| 2016-11-02 16:15:46 | RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC, 5TH EDITION (2014). |
| | |
| | 1- ENERGY CALCULATIONS SUBMITTED: |
| | A) NEED THE OWNER/AGENT CERTIFICATION AT THE BOTTOM OF |
| | THE FORM AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. NO ADDRESSED. |
| | |
| | B) ENERGY CALCULATIONS WERE PREPARED BY ANOTHER PERSON. |
| | PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE |
| | COMPLIANCE REPORT AS REQUIRED BY SEC. R405.4.2 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | C) ITEM #15 IS TAKING THE CROSS VENTILATION CREDIT. |
| | PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW |
| | COMPLYING WITH THE CROSS VENTILATION AS REQUIRED BY |
| | SEC. R405.7.4 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | D) DOORS ON PAGE 3 OF 4 SHOW (2) 6'X 8 INSULATED DOORS. |
| | WHERE ARE THESE DOORS LOCATED ON PLANS. REVISED AS |
| | REQUIRED TO MATCH PLANS. ALSO, SEE PLANS AND DOOR |
| | PRODUCT APPROVALS SUBMITTED. R101. 5.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. INFORMATION WAS NOT |
| | CHANGED. WHERE ARE THESE DOORS LOCATED ON PLANS? . |
| | ALSO, SEE PLANS FOR CORRECT ORIENTATION OF EXTERIOR |
| | DOORS. REVISE AS REQUIRED TO MATCH PLANS AND PRODUCT |
| | APPROVALS SUBMITTED. |
| | |
| | E) WINDOWS INFORMATION ON PAGE 3 OF 4 SHOWS VINYL |
| | WINDOWS. THIS DOESN'T MATCH PRODUCT APPROVALS |
| | SUBMITTED. REVISE AS REQUIRED. SEE PRODUCT APPROVALS |
| | SUBMITTED. SEC. R101. 5.1.1.2 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | RESPONSE: |
| | NEW SINGLE HUNG FLORIDA PRODUCT APPROVAL FL14911.23 WAS |
| | SUBMITTED. NOTE: HISTORIC MAY NOT ALLOW VINYL WINDOWS. |
| | THIS WILL BE VERIFIED WITH HISTORIC. ON THE OTHER HAND, |
| | THERE WAS NOT PRODUCT APPROVAL SUBMITTED FOR THE NEW |
| | HORIZONTAL SLIDER WINDOWS SPECIFIED FOR THE SECOND |
| | FLOOR EGRESS WINDOWS. THEREFORE, UNABLE TO VERIFY IF |
| | THEY ARE GOING TO BE VINYL OR ALUMINUM. |
| | |
| | F) THE AIR BARRIER AND INSULATION INSPECTION COMPONENT |
| | CRITERIA CHECKLIST SUBMITTED WAS NOT COMPLETES. NEED TO |
| | BE COMPLETED. SEC. R405.4.2 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | |
| | G) PROVIDE COMPLETE EPL DISPLAY CARD AS REQUIRED BY |
| | SEC. R405.4.3 (1) FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | H) PROVIDE THE CORRECT CORRECT NAME OF THE BUILDER ON |
| | THE FRONT PAGE OF THE ENERGY CALCULATIONS. NOTE: ENERGY |
| | CALCULATIONS NAME "OWNER" AS THE BUILDER. "OWNER" IS |
| | NOT A BUILDER. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | NOTE: |
| | LABEL FOR WINDOWS AND DOORS U-FACTOR AND SHGC FACTOR |
| | SPECIFIED ON THE ENERGY CALCULATIONS WILL BE REQUIRED |
| | WHEN THE ENERGY CALCULATIONS ARE NOT USING THE SOFTWARE |
| | DEFAULT FACTOR FOR GLAZING. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY |
| | MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. THERE ARE WINDOW |
| | MULLIONS ON DINING ROOM AREA AND STORAGE AREA. SEE |
| | PLANS. |
| | |
| | B) OUTSWING EXTERIOR DOORS AS SHOWN ON PLANS. |
| | RESPONSE: |
| | DRAWINGS SUBMITTED WITH FLORIDA PRODUCT APPROVAL |
| | FL13540-R3 DON'T MEET THE DESIGN PRESSURES CALCULATED |
| | BY THE ENGINEER OF RECORD ON SHEET A-1/3. NEED PRODUCT |
| | APPROVAL FOR DOORS THAT MEET THE CALCULATED DESIGN |
| | PRESSURES. |
| | |
| | C) SINGLE HUNG WINDOWS. |
| | RESPONSE: |
| | NEW SINGLE HUNG FLORIDA PRODUCT APPROVAL FL14911.23 WAS |
| | SUBMITTED. THIS PRODUCT APPROVAL DOESN'T MEET THE |
| | DESIGN PRESSURES CALCULATED BY THE ENGINEER OF RECORD |
| | ON SHEET A-1/3. NEED PRODUCT APPROVAL FOR WINDOWS THAT |
| | MEET THE CALCULATED DESIGN PRESSURES. |
| | NOTE: HISTORIC MAY NOT ALLOW VINYL WINDOWS. THIS WILL |
| | BE VERIFIED WITH HISTORIC. |
| | NOTE: ORIGINALLY NOA 13-0430.09 WAS SUBMITTED FOR |
| | SINGLE HUNG WINDOWS. THIS NOA WAS ALREADY APPROVED. |
| | CLARIFY IF USING THE NOA THAT WAS ALREADY APPROVED OR |
| | IF NEW PRODUCT APPROVAL L WILL BE PROVIDED. DISCARD |
| | PRODUCT APPROVALS THAT WILL NOT BE USED. |
| | |
| | D) HORIZONTAL SLIDER WINDOWS. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | NOTE: PLEASE MAKE SURE SUBMITTED PRODUCT APPROVAL MEETS |
| | THE DESIGN PRESSURES AS SPECIFIED BY THE ENGINEER OF |
| | RECORD ON THE REVISED DRAWINGS. ALSO: CONFIRM WITH |
| | HISTORIC IF HORIZONTAL SLIDER WINDOWS ARE ALLOWED. |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD |
| | DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. |
| | |