| 2016-06-30 10:51:30 | RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW |
| | CHECKLIST. |
| | CODE: FBC, 5TH EDITION (2014). |
| | |
| | |
| | NOTE: |
| | CONTRACTOR MAY SUBMIT COMPLETE HVAC INFORMATION UNDER A |
| | SEPARATE PERMIT. PLEASE ADVICE IF RE-SUBMITTING ALL THE |
| | REQUIRED INFORMATION NOW OR IF ALL THE INFORMATION WILL |
| | BE SUBMITTED BY THE MECHANICAL CONTRACTOR UNDER A |
| | SEPARATE PERMIT. |
| | |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE EQUIPMENT SIZING CALCULATIONS. SPECIFY |
| | MANUFACTURER AND MODEL NUMBER AS REQUIRED BY SEC. |
| | R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 2- DRAWING M-1 SUBMITTED: |
| | ORIGINAL COMMENT: |
| | A) LIST THE EQUIPMENT SPECIFIED ON THE EQUIPMENT SIZING |
| | CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | B) SPECIFY THE CFM'S FOR EACH GRILL SHOWN ON PLAN. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | RESPONSE: |
| | REVISED PLAN SUBMITTED DOESN'T SHOW THE DUCT SIZES AND |
| | LOCATION. NEED TO SHOW ALL DUCTWORK. |
| | NOTE: BALANCE RETURN AIR REQUIREMENTS WILL BE REVIEWED |
| | ONCE THE DUCTWORK IS PROVIDED. |
| | |
| | ORIGINAL COMMENT: |
| | C) LABEL EACH FLOOR. FIRST AND SECOND FLOOR. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | RESPONSE; |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD |
| | DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. |
| | |