR-1364. PLEASE SUBMIT REPORT TO VERIFY
 COMPLIANCE WITH EITHER 1405.7 STONE VENEERS/ ANCHORED
 OR 1405.10 ADHERED MASONRY VENEERS. TO BE REVIEWED BY
 THE DESIGNER OF RECORD BEFORE BEING SUBMITTED TO THE
 BUILDING DEPARTMENT.
  
 9) SHEET S-2 REC BUILDING NOTES.
 9A) THE DESIGN PARAMETERS LIST THIS CONSTRUCTION AS
 BUILDING TYPE VB. WHEREAS THE LIFE SAFETY SHEET A2.00
 INDICATES THE BUILDING TYPE IIIB. DISCREPANCY IN PLANS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 9B) THE DESIGN PARAMETERS AND ASSUMPTIONS LIST THE
 OCCUPANCY CLASSIFICATION AS R-3. NOTE THIS IS A MIXED
 USE OCCUPANCY A3/B.
  
 9C) NO WIND LOAD CHART HAS BEEN PROVIDED FOR ZONES
 1,2,3, 4 & 5. PLEASE PROVIDE THE POSITIVE AND NEGATIVE
 PRESSURES IN VASD SINCE THE PRODUCT APPROVALS ARE GIVEN
 IN VASD. PLEASE PROVIDE CALCULATIONS (STATING VASD) FOR
 10 SQ. FT., 20 SQ. FT., 50 SQ. FT. & 100 SQ. FT. 2014
 FBC-B 1603.1.4 WIND DESIGN DATA, WIND DESIGN PRESSURES.
  
 10A) MISSING FROM THE SUBMITTED DOCUMENT FILE WERE
 PRODUCT APPROVAL DOCUMENTS. EITHER THE DESIGNER OF
 RECORD OR CONTRACTOR CAN SUBMIT THE PRODUCT APPROVAL
 DOCUMENTS OR ELECT TO HAVE THESE DOCUMENTS BE
 CONSIDERED AS A DEFERRED SUBMITTAL. IF THEY PREFER THE
 PRODUCT APPROVALS TO BE DEFERRED SUBMITTALS THEY MUST
 STATE SO IN THE RESPONSE NARRATIVE.
  
 10B) COMPONENTS & CLADDING. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 10C) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING
 BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 10D) FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIXE.
  
 10E) FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED. IF SO RAS 117
 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA ARCHITECT
 OR ENGINEER.
  
 10F) FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF DECK AS WELL AS FROM
 THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2014
 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 11A) SHEET A3.02 INDICATES A AWNING DETAIL FOUND ON
 SHEET A8.01, THERE IS NO SUCH SHEET IN THIS SET OF
 DRAWINGS. PLEASE PROVIDE DOCUMENTATION AS TO IS THIS A
 FABRIC AWNING OR A RIGID FIXED AWNING? PLEASE PROVIDE
 TO WHICH DESIGN CRITERIA THE AWNING IS TO BE DESIGNED
 TOO?
 2014 FBC-B 3105.4 DESIGN.
 2014 FBC-B 3105.5 RIGID AWNINGS AND CANOPY SHUTTERS.
  
 11B) 2014 FBC-B 3105.3.3.1 FABRIC USED FOR AWNINGS OR
 FABRIC-COVERED FRAMES SHALL MEET THE FLAME PROPAGATION
 PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD
 INDEX NOT GREATER THAN 25 WHEN TESTED IN ACCORDANCE
 WITH ASTM E 84 OR UL 723.
  
 12) SHEET S-4 DETAIL C SHOWS A DOUBLE LEDGER TO BE
 ATTACHED TO THE BLOCK WALL WITH FILED CELLS.
 12A) THE PLANS DO NOT PROVIDE WHAT SIZE OF LUMBER THE
 LEDGER SHOULD BE NOR THE TYPE OF WOOD, SPECIES, & GRADE
 ? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 12B) THIS SAME DETAIL INDICATES THE LEDGER BE FASTENED
 TO THE FILED CELL BLOCK WALL, BUT MISSING THE TYPE OF
 ANCHOR, DIAMETER & LENGTH, AND AT WHAT CENTER TO CENTER
 ARE THEY TO BE PLACED. THE PLANS ALSO FAIL TO INDICATE
 THE LOCATION OF THE ANCHOR IN REGARDS TO THE FRAMING
 MEMBER, UPPER 1/3RD, CENTERED OR IN THE LOWER 1/3RD OR
 STAGGERED? ADDITIONAL INFORMATION IS REQUIRED.
 107.2.1.3.
  
 12C) THE TYPICAL CUT SECTION THROUGH A 1 STORY
 STRUCTURE LOWER RIGHT CORNER OF THE SHEET INDICATES
 19/32 EXPOSURE1, EXTERIOR GRADE PLYWOOD
 SHEATHING(OPTION OSB).
 PLEASE REVIEW 2014 FLORIDA BUILDING CODE W 2014 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  