| 2017-01-09 13:57:43 | RESIDENTIAL (R3) ALTERATION, FOURTH MECHANICAL REVIEW |
| | CHECKLIST. |
| | CODE: FBC, 5TH EDITION (2014). |
| | |
| | |
| | NOTE: |
| | ENGINEER OF RECORD MAY BE CHARGED 4 TIMES THE PLAN |
| | REVIEW FEE AS REQUIRED BY SEC. 553.80(2)(B) FLORIDA |
| | STATUTE. |
| | |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE EQUIPMENT SIZING CALCULATIONS. SPECIFY |
| | MANUFACTURER AND MODEL NUMBER AS REQUIRED BY SEC. |
| | R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| | |
| | 2- DRAWING M-1 SUBMITTED: |
| | A) LIST THE EQUIPMENT SPECIFIED ON THE EQUIPMENT SIZING |
| | CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| | |
| | B) ENGINEER OF RECORD TO CLARIFY HOW HE IS SPECIFYING |
| | THE CFM'S FOR EACH SUPPLY REGISTER IF THE SIZE OF THE |
| | EQUIPMENT IS NOT PROVIDED. EQUIPMENT MAY NOT BE |
| | ADEQUATE TO PROVIDE THE SPECIFIED CFM'S. COORDINATE |
| | CFM'S WITH THE EQUIPMENT SIZING CALCULATIONS. SEC. |
| | R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | C) FOOTPRINT OF FLOOR PLANS DON'T MATCH FOOTPRINT OF |
| | PLANS SHOWN ON SHEE A-1/3. PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS SHOWING THE CONSTRUCTION THE OF A/C |
| | SHAFT AS SHOWN ON PLANS. NOTE: NEED TO REVISE PLANS AND |
| | EXTERIOR ELEVATIONS TO SHOW THE NEW A/C SHAFT. SEC. |
| | R301.1 FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | D) CLARIFY SIZE OF A/C GRILLES SPECIFIED ON PLANS. WHY |
| | THE GRILLES ARE SPECIFIED WITH 3 NUMBERS. WHAT ARE |
| | THEY?. PROVIDE TYPICAL DETAIL SHOWING SPECIFIED SIZES. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD |
| | DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. |
| | |