| 2016-03-16 16:25:20 | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. MARCH 16/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST/ SEMI COMPLIED. THE PERMIT APPLICATION |
| | INDICATES THE WORK TO BE PREFORMED UNDER THIS PERMIT IS |
| | TO INSTALL A WINDOW AND SHUTTER. THE FLOOR PLAN |
| | SUBMITTED INDICATES THERE IS A NEW WINDOW(NON-IMPACT/ |
| | NO STORM SHUTTER SUBMITTED FOR THIS OPENING, AND A |
| | SHUTTER UNDER FOR A SEPARATE OPENING, WHAT APPEARS TO |
| | BE A DOOR ONTO A PATIO. PLEASE PROVIDE THE SIZE OF EACH |
| | OF THE OPENINGS (WINDOW AND DOOR) ON THE FLOOR PLAN. |
| | THE WINDOW IS THIS A REPLACEMENT SAME SIZE SAME TYPE OF |
| | WINDOW? PLEASE NOTE THIS IS NOT A SINGLE FAMILY |
| | RESIDENCE BUT A CONDOMINIUM.107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 2) THE ENGINEERING EXPRESS SHEET SUBMITTED WILL NEED TO |
| | HAVE A ELECTRONIC SIGNATURE TO BE A VALID ENGINEERING |
| | SHEET. THE SUBMITTED ENGINEERING SHEET IS FOR THE MORE |
| | RESTRICTIVE "D" EXPOSURE WITH ASSOCIATED HIGHER |
| | PRESSURES, PLEASE PROVIDE WHAT THE MEAN ROOF HEIGHT OF |
| | THIS BUILDING? |
| | |
| | WIND DESIGN REQUIREMENTS. 2014 FBC-B 1603.1.4 WIND |
| | DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 2.2. RISK CATEGORY. |
| | |
| | 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | |
| | 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 3)SEMI-COMPLIED. UNTIL THE ABOVE COMMENTS ARE SATISFIED |
| | THE PRESSURES CAN NOT BE VALIDATED. SUBMIT PRODUCT |
| | APPROVALS FOR WINDOWS AND SHUTTERS. 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31) (B) WINDOWS |
| | (E) SHUTTERS |
| | |
| | 4) )SEMI-COMPLIED. UNTIL THE ABOVE COMMENTS ARE |
| | SATISFIED THE PRESSURES CAN NOT BE VALIDATED. STORM |
| | SHUTTERS: PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC |
| | ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT |
| | GLAZING. FBC 1609.1.2. FL BLD CODE 2010 SECTION |
| | 107.2.5.,1609.1.2, 1715.8 & EXIST BUILD CODE 606.4 |
| | PROCEDURES: A COMPLETE INSTALLATION SCHEDULE |
| | SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS, |
| | UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR |
| | REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT |
| | TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT |
| | APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |