| 2017-01-05 15:41:49 | RESIDENTIAL (R3) ALTERATION, FOURTH BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC, 5TH EDITION (2014). |
| | |
| | NEW COMMENT: |
| | 1- ENERGY CALCULATIONS SUBMITTED NOW REVISED THE ATTIC |
| | VENTILATION RATIO FROM 1/150 TO 1/300. ENGINEER OF |
| | RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| | SHOWING HOW THE HOUSE COMPLIES WITH THE 1/300 |
| | VENTILATION RATIO. SEE THE EXCEPTION ON SEC. R806.2 FOR |
| | THE MINIMUM CRITERIA REQUIRED TO COMPLY WITH THE 1/300 |
| | VENTILATION RATIO AND PROVIDE DETAILS AND |
| | SPECIFICATIONS. SEC. R103.2 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). NOTE: COORDINATE WITH THE PERSON |
| | PREPARING THE ENERGY CALCULATIONS. |
| | |
| | 2- SHEET A-2/2: |
| | A) NORTH ELEVATION SHOWS TWO DIFFERENT KIND OF WINDOWS |
| | ON THE SECOND FLOOR. REVISE AS REQUIRED TO MATCH |
| | SPECIFICATIONS ON FLOOR PLAN ON SHEET A-1/3. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | B) WEST ELEVATION SHOWS TWO DIFFERENT TYPES OF SIDING: |
| | HARDIE BOARD SIDING AND CEDAR SIDING. REVISE AS |
| | REQUIRED. SPECIFY ONLY ONE TYPE OF SIDING. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | 3- ENERGY CALCULATIONS SUBMITTED: |
| | A) NEED THE OWNER'S OR OWNER'S LEGALLY AUTHORIZED AGENT |
| | CERTIFICATION AT THE BOTTOM OF THE FORM AS REQUIRED BY |
| | SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. NO ADDRESSED AT ALL. |
| | |
| | B) ENERGY CALCULATIONS WERE PREPARED BY ANOTHER PERSON. |
| | PROVIDE THE NAME OF THE INDIVIDUAL WHO PREPARED THE |
| | ENERGY CALCULATIONS AS REQUIRED BY SEC. R405.4.2 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED AT ALL. NEED THE NAME OF |
| | THE PERSON WHO PREPARED THE ENERGY CALCULATIONS NOT |
| | JUST THE SIGNATURE |
| | |
| | C) REVISE ORIENTATION OF DOORS ON PAGE 3 OF 4. SEC. |
| | R101. 5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. THERE ARE NO DOORS ON THE NORTH SIDE. |
| | SEE DRAWING A-2/2 AND REVISE AS REQUIRED. |
| | |
| | NEW COMMENTS: |
| | D) THE ATTIC VENTILATION RATIO WAS CHANGED ON PAGE 2 OF |
| | 4. THE NEW VENT RATIO SPECIFIES 1/300 RATIO. SEC. |
| | R806.2 FBC-RESIDENTIAL REQUIRES 1/150 MIN. VENTILATION |
| | RATIO. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| | SHOWING HOW THE HOUSE COMPLIES WITH THE 1/300 |
| | VENTILATION RATIO. SEE EXCEPTION ON SEC. R806.2 FOR THE |
| | MINIMUM CRITERIA REQUIRED TO COMPLY WITH THE 1/300 |
| | VENTILATION RATIO. NOTE: COORDINATE WITH PLANS |
| | SUBMITTED. |
| | |
| | E) ENERGY CALCULATIONS SUBMITTED SHOW GARAGE |
| | INFORMATION ON PAGE 3 OF 4. THERE IS NOT GARAGE IN THIS |
| | HOUSE. REVISE AS REQUIRED. SEC. R101. 5.1.1.2 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | NOTE: |
| | LABEL FOR WINDOWS AND DOORS U-FACTOR AND SHGC FACTOR |
| | SPECIFIED ON THE ENERGY CALCULATIONS WILL BE REQUIRED |
| | AT TIME OF INSPECTION WHEN THE ENERGY CALCULATIONS ARE |
| | NOT USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY |
| | MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| | |
| | B) OUTSWING EXTERIOR DOORS AS SHOWN ON PLANS. |
| | RESPONSE: |
| | REPEAT COMMENT. JELD -WEN DRAWINGS SUBMITTED NOW |
| | (NI006794D-R3) STILL DON'T MEET THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER OF RECORD ON SHEET A-1/3. |
| | ALSO, THESE DOORS DON'T MATCH DOORS SHOWN ON PLANS AND |
| | ELEVATIONS. AND FINALLY DRAWINGS SUBMITTED DON'T HAVE A |
| | FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO |
| | DRAWINGS SUBMITTED. SUBMIT FLORIDA OR MIAMI-DADE NOA |
| | PRODUCT APPROVAL FOR SINGLE OUTSWING EXTERIOR DOORS AS |
| | SHOWN ON PLANS (SOLID, WITHOUT GLAZING) THAT MEETS THE |
| | DESIGN PRESSURES CALCULATED BY THE ENGINEER OF RECORD. |
| | |
| | C) SINGLE HUNG WINDOWS. |
| | RESPONSE: |
| | REPEAT COMMENT. MI WINDOWS & DOORS DRAWINGS SUBMITTED |
| | NOW (08-02544) STILL DON'T MEET THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER OF RECORD ON SHEET A-1/3. |
| | ALSO, DRAWINGS SUBMITTED DON'T HAVE A FLORIDA PRODUCT |
| | APPROVAL COVER PAGE THAT CORRESPONDS TO DRAWINGS |
| | SUBMITTED. SUBMIT FLORIDA OR MIAMI-DADE NOA PRODUCT |
| | APPROVAL FOR SINGLE HUNG WINDOWS THAT MEET THE DESIGN |
| | PRESSURES CALCULATED BY THE ENGINEER OF RECORD. |
| | NOTE: ORIGINALLY NOA 13-0430.09 WAS SUBMITTED FOR |
| | SINGLE HUNG WINDOWS. THIS NOA WAS ALREADY APPROVED. |
| | CLARIFY IF USING THE NOA THAT WAS ALREADY APPROVED OR |
| | IF NEW PRODUCT APPROVAL L WILL BE PROVIDED. DISCARD |
| | PRODUCT APPROVALS THAT WILL NOT BE USED. |
| | |
| | D) CASEMENT EGRESS WINDOWS AS SPECIFIED ON PLANS. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD |
| | DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. |
| | |